The Turkish Fire Regulation (Regulation on the Fire Protection of Buildings, BYKHY) was published in the Official Gazette No. 26735 of 19 December 2007; it consists of 12 parts and 171 articles. The articles on escape routes, compartments and building types set a fire door's rating, smoke-tightness, self-closing and dimensions. This page sets a plain summary of each article side by side with the official text. This English text is an unofficial translation for information; only the Turkish text published in the Official Gazette is legally binding.

Fire protection regulation Turkey – glazed separation in a public building corridor
Corridor separated in line with the Regulation
Official Gazette
19.12.2007 · 26735
Decision number
2007/12937
Building
12 parts · 171 articles
Latest addition
Provisional Article 4 · 1.7.2025
On this page
163 article summaries

Download PDF

Download the Regulation

The complete official text or a guide to the door and glass articles. Both are free; no form to fill in.

PDFOfficial text · full version

Turkish Regulation on Fire Protection of Buildings (BYKHY)

105 pages894 KBText: 1 July 2025

  • Unaltered official text, with a reference cover page at the front
  • 171 articles, including Provisional Article 4 of 2025

PDFAbay guide · doors and glass

Fire doors and glass partitions: what does the Regulation require?

8 pages739 KBNovember 2026

  • 14 locations in one table: which door, where, how many minutes
  • Size, opening direction, lock and force requirements for the door
  • A 7-point checklist for handover

The official text is the binding one; both files are updated when the Regulation changes.

01 Article finder

Find the article you need, including the fire escape stair rules

Choose the topic, whether the building is new or existing, and your role; you can also search by article number or keyword. Each article has a link to our related page.

163 articles

Our related pages
  1. In a new building, escape stair and fire safety lobby doors must be smoke-tight; at least 60 min if serving fewer than 4 storeys, at least 90 min if serving basements or more than 4 storeys; self-closing.

    Official text
    Escape stair and fire safety lobby doors must be smoke-tight and fire-resistant for at least 60 minutes if they serve fewer than 4 storeys, and for at least 90 minutes if they serve basement storeys and more than 4 storeys. The doors must be fitted with self-closing devices and must allow firefighters or staff to enter from outside when necessary.

    Source: BYKHY 47(3) · mevzuat.gov.tr

  2. Escape stairs are separated from other parts by walls rated for at least 120 min and smoke-tight doors rated for at least 90 min.

    Official text
    No combustible material may be used in the walls, ceiling and floor of escape stairs, and these stairs are separated from other parts by walls resistant to fire for at least 120 minutes and smoke-tight doors resistant for at least 90 minutes.

    Source: BYKHY 38(3) · mevzuat.gov.tr

  3. In existing buildings, escape stair doors must be rated for at least 60 min if the building height is below 30.50 m and at least 90 min if it is 30.50 m or more, and smoke-tight; width at least 70 cm, height at least 190 cm.

    Official text
    In existing buildings, escape stair doors must be fire-resistant for at least 60 minutes where the building height is less than 30.50 m, and for at least 90 minutes in buildings 30.50 m high or more, and must be smoke-tight. The width of escape route doors may not be less than 70 cm and their height not less than 190 cm.

    Source: BYKHY 157(1) · mevzuat.gov.tr

  4. Escape route doors have a clear width of at least 80 cm and a height of at least 200 cm; no threshold; revolving doors and turnstiles do not count as exits.

    Official text
    The minimum clear width of escape route doors may not be less than 80 cm and their height not less than 200 cm. Escape route doors must have no threshold. Revolving doors and turnstiles may not be used as exit doors.

    Source: BYKHY 47(1) · mevzuat.gov.tr

  5. If a door or fixed light in a fire wall cannot be avoided, it must be rated for at least half the wall's resistance; doors must be self-closing and smoke-tight.

    Official text
    Fire walls may have no holes or openings. Where openings such as doors and fixed lights in the walls cannot be avoided, they must be fire-resistant for at least half the resistance period of the fire wall. The doors must be self-closing and smoke-tight.

    Source: BYKHY 25(2) · mevzuat.gov.tr

  6. The fire safety lobby is separated by walls rated for at least 120 min and smoke-tight doors rated for at least 90 min.

    Official text
    No combustible material may be used in the walls, ceiling and floor of fire safety lobbies, and these lobbies must be separated from other parts by walls resistant to fire for at least 120 minutes and smoke-tight doors resistant for at least 90 minutes.

    Source: BYKHY 34(2) · mevzuat.gov.tr

  7. A door, hatch or shutter that, when closed, resists the passage of smoke, heat and flame for a set time.

    Official text
    Fire door: a door, hatch or shutter that allows the movement of occupants, air or objects within a building and which, when kept closed, is capable of resisting the passage of smoke, heat and flame for a set time,

    Source: BYKHY 4(1)(şş) · mevzuat.gov.tr

  8. In spaces with more than 50 people, exit doors open in the direction of escape; they open by hand and are not kept locked.

    Official text
    The leaves of escape route doors must not obstruct the movement of occupants. Exit doors of spaces with an occupant load of more than 50 people must open in the direction of escape. Escape route doors must open by hand and must not be kept locked.

    Source: BYKHY 47(2) · mevzuat.gov.tr

  9. Ground-level exit doors, and escape stair, corridor and lobby doors where a floor holds more than 100 people, open in the direction of escape without using a handle.

    Official text
    All escape route doors opening from the stair to a safe area at natural ground level, and, where the number of people on a floor exceeds 100, escape stair, escape corridor and fire safety lobby doors, are arranged so that they can be opened in the direction of escape without using a door handle.

    Source: BYKHY 47(5) · mevzuat.gov.tr

  10. No lock, bolt or similar may be fitted to exits and doors in a way that obstructs free escape. Exception: places housing people with intellectual disabilities, detainees or inmates, where staff are permanently on duty and able to move the occupants.

    Official text
    No lock, bolt or similar component may be fitted to exits or doors of any building in a way that obstructs free escape from inside. The use of locks is permitted in places housing people with intellectual disabilities, detainees or inmates, where authorised staff are permanently on duty and there are adequate means to move the occupants in a fire or other emergency.

    Source: BYKHY 30(4) · mevzuat.gov.tr

  11. Boiler room exit doors must be rated for at least 90 min, smoke-tight and self-closing; at least 2 doors in large boiler rooms.

    Official text
    The exit doors must be placed as far as possible in opposite directions to each other, and must be fire-resistant for at least 90 minutes, smoke-tight and self-closing.

    Source: BYKHY 54(5) · mevzuat.gov.tr

  12. In hotels and dormitories, doors opening onto an internal corridor must be rated for at least 30 min and self-closing.

    Official text
    Doors opening onto the internal corridor must be fire-resistant for at least 30 minutes and fitted with self-closing devices.

    Source: BYKHY 50(1)(b) · mevzuat.gov.tr

  13. The total height of all storeys, including basements, mezzanines and attic rooms.

    Official text
    Building height (including basements): the total height of all storeys built in the structure, including basements, mezzanines and attic rooms,

    Source: BYKHY 4(1)(bbb) · mevzuat.gov.tr

  14. Buildings with a building height above ground of more than 21.50 m, or a building height including basements of more than 30.50 m.

    Official text
    High-rise building: buildings with a building height above ground of more than 21.50 m or a building height including basements of more than 30.50 m,

    Source: BYKHY 4(1)(ccc) · mevzuat.gov.tr

  15. A corridor or lobby protected by being separated from adjoining spaces with fire-resistant building elements.

    Official text
    Protected corridor or lobby: a corridor or lobby protected from the effects of fire by being separated from the spaces it adjoins with fire-resistant building elements,

    Source: BYKHY 4(1)(dd) · mevzuat.gov.tr

  16. A stair enclosed in fire-resistant material or arranged so that it is not affected by fire.

    Official text
    Protected stair: a stair enclosed in a fire-resistant material or arranged so that it is not affected by fire,

    Source: BYKHY 4(1)(ee) · mevzuat.gov.tr

  17. The distance from the building's datum level to eaves level, or the height set in the zoning plan and the Regulation.

    Official text
    Building height above ground: the distance from the point at which the building's datum level is taken to eaves level, or the height set in the zoning plan and in this Regulation,

    Source: BYKHY 4(1)(h) · mevzuat.gov.tr

  18. A vertical element that separates two buildings, or spaces with different fire loads in the same building, and stops fire for a set time.

    Official text
    Fire wall: a vertical element that stops the progress and spread of fire for a set time where spaces with different fire loads must be separated from each other, between two buildings or within the same building,

    Source: BYKHY 4(1)(rr) · mevzuat.gov.tr

  19. Occupants moving away from the fire and taking refuge in the neighbouring compartment on the same floor.

    Official text
    Progressive horizontal evacuation: occupants moving away from the fire and taking refuge in the fire-tight neighbouring compartment on the same floor level,

    Source: BYKHY 4(1)(s) · mevzuat.gov.tr

  20. A section built to prevent fire and smoke from passing into escape stairs.

    Official text
    Fire safety lobby: a section to be built to prevent fire and smoke from passing into escape stairs,

    Source: BYKHY 4(1)(ss) · mevzuat.gov.tr

  21. A zone separated on all sides by elements rated for at least 60 minutes, so that smoke and heat cannot pass.

    Official text
    Fire compartment: a zone within a building separated, on all sides including the ceiling and floor slab, into smoke- and heat-tight areas by building elements resistant to fire for at least 60 minutes,

    Source: BYKHY 4(1)(tt) · mevzuat.gov.tr

  22. A document issued after testing by TSE or an international approval body accepted by TSE, showing conformity with the relevant standards.

    Official text
    ğğ) Certificate: a document issued for any equipment, material or service after testing by the Turkish Standards Institution or by an international approval body accepted by the Turkish Standards Institution, showing conformity with the relevant standards,

    Source: BYKHY 4(1)(ğğ) · mevzuat.gov.tr

  23. If the design does not comply with the Regulation, no building permit is issued. If a new building is found not to have been built in compliance with the Regulation, no occupancy permit is issued until the deficiencies are remedied.

    Official text
    If designs do not comply, in addition to the statutory requirements, with the fire safety conditions set in this Regulation, no building permit is issued. Where it is found that a newly built building, or one whose use has been changed by a design amendment, has not been built in accordance with the principles set in this Regulation, no occupancy permit or operating licence is issued for the building until these deficiencies are remedied.

    Source: BYKHY 5(1) · mevzuat.gov.tr

  24. Where the Regulation has no adequate provision, Turkish Standards apply first, and European Standards if there are none.

    Official text
    On matters for which this Regulation has no adequate provision, designers (…) apply Turkish Standards and, where these standards do not exist, European Standards. On matters not covered by Turkish or European Standards, internationally recognised standards may also be used.

    Source: BYKHY 5(2) · mevzuat.gov.tr

  25. The permitting authorities, investors, building owners, employers, architects and engineers in design and construction, contractors, manufacturers and building inspection are responsible for applying the Regulation.

    Official text
    (1) For the application of the provisions of this Regulation, the following are charged, authorised and responsible: a) Authorities empowered to issue building permits, b) Investing organisations, c) Building owners, ç) The employer or their representatives, d) Architects and engineers charged with design and construction, and executing contractors and manufacturers, e) Consultants, advisers, design checkers, building inspectors and operating officers involved in the construction and use of the building.

    Source: BYKHY 6(1) · mevzuat.gov.tr

  26. Hotels, motels, thermal facilities, holiday villages, guesthouses, campsites, student dormitories, camps and similar.

    Official text
    Hotels, motels, thermal facilities, holiday villages and guesthouses, campsites, student dormitories, camps and similar facilities are accommodation buildings.

    Source: BYKHY 10(1) · mevzuat.gov.tr

  27. Buildings used for education by 6 or more people for more than 4 hours a day or 12 hours a week: kindergartens, nurseries, primary and secondary schools, private tutoring centres, libraries, higher education.

    Official text
    a) Educational facilities: places where education and teaching activities are carried out.

    Source: BYKHY 11(1)(a) · mevzuat.gov.tr

  28. Treatment and care buildings where four or more people can be admitted as inpatients: hospitals, care homes for the elderly, childcare and rehabilitation centres, dispensaries; health centres, private clinics, diagnosis and treatment centres and medical laboratories are also in this class.

    Official text
    b) Healthcare buildings: covers buildings, or parts of buildings used for this purpose, where a physical or mental illness or disability is treated or cared for, or which are used for the care of young children, convalescents or elderly people in need of care, and where four or more people can be admitted as inpatients. Hospitals, care homes for the elderly, childcare and rehabilitation centres, dispensaries and similar places fall into this class.

    Source: BYKHY 11(1)(b) · mevzuat.gov.tr

  29. Buildings where office services and accounting and record-keeping work are carried out; banks, stock exchanges, public service buildings, general office buildings, doctors' surgeries.

    Official text
    ARTICLE 12 – (1) Office buildings are buildings, excluding work falling within the scope of commercial buildings, where all kinds of office services are carried out for business purposes and where accounting and record-keeping and similar work is done. Banks, stock exchanges, public service buildings, general office buildings, and doctors' and dentists' surgeries are among these buildings.

    Source: BYKHY 12(1) · mevzuat.gov.tr

  30. Places where food, clothing, health and other necessities are sold: shops, stores, markets, supermarkets, wholesale centres, covered bazaars, arcades and similar.

    Official text
    ARTICLE 13 – (1) Commercial buildings are places where food, clothing, health and other necessities are sold wholesale and retail.

    Source: BYKHY 13(1) · mevzuat.gov.tr

  31. Office, storage and service areas in the same building that are linked to sales fall into the commercial class.

    Official text
    (2) Office, storage and service areas used in connection with the sale of commercial goods and located in the same building fall into the commercial building class.

    Source: BYKHY 13(2) · mevzuat.gov.tr

  32. Factories where any kind of product is made; buildings for processing, assembly, packaging, storage, distribution and repair; textile, food processing and power generation facilities, refineries.

    Official text
    ARTICLE 14 – (1) Industrial buildings are factories where any kind of product is made, and buildings and structures intended for operations such as processing, assembly, mixing, cleaning, washing, packaging, storage, distribution and repair.

    Source: BYKHY 14(1) · mevzuat.gov.tr

  33. Buildings where goods, items, products, vehicles or animals of any kind are stored: warehouses (silos, bonded warehouses, stores, archives) and car parks.

    Official text
    ARTICLE 16 – (1) Storage facilities means buildings and structures used for the storage or keeping of goods, items, products, vehicles or animals of any kind.

    Source: BYKHY 16(1) · mevzuat.gov.tr

  34. Storage areas smaller than 50 m² inside a building count as part of the main building.

    Official text
    (2) Storage areas smaller than 50 m2 within a building are accepted as part of the main building.

    Source: BYKHY 16(2) · mevzuat.gov.tr

  35. Places where flammable and explosive substances and fuels are manufactured, stored, filled, discharged and sold; places involving combustible liquids (c) included.

    Official text
    ARTICLE 17 – (1) Places where flammable and explosive substances and fuels are manufactured and stored, and where filling, discharging and sales take place, are considered high-hazard places.

    Source: BYKHY 17(1) · mevzuat.gov.tr

  36. If parts of different classes cannot be separated by a fire separation suited to the higher hazard class, the rules of the class requiring the higher protection apply to the whole building.

    Official text
    ARTICLE 18 – (1) If a building has parts subject to two or more use classifications, and these parts cannot be separated from each other by a fire separation suited to the higher hazard class, or separate protection measures cannot be applied because they are intertwined, the rules for the classification requiring the higher protection measures apply to the whole building.

    Source: BYKHY 18(1) · mevzuat.gov.tr

  37. Low-hazard (low fire load, ≥ 30 min, compartment ≤ 126 m²), medium-hazard (medium fire load) and high-hazard (high fire load, rapid spread) places; the areas are listed in Annex 1/A, B and C.

    Official text
    (2) When extinguishing systems and compartments are designed in a building or part of it, the following hazard classification is taken into account during design:

    Source: BYKHY 19(2) · mevzuat.gov.tr

  38. The minimum fire resistance periods of compartment walls and floors are in Annex 3/B.

    Official text
    The minimum fire resistance periods of fire compartment walls and floors are given in Annex 3/B.

    Source: BYKHY 24(1) · mevzuat.gov.tr

  39. Walls shared by two or more buildings, and the walls and floors of enclosed areas with a fire hazard such as boiler rooms, car parks, main electrical distribution rooms, transformers and generator rooms, have the properties of compartment walls.

    Official text
    Walls shared by two or more buildings, and the walls and floors of boiler rooms, car parks, main electrical distribution rooms, transformer substations inside the building, medium-voltage substations, generator set rooms and similar enclosed areas with a fire hazard, have the properties of compartment walls.

    Source: BYKHY 24(2) · mevzuat.gov.tr

  40. Party walls between buildings are fire-resistant; the wall separating semi-detached houses is a fire wall, and the houses are separate buildings.

    Official text
    Party walls belonging to two or more buildings are built as fire-resistant walls. Every wall separating semi-detached houses from each other is built as a fire wall, and the houses are considered separate buildings.

    Source: BYKHY 24(3) · mevzuat.gov.tr

  41. In non-residential buildings with a building height above ground of more than 21.50 m (30.50 m for housing), at most three storeys form one fire compartment on the floors above that height.

    Official text
    In non-residential buildings with a building height above ground of more than 21.50 m, and in residential buildings with a building height above ground of more than 30.50 m, the storeys above these heights are arranged with at most three storeys forming one fire compartment.

    Source: BYKHY 24(4) · mevzuat.gov.tr

  42. Atriums only in low- and medium-hazard uses; area in principle ≥ 90 m²; in a smaller void a smoke curtain of ≥ 45 cm on every floor; smoke control.

    Official text
    (5) (Amended: 10/8/2009-2009/15316 K.) Atrium areas are permitted only in buildings whose uses include only low- and medium-hazard classes. The principle is that the atrium area is not smaller than 90 m2 at any point.

    Source: BYKHY 24(5) · mevzuat.gov.tr

  43. The maximum compartment area permitted in buildings is given in Annex 4 of the Regulation.

    Official text
    The maximum compartment area permitted in buildings is given in Annex 4.

    Source: BYKHY 24(6) · mevzuat.gov.tr

  44. The fire resistance of the elements enclosing a compartment continues at their junctions; there may be no non-fire-resistant opening between compartments.

    Official text
    For fire compartments to be effective, the fire resistance of the elements enclosing the compartment is also continuous at their junctions, and there may be no non-fire-resistant openings between compartments.

    Source: BYKHY 24(7) · mevzuat.gov.tr

  45. Fire walls separating adjoining (terraced) buildings are designed to resist fire for at least 90 minutes.

    Official text
    Fire walls separating adjoining (terraced) buildings from each other are designed to resist fire for at least 90 minutes. The properties that fire walls must have at façades and roofs are set out in the relevant articles.

    Source: BYKHY 25(1) · mevzuat.gov.tr

  46. In high-rise buildings, vertical shaft and flue walls must be rated for at least 120 min, and their hatches for at least 90 min and smoke-tight.

    Official text
    In high-rise buildings, the walls of vertical service shafts and flues, such as those for refuse, communications, documents and technical equipment, must be fire-resistant for at least 120 minutes, and their hatches for at least 90 minutes, and smoke-tight.

    Source: BYKHY 25(3) · mevzuat.gov.tr

  47. All floors have the properties of a fire wall; their ratings are in Annex 3/B.

    Official text
    All floors must have the properties of a fire wall. The fire resistance periods of floors are given in Annex 3/B.

    Source: BYKHY 26(1) · mevzuat.gov.tr

  48. The façade cladding of the taller building at the roof level of the lower building is non-combustible.

    Official text
    In adjoining buildings of different heights, the external façade cladding of the taller building's storey at the roof level of the lower building must be clad with a non-combustible material or system.

    Source: BYKHY 27(2)(c) · mevzuat.gov.tr

  49. On a curtain wall, the junction of the façade and the floor is sealed for the fire resistance period of the floor.

    Official text
    The junctions of façade elements with floors that have no voids through which flames can pass are sealed, for as long as needed to provide the floor's fire resistance, so as to prevent flames from leaping to adjacent storeys.

    Source: BYKHY 27(3)(a) · mevzuat.gov.tr

  50. The roof slab is a horizontal fire barrier; the structure and covering are non-combustible.

    Official text
    In high-rise buildings and adjoining buildings; a) the slabs on which roofs sit must be horizontal fire barriers, b) the roof structure and roof coverings must be of non-combustible material.

    Source: BYKHY 28(3) · mevzuat.gov.tr

  51. For escape and panic calculations, the occupant load factor is taken from Annex 5/A.

    Official text
    ARTICLE 32 – (1) The values given in Annex 5/A are used as the occupant load factor in the required escape and panic calculations.

    Source: BYKHY 32(1) · mevzuat.gov.tr

  52. Exit doors, stairs and corridors are calculated with a width unit of 50 cm; the number of people passing through one unit is in Annex 5/B.

    Official text
    (2) For exit width, the capacities of exit doors, escape stairs, corridors and other escape routes are calculated using a width unit of 50 cm.

    Source: BYKHY 32(2) · mevzuat.gov.tr

  53. Where there is a horizontal evacuation area, the travel distance is measured to the exit door of the corridor leading to that area; at least one protected escape route is reachable from every horizontal evacuation area.

    Official text
    In places such as hospitals where a horizontal evacuation area resistant to fire for at least 60 minutes and protected against the passage of smoke is provided, the travel distance is measured to the exit door of the corridor leading to the horizontal evacuation area. At least one protected escape route must be reachable from every horizontal evacuation area.

    Source: BYKHY 32(7) · mevzuat.gov.tr

  54. In a ground-floor shop or similar, a single exit is enough if there are fewer than 50 people and the distance to the outside door is less than 25 m.

    Official text
    In ground-floor shops and similar places, if the number of people is below 50 and the travel distance from the furthest point to the door opening to the outside is less than 25 m, a single exit from the building is accepted as sufficient.

    Source: BYKHY 32(8) · mevzuat.gov.tr

  55. With 50–500 people on a floor, one escape route is at least 100 cm wide; with 501–2000 people at least 150 cm; with 2001 or more at least 200 cm. Corridors and lobbies serving rooms are at least 110 cm; no exit may be narrower than 80 cm.

    Official text
    If the total number of occupants is between 50 and 500, the number of exits is set so that the width of an escape route on the floor is not less than 100 cm; if between 501 and 2000, not less than 150 cm; and if 2001 or more, not less than 200 cm. If the escape route is also used as a corridor and lobby serving the rooms of the building, it may not be less than 110 cm wide. No exit, escape stair or other escape route may be narrower than these calculated values or than 80 cm.

    Source: BYKHY 33(1) · mevzuat.gov.tr

  56. In high-rise buildings, escape routes and stairs are at least 120 cm wide.

    Official text
    In high-rise buildings, the width of escape routes and stairs may not be less than 120 cm.

    Source: BYKHY 33(2) · mevzuat.gov.tr

  57. In a space needing two exits, each exit is wide enough for at least half of the total occupant load.

    Official text
    In spaces needing two exits, each exit must be wide enough to serve at least half of the total occupant load.

    Source: BYKHY 33(4) · mevzuat.gov.tr

  58. Widths are measured as clear widths; at an exit door, between the frame and the leaf opened at 90° for a single leaf, and between the two open leaves for a double leaf.

    Official text
    Widths are measured as clear widths. On escape stairs and at the exit door, the clear width is measured as follows: (...) b) At the exit door; for a single-leaf door, the clear width is the distance between the door frame or rebate projection and the face of the leaf opened at 90 degrees. The clear width of a single-leaf exit door may not be less than 80 cm or more than 120 cm. For a double-leaf door, the clear width is the distance between the faces of the leaves with both leaves open at 90 degrees.

    Source: BYKHY 33(5) · mevzuat.gov.tr

  59. To prevent smoke from passing into the stair, for use by firefighting and rescue teams, and for holding disabled and injured people; it does not obstruct movement during escape.

    Official text
    Fire safety lobbies are built to prevent smoke from passing into escape stairs, for use by firefighting and rescue personnel, and, where necessary, for holding disabled and injured people. The lobbies must be designed so as not to obstruct the movement of occupants along the escape route.

    Source: BYKHY 34(1) · mevzuat.gov.tr

  60. The floor area may not be less than 3 m² or more than 6 m²; its dimension in the direction of escape may not be less than 1.8 m.

  61. The fire safety lobby in front of a firefighting lift is 6–10 m²; no side may be shorter than 2 m.

  62. In the lift lobby, the floor is given a slope of at most 1/200 towards the exit door.

    Official text
    In the lift lobby, the floor is given a slope not exceeding 1/200 towards the exit door.

    Source: BYKHY 34(5) · mevzuat.gov.tr

  63. Unless stated otherwise, the escape stair is reached through a fire safety lobby, or through a lobby, corridor or foyer separated from the occupied areas by a door.

    Official text
    Unless stated otherwise, escape stairs are reached by passing through a fire safety lobby, or through a lobby, corridor or foyer separated from the occupied areas by a door.

    Source: BYKHY 34(6) · mevzuat.gov.tr

  64. In buildings with a firefighting lift and a building height of more than 51.50 m, a fire safety lobby in front of the escape stair is mandatory; the firefighting lift opens into this lobby.

  65. The building or business owner and managers are responsible for keeping the fire safety lobby usable and clear.

  66. The fire resistance periods of protected corridors and lobbies that are escape routes comply with the periods in Annex 3/B and Annex 3/C.

    Official text
    In a building or building storey, the fire resistance periods of protected corridors or protected lobbies serving as escape routes must comply with the periods given in Annex 3/B and Annex 3/C.

    Source: BYKHY 36(1)(a) · mevzuat.gov.tr

  67. Exit doors opening onto an internal escape corridor must have a rating equivalent to escape stair doors and be self-closing.

    Official text
    Exit doors opening onto an internal escape corridor or passage must be fire-resistant to a level equivalent to exit doors opening onto escape stairs, and must be fitted with automatic self-closing devices.

    Source: BYKHY 36(1)(b)(1) · mevzuat.gov.tr

  68. An external passage can be used as an escape route instead of an internal corridor.

    Official text
    An external passage can be used as an escape route instead of an internal corridor.

    Source: BYKHY 37(1) · mevzuat.gov.tr

  69. An exit door opening onto an external passage must be rated for 30 min and self-closing.

    Official text
    An exit door opening onto an external passage must be fire-resistant for 30 minutes and fitted with self-closing devices.

    Source: BYKHY 37(2) · mevzuat.gov.tr

  70. Unless stated otherwise, all buildings have at least 2 exits, and the exits are protected.

    Official text
    Unless stated otherwise, at least 2 exits must be provided in all buildings, and the exits must be protected.

    Source: BYKHY 39(1) · mevzuat.gov.tr

  71. At least 2 in high-hazard spaces with more than 25 people and in every space with more than 50 people; at least 3 above 500 people; at least 4 above 1000 people.

    Official text
    The number of exits may not be less than the number determined on the basis of Article 33. Unless stated otherwise, there must be at least 2 exits in high-hazard spaces where 25 people are exceeded and in every space where 50 people are exceeded. If the number of people exceeds 500, there must be at least 3 exits, and if it exceeds 1000, at least 4 exits.

    Source: BYKHY 39(2) · mevzuat.gov.tr

  72. In a single undivided space, the distance between two exits is at least half the diagonal without sprinklers, and at least one third with sprinklers.

    Official text
    Exits must be as far from each other as possible. Where 2 exits are needed in single undivided spaces, the distance between the exits may not be less than 1/2 of the diagonal distance where there is no sprinkler system, and not less than 1/3 of the diagonal distance where a sprinkler system is installed.

    Source: BYKHY 39(3) · mevzuat.gov.tr

  73. The entrance to the escape stair and the floor landing are at the same level; the escape stair cannot be reached by passing through a general stair.

    Official text
    The entrance to the escape stair and the floor landing must be at the same level. The escape stair cannot be reached by passing through general stairs.

    Source: BYKHY 40(1) · mevzuat.gov.tr

  74. Doors opening onto an escape stair landing may never be positioned so as to narrow the escape route by more than 1/3.

    Official text
    Doors opening onto the escape stair landing may never be positioned so as to narrow the escape route by more than 1/3.

    Source: BYKHY 41(5) · mevzuat.gov.tr

  75. No service shaft hatch may open into the escape stair enclosure or the fire safety lobby; no combi boiler, outdoor air-conditioning unit, meter or similar may be placed there.

  76. Within 3 m to the sides of and below an open external escape stair, there may be no doors or windows less protected than the stair.

    Official text
    Within 3 m horizontally to the sides and vertically below any part of an open external escape stair, there may be no wall opening, such as a door or window, less protected than the stair.

    Source: BYKHY 42(2) · mevzuat.gov.tr

  77. In buildings with a building height above ground of more than 21.50 m, open stairs outside the building are not permitted.

    Official text
    In buildings with a building height above ground of more than 21.50 m, open stairs outside the building are not permitted.

    Source: BYKHY 42(3) · mevzuat.gov.tr

  78. If the normal floor stair continues down to the basement and serves more than 4 storeys including the basement, a fire safety lobby is provided for access to the stair on the basement storeys, except in special cases for housing.

    Official text
    If the stair serves more than 4 storeys including basement storeys, a fire safety lobby is provided for access to the stair on the basement storeys, except in special cases for housing.

    Source: BYKHY 46(2)(a) · mevzuat.gov.tr

  79. So that people escaping from upper floors do not go down to the basement, the ground landing of the stair is separated from the basement stair by a door or similar barrier, or visible signage is provided.

    Official text
    To prevent occupants leaving the upper floors in any emergency from going down to the basement, the ground-level landing of the stair must be separated from the basement stair by a door or similar physical barrier, or suitable visible signage must be provided.

    Source: BYKHY 46(2)(b) · mevzuat.gov.tr

  80. For a single leaf, between the frame and the face of the leaf opened at 90°; a single-leaf exit door is 80–120 cm; for a double leaf, between the leaves with both open at 90°.

    Official text
    At an escape door, for a single-leaf door, the clear width is the distance between the door frame or rebate projection and the face of the leaf opened at 90 degrees. The clear width of a single-leaf exit door may not be less than 80 cm or more than 120 cm. For a double-leaf door, the clear width is the distance between the faces of the leaves with both leaves open at 90 degrees.

    Source: BYKHY 47(4) · mevzuat.gov.tr

  81. Doors must open with a force of at most 110 N.

    Official text
    Doors must be designed to open with a force of at most 110 N.

    Source: BYKHY 47(6) · mevzuat.gov.tr

  82. In housing with a building height below 21.50 m, an unprotected normal stair counts as an escape route, and no second exit is required.

    Official text
    In housing with a building height below 21.50 m, an unprotected normal stair is accepted as an escape route and no second exit is required.

    Source: BYKHY 48(5)(a) · mevzuat.gov.tr

  83. In housing with a building height of 21.50–30.50 m, at least 2 stairs, at least one of them protected; both are reachable from every flat.

    Official text
    In housing with a building height of more than 21.50 m and less than 30.50 m, at least 2 stairs must be provided, at least one of the stairs must be protected, and both stairs must be reachable from every flat.

    Source: BYKHY 48(5)(b) · mevzuat.gov.tr

  84. Two protected escape stairs; a lobby or pressurisation in at least one.

    Official text
    In housing with a building height of more than 30.50 m and less than 51.50 m, 2 escape stairs must be built that are alternatives to each other, both protected, and at least one of them provided with a fire safety lobby or pressurisation.

    Source: BYKHY 48(5)(c) · mevzuat.gov.tr

  85. At least two escape stairs with lobbies and pressurisation.

    Official text
    In housing with a building height of more than 51.50 m, at least 2 escape stairs must be built that are alternatives to each other, with fire safety lobbies and pressurised.

    Source: BYKHY 48(5)(ç) · mevzuat.gov.tr

  86. A lobby is built in front of an escape stair shared with the housing.

    Official text
    In basement storeys of residential buildings used for other purposes, a fire safety lobby must be provided in front of escape stairs shared with the housing.

    Source: BYKHY 48(6) · mevzuat.gov.tr

  87. Basement storeys whose entrances, exits and shafts are separated from the upper floors by a floor or separation rated for 120 minutes are not included in the building heights in 48(5) and are considered separately.

    Official text
    Basement storeys whose entrances, exits and shafts are separated from the upper floors by a floor or separation resistant to fire for 120 minutes are not included in the building heights specified in paragraph five, and are considered separately in terms of fire safety measures.

    Source: BYKHY 48(7) · mevzuat.gov.tr

  88. A patient bedroom or suite with an occupant load of more than 15 people needs two doors located away from each other.

    Official text
    Any patient bedroom or suite with an occupant load of more than 15 people must have 2 doors located away from each other.

    Source: BYKHY 49(1)(a) · mevzuat.gov.tr

  89. Every patient (in-patient) floor larger than 300 m² is divided into two or more fire compartments, each at least half its size, or protected horizontal evacuation areas are provided.

    Official text
    Every in-patient floor of hospitals and care homes larger than 300 m2 is divided into two or more fire compartments, each at least half its size, or protected horizontal evacuation areas are formed. In calculating horizontal evacuation areas, the occupant load is taken as 2.8 m²/person.

    Source: BYKHY 49(1)(b) · mevzuat.gov.tr

  90. In hospitals the corridor width cannot be less than 2 m; door and passage dimensions in the corridor are planned accordingly.

    Official text
    In hospitals, corridor widths cannot be less than 2 m.

    Source: BYKHY 49(2) · mevzuat.gov.tr

  91. Bedrooms are separated from the internal corridor by a 60 min wall; in a hotel with more than 20 beds or more than 2 storeys, at least 2 exits on every floor.

    Official text
    Bedrooms are separated from the internal corridor by a wall resistant to fire for at least 60 minutes. In hotels with more than 20 beds in total or more than two storeys, at least 2 exits are provided on every floor.

    Source: BYKHY 50(1)(a) · mevzuat.gov.tr

  92. The internal corridor is ventilated naturally through openings in the external wall or by mechanical smoke extraction.

    Official text
    Internal corridors are ventilated naturally through openings in an external wall, or mechanical smoke extraction is provided.

    Source: BYKHY 50(1)(c) · mevzuat.gov.tr

  93. Other rooms opening onto the corridor have the same level of compartmentation as the bedrooms.

    Official text
    For other rooms opening onto the bedroom corridor, or other spaces forming part of the corridor that could endanger escape, the same level of compartmentation as the bedrooms must be provided.

    Source: BYKHY 50(1)(ç) · mevzuat.gov.tr

  94. A room reached from an external corridor also has a 60 min wall, except for non-combustible ventilation openings with a parapet of ≥ 1.1 m.

    Official text
    Bedrooms must be separated from the external corridor by a wall resistant to fire for at least 60 minutes.

    Source: BYKHY 50(2)(a) · mevzuat.gov.tr

  95. Doors opening onto an external corridor are at least 30 min and self-closing.

    Official text
    Doors opening onto an external corridor must be resistant to fire for at least 30 minutes and fitted with self-closing devices.

    Source: BYKHY 50(2)(b) · mevzuat.gov.tr

  96. One door if the distance from the furthest point to the door is ≤ 15 m; if exceeded, at least 2 doors far apart; ≤ 20 m in a fully sprinklered hotel.

    Official text
    If the distance measured from the furthest point of a hotel bedroom or suite to the exit door does not exceed 15 m, a single escape door is considered sufficient.

    Source: BYKHY 50(3) · mevzuat.gov.tr

  97. From the room door to the escape stair, the external escape walkway or the door opening to the outside.

    Official text
    Travel distance is the distance measured from the exit door of the bedroom or suite to an exit door opening onto an escape stair, an external escape walkway or the open air outside.

    Source: BYKHY 50(4) · mevzuat.gov.tr

  98. With one-way escape it is measured from the furthest room door; with two-way escape, from each room's door.

    Official text
    If escape along the corridor is possible in one direction only, travel distance is measured from the exit door of the furthest bedroom.

    Source: BYKHY 50(5) · mevzuat.gov.tr

  99. Internal corridors not ventilated naturally or mechanically are divided by smoke barriers at 45 m intervals in a sprinklered building and 30 m in an unsprinklered building; the smoke barrier extends up to the ceiling.

    Official text
    Internal corridors not ventilated naturally or mechanically are divided by smoke barriers at 45 m intervals in buildings with a sprinkler system and 30 m intervals in buildings without a sprinkler system, and the following conditions are complied with there: a) Smoke barriers are resistant to fire for at least 60 minutes. (…) Smoke barriers, including the wall enclosing the corridor, must continue over the full storey height up to the ceiling or the underside of the roof covering and tightly close off the intermediate sections.

    Source: BYKHY 50(6) · mevzuat.gov.tr

  100. Unventilated hotel internal corridors are divided by smoke barriers at 45 m (30 m without sprinklers) intervals; escape doors in the barrier are rated for at least 60 min and smoke-tight.

    Official text
    Smoke barriers are resistant to fire for at least 60 minutes. Escape doors located within the barrier must be resistant to fire for at least 60 minutes and smoke-tight.

    Source: BYKHY 50(6)(a) · mevzuat.gov.tr

  101. From every section, direct unobstructed access to an exit, escape stair, external escape walkway or ramp.

    Official text
    From each of the sections formed by smoke barriers, direct unobstructed access to an exit, escape stair, external escape walkway or escape ramp must be provided.

    Source: BYKHY 50(6)(b) · mevzuat.gov.tr

  102. Smoke-tight doors in hotel internal corridors, except glazed doors, have vision glass of at least 25% of each leaf.

    Official text
    Smoke-tight doors, except glazed doors, are fitted with glass panels giving clear vision over an area of at least 25% of the surface area of each leaf.

    Source: BYKHY 50(6)(c) · mevzuat.gov.tr

  103. Normally closed; it may be held open if it closes automatically via an electromagnetic/electromechanical device connected to the detection system.

    Official text
    Smoke-tight doors must normally be kept closed.

    Source: BYKHY 50(6)(d) · mevzuat.gov.tr

  104. Smoke-tight doors may be single or double leaf; they are self-closing, close the opening completely, and the gap between leaf and floor is at most 4 mm.

    Official text
    Smoke-tight doors may be single or double leaf. However, they must be fitted with self-closing devices and the leaves must completely close the opening in which they are located. Frames must be fixed tightly into the wall opening and the gap between leaf and floor must not exceed 4 mm.

    Source: BYKHY 50(6)(ç) · mevzuat.gov.tr

  105. In a mixed-use building, at least half of the required number and capacity of exits of a theatre, cinema or concert hall is provided within its own compartment.

    Official text
    (2) (Amended: 10/8/2009-2009/15316 Decision) In mixed-use buildings, at least half of the number and capacity of the required exits of theatres, cinemas or concert halls must be provided within their own compartment.

    Source: BYKHY 51(2) · mevzuat.gov.tr

  106. At least 2 independent escape stairs or other exits; a single stair only if building height < 21.50 m, < 50 people per floor, travel distances comply with Annex 5/B, non-combustible products, no highly flammable substances — all together.

    Official text
    (1) In factories, workshops, department stores, shops, warehouses, office buildings and outpatient treatment centres, at least 2 independent escape stairs or other exits must be provided.

    Source: BYKHY 52(1) · mevzuat.gov.tr

  107. The boiler room is separated by partitions resistant to fire for at least 120 minutes and is in a central location and in one piece; an expansion joint cannot pass through it.

    Official text
    The boiler room is located in a central place and in one piece, separated from the other parts of the building by partitions resistant to fire for at least 120 minutes. A building expansion joint cannot pass through the boiler room.

    Source: BYKHY 54(2) · mevzuat.gov.tr

  108. Fresh and exhaust air ducts are built in addition to the flues.

    Official text
    In boiler rooms, fresh and exhaust air ducts must be built in addition to the flues.

    Source: BYKHY 54(3) · mevzuat.gov.tr

  109. The boiler room door cannot open directly onto an escape stair or a general-use stair; it opens onto a common lobby or corridor.

    Official text
    The boiler room door must not open directly onto an escape stair or general-use stairs and must open onto a common lobby or corridor.

    Source: BYKHY 54(4) · mevzuat.gov.tr

  110. At least 1 6 kg multi-purpose dry chemical powder extinguisher; at least 1 fire hose cabinet in a large boiler room.

    Official text
    In the boiler room, at least 1 6 kg multi-purpose dry chemical powder fire extinguisher is kept, and in large boiler rooms at least 1 fire hose cabinet.

    Source: BYKHY 54(8) · mevzuat.gov.tr

  111. Meters are placed outside the boiler room.

    Official text
    Meters must be placed outside the boiler room.

    Source: BYKHY 55(2) · mevzuat.gov.tr

  112. Main shut-off valve, main circuit breaker and main electrical panel outside the boiler room, in an easily accessible place.

    Official text
    The main shut-off valve that will cut off the gas in the event of any danger, and the main circuit breaker and main electrical panel that will cut off the electric current, are placed in an easily accessible location outside the boiler room.

    Source: BYKHY 55(3) · mevzuat.gov.tr

  113. A gas detector is mandatory in a boiler room using natural gas or LPG.

    Official text
    Where natural gas or LPG is used in the boiler room, the use of gas detectors that detect these gases is mandatory.

    Source: BYKHY 55(5) · mevzuat.gov.tr

  114. A boiler room using LPG cannot be built in the basement; LPG cylinders cannot be kept in the basement.

    Official text
    Boiler rooms using LPG cannot be built on a basement floor. LPG cylinders cannot be kept in basements.

    Source: BYKHY 55(10) · mevzuat.gov.tr

  115. Fuel store in a separate protected space; separated from the boiler room by a 120 min partition; ventilation and bunding for one third of the tank capacity.

    Official text
    Fuel stores are placed in a space protected by fire-resistant partitions. The fuel store and the boiler room must be separated by a partition resistant to fire for 120 minutes. Adequate ventilation must be provided in the store and bunding must be built to hold at least one third of the tank capacity.

    Source: BYKHY 56(1) · mevzuat.gov.tr

  116. Kitchens in shopping centres and high-rise buildings, food factories, kitchens serving 100+ people: automatic hood extinguishing + gas detection, shut-off and alarm.

    Official text
    ARTICLE 57- (1) Except for dwellings, an automatic extinguishing system being installed in the hoods of kitchens in shopping centres and high-rise buildings, of food factories and of kitchens serving more than 100 people at one time

    Source: BYKHY 57(1) · mevzuat.gov.tr

  117. Kitchens and tea kitchens are separated from the rest of the building by partitions rated for at least 120 min; no timber or easily combustible partitions.

    Official text
    (3) Kitchens and tea kitchens are positioned so that they are separated from the other parts of the building by partitions resistant to fire for at least 120 minutes.

    Source: BYKHY 57(3) · mevzuat.gov.tr

  118. Flue installation complies with TS principles; preferably a separate flue for each boiler.

    Official text
    The flue installation must comply with the principles of the relevant Turkish Standards. A separate flue is preferably used for each boiler; stove and water-heater pipes cannot be connected to boiler flues.

    Source: BYKHY 58(1) · mevzuat.gov.tr

  119. A separate ventilation duct is built for the boiler room.

    Official text
    A separate ventilation duct is built for the boiler room.

    Source: BYKHY 58(2) · mevzuat.gov.tr

  120. If a lobby of laminated glass is formed in front of lifts and escalators in car parks, the car park section and the glass are protected by a sprinkler system.

    Official text
    Where a lobby is formed with laminated glass in front of lifts and escalators in car parks, the car park section and the glass are protected by a sprinkler system.

    Source: BYKHY 62(4) · mevzuat.gov.tr

  121. In high-rise buildings and buildings open to the public, on a fire alarm the lift returns to the emergency exit floor without opening its doors and waits with its doors open.

    Official text
    Lifts used in high-rise buildings and buildings open to the public must comply with the principles set out below: a) On receiving a fire alarm, lifts must automatically return to the emergency exit floor without opening their doors, whatever their direction of travel, and wait with their doors open. However, lifts must also have an electrical system that can be used by the authorities when necessary.

    Source: BYKHY 62(5)(a) · mevzuat.gov.tr

  122. A lift door cannot open into the fire escape stair enclosure.

    Official text
    A lift door cannot open into the fire stair enclosure.

    Source: BYKHY 62(6) · mevzuat.gov.tr

  123. At least 1 firefighting lift in buildings with a building height over 51.50 m.

    Official text
    In buildings with a building height of more than 51.50 m, at least 1 lift must be arranged as a firefighting lift for use in emergencies.

    Source: BYKHY 63(2) · mevzuat.gov.tr

  124. A lobby of 6–10 m² on every floor, each dimension at least 2 m, also giving access to the stair.

    Official text
    In front of firefighting lifts, a fire safety lobby is formed on every floor, also giving access to the escape stair, of not less than 6 m2 and not more than 10 m2, with no dimension less than 2 m.

    Source: BYKHY 63(3) · mevzuat.gov.tr

  125. When the external supply fails, or when electricity is cut for reasons such as fire or earthquake, it switches on automatically and provides adequate lighting.

    Official text
    ARTICLE 72- (1) The emergency lighting system is arranged so that it switches on automatically and provides adequate lighting when normal lighting fails because the mains or a similar external electricity supply is cut, because the electricity of the building or structure is cut for safety reasons such as fire or earthquake, or because a circuit breaker or fuse trips.

    Source: BYKHY 72(1) · mevzuat.gov.tr

  126. Emergency lighting is mandatory on all escape routes and in the listed places; also in hospitals, care homes and educational buildings.

    Official text
    a) In hospitals and care homes and in educational buildings,

    Source: BYKHY 72(2)(a) · mevzuat.gov.tr

  127. In a fire, the emergency control system releases the electromagnetic hold-open devices that normally keep open the fire doors that must close.

    Official text
    ARTICLE 82- (1) Of the emergency control system that will automatically perform the necessary control functions in the event of fire; a) Release of electromagnetic door holders and similar devices that normally keep open the fire doors that must close during a fire and the devices intended to close other openings,

    Source: BYKHY 82(1)(a) · mevzuat.gov.tr

  128. In a fire, the emergency control system opens doors and turnstiles kept locked for security and similar reasons.

    Official text
    d) Opening of doors and turnstiles kept locked for security and similar reasons,

    Source: BYKHY 82(1)(d) · mevzuat.gov.tr

  129. If one air handling unit ventilates more than one compartment, fire dampers are fitted in the supply and extract ducts at the crossings.

    Official text
    If more than one fire compartment is ventilated or air-conditioned by the same air handling unit, fire dampers must be used in the supply and extract ducts at the crossings between fire compartments.

    Source: BYKHY 87(6) · mevzuat.gov.tr

  130. Ventilation and smoke extraction ducts should not pierce the compartment wall; at a 120-minute wall or floor crossing, a damper or equivalent measure is provided.

    Official text
    Ventilation and smoke extraction ducts must not pierce fire compartment walls.

    Source: BYKHY 87(8) · mevzuat.gov.tr

  131. Service shafts and ducts that play a role in fire spread are aligned with the compartments and insulated so as not to reduce the compartment's fire resistance.

    Official text
    Service shafts and ducts that play a role in the spread of fire must be aligned with the fire compartments and insulated so as not to reduce the fire resistance of the compartment.

    Source: BYKHY 87(11) · mevzuat.gov.tr

  132. Mechanical smoke extraction system in a boiler room over 2,000 m², at least 10 air changes per hour.

    Official text
    A mechanical smoke extraction system is mandatory in boiler rooms with a total area over 2,000 m2, in enclosed car parks and in storage areas on basement floors.

    Source: BYKHY 88(3) · mevzuat.gov.tr

  133. If pressurisation is also applied to the lobby, the pressure in the stair is higher than in the lobby.

    Official text
    Where the pressurisation system is also applied to the fire safety lobby, a pressure distribution must be created in which the pressure on the stair side is higher than the pressure on the fire safety lobby side.

    Source: BYKHY 89(6) · mevzuat.gov.tr

  134. Despite the pressure and the closer, the door opens with a force of at most 110 N.

    Official text
    The force that must be applied to the door handle to open the door, overcoming the force exerted on the door by both the pressurised air and the automatic door closer, 110 newtons

    Source: BYKHY 89(7) · mevzuat.gov.tr

  135. A fire hose cabinet is mandatory in high-rise buildings, workshops etc. over 1,000 m², enclosed car parks over 600 m² and boiler rooms over 350 kW.

    Official text
    in enclosed car parks and in boiler rooms with a thermal capacity over 350 kW, a fire hose cabinet is mandatory.

    Source: BYKHY 94(1)(b)(1) · mevzuat.gov.tr

  136. Automatic sprinklers are mandatory in all non-residential buildings with a building height over 30.50 m.

    Official text
    a) In all buildings other than residential buildings with a building height of more than 30.50 m,

    Source: BYKHY 96(2)(a) · mevzuat.gov.tr

  137. Sprinklers are mandatory in enclosed car parks with a total area over 600 m² and in enclosed car parks where more than 10 vehicles are taken up by lift.

    Official text
    c) (Amended: 10/8/2009-2009/15316 Decision) In enclosed car parks with a total area greater than 600 m2 and in enclosed car parks where more than 10 vehicles are taken up by lift,

    Source: BYKHY 96(2)(c) · mevzuat.gov.tr

  138. Sprinklers are mandatory in multi-storey shops and in shopping, commercial and entertainment premises with a total area over 2,000 m².

    Official text
    d) (Amended: 10/8/2009-2009/15316 Decision) In multi-storey shops and in shopping, commercial and entertainment premises with a total area over 2,000 m2,

    Source: BYKHY 96(2)(d) · mevzuat.gov.tr

  139. Hotels, dormitories, guesthouses and lodging houses with more than 100 rooms or 200 beds in a multi-storey building; all residential accommodation facilities over 21.50 m.

    Official text
    In hotels, dormitories, guesthouses and lodging houses within a multi-storey building with more than 100 bedrooms or more than 200 beds, and in all residential accommodation facilities with a building height of more than 21.50 m,

    Source: BYKHY 96(2)(ç) · mevzuat.gov.tr

  140. The existing-buildings part does not apply to existing buildings whose use is changed to healthcare, residential healthcare, kindergarten, nursery, children's club, primary school, children's home, entertainment, accommodation or hazardous-substance buildings.

    Official text
    ARTICLE 138- (1) (Amended: 10/8/2009-2009/15316 Decision) Of existing buildings, those whose use is changed after this Regulation enters into force,

    Source: BYKHY 138(1) · mevzuat.gov.tr

  141. In existing buildings where fire measures complying with the 2002 regulation have been taken, the principle is that no additional measures are required under this regulation; the building owner may take them if they wish.

    Official text
    In existing buildings where fire measures have been taken in compliance with the Regulation on the Fire Protection of Buildings put into force by Council of Ministers Decision No. 2002/4390 of 12/6/2002, the principle is that no additional measures are taken under the provisions of this Regulation. However, the building owner may, if they wish, take additional measures under the provisions of this Regulation.

    Source: BYKHY 138(2) · mevzuat.gov.tr

  142. Buildings, structures, facilities and premises whose designs in the building permit application were approved before 19/12/2007 are also considered existing buildings.

    Official text
    Buildings, structures, facilities and premises whose building designs attached to the building permit application were approved by the relevant authority before 19/12/2007 are also considered existing buildings for the purposes of applying this Regulation.

    Source: BYKHY 138(4) · mevzuat.gov.tr

  143. For existing buildings whose use changes and which are listed in 138(1), the provisions in the other parts of the regulation apply.

    Official text
    For those existing buildings whose use is changed after this Regulation enters into force and which are listed in paragraph one of Article 138, the provisions set out in the other parts of this Regulation apply.

    Source: BYKHY 139(1) · mevzuat.gov.tr

  144. If there is a use requiring an additional exit or the rearrangement of the escape stairs, the building owner or the flat owners have this arrangement made for the whole building.

    Official text
    If there is a use in the building requiring an additional exit or making it necessary to rearrange the escape stairs, an additional exit or escape stair must be built for the whole building by the building owner or the flat owners, taking the building as a whole into account.

    Source: BYKHY 141(1) · mevzuat.gov.tr

  145. On matters not specified or not clear in Part 10, the opinion of the authority competent to issue building permits prevails.

    Official text
    On matters not specified or not clear in this Part, the opinion of the authority competent to issue building permits prevails, and the measures to be taken are carried out by the building owner or the flat owners.

    Source: BYKHY 144(1) · mevzuat.gov.tr

  146. In an existing building with no more than 50 people per floor, the escape stair may be reached through a room: the room door is self-closing and unlocked, at most 9 m to the stair; if the room's walls and door are rated for 60 min and the door is smoke-tight, travel distance is taken to the room door.

    Official text
    In existing buildings, provided that the number of occupants on the floor does not exceed 50, exits with the features set out below are accepted as a second escape route: (...) b) Reaching the escape stair by passing through a room is permitted if the room door is self-closing and kept unlocked and the maximum distance from the door of the room giving access to the escape stair to the escape stair does not exceed 9 m. If the walls and door of this room are resistant to fire for at least 60 minutes and the door is smoke-tight, travel distance is taken up to the door of this room.

    Source: BYKHY 146(3)(b) · mevzuat.gov.tr

  147. At least 60 cm for a straight-flight stair with landings (70 cm if more than 60 people per floor); at least 100 cm in hospitals, care homes, kindergartens and primary schools.

    Official text
    The width of the escape stair cannot be less than 60 cm for a straight-flight stair with landings or 70 cm for a spiral stair. On floors with more than 60 occupants in total, this width cannot be less than 70 cm for straight-flight stairs with landings or 80 cm for spiral stairs. In hospitals, care homes, kindergartens and primary schools, only straight-flight stairs with landings may be provided, and the width of such a stair cannot be less than 100 cm.

    Source: BYKHY 148(1)(b) · mevzuat.gov.tr

  148. In a non-residential existing building over 30.50 m, if the stair is entered directly and there is no pressurisation, Article 34 applies.

    Official text
    In non-residential existing buildings with a building height of more than 30.50 m, where the escape stair is entered directly without passing through a use area such as a lobby, corridor or hall, and there is no pressurisation in the stair, Article 34 applies with regard to the fire safety lobby.

    Source: BYKHY 149(1)(a) · mevzuat.gov.tr

  149. In an existing building, a fire safety lobby is not mandatory if the escape stair doors open onto a corridor or lobby that contains no flammable substances and is separated from the occupied areas by doors.

    Official text
    In existing buildings, if the escape stair doors open onto corridors, lobbies and similar spaces that contain no flammable substances and are separated from the occupied areas by doors, building a fire safety lobby is not mandatory.

    Source: BYKHY 149(1)(b) · mevzuat.gov.tr

  150. In existing buildings, at least 2 exits in high-hazard places exceeding 25 people and places exceeding 60 people, at least 3 above 600 people, at least 4 above 1,000 people.

    Official text
    On a floor or part of a floor, at least 2 exits must be provided in high-hazard places where 25 people are exceeded, not being less than the calculated value, and in places where 60 people are exceeded; at least 3 exits where 600 people are exceeded; and at least 4 exits where 1,000 people are exceeded.

    Source: BYKHY 150(1)(a) · mevzuat.gov.tr

  151. Provided there is no unprotected wall opening within 1.8 m to the sides and it has the features of an escape stair, an external escape stair is permitted up to a building height of 51.50 m for dwellings and 30.50 m for other buildings.

    Official text
    In existing buildings, external escape stairs are permitted up to a building height of 51.50 m for dwellings and 30.50 m for other buildings, provided that there is no unprotected wall opening within a horizontal distance of 1.8 m to the sides of any part of them and that they have the features of an escape stair.

    Source: BYKHY 153(1) · mevzuat.gov.tr

  152. If there are unprotected openings within 1.8 m, on all floors these openings are converted to materials resistant to fire for at least 60 minutes, or the stair is placed in a 60-minute protected enclosure.

    Official text
    If there is an unprotected wall opening within a horizontal distance of 1.8 m to the sides of any part of it, the openings within this distance on all floors must be converted to materials resistant to fire for at least 60 minutes, or the escape stair must be placed in a protected enclosure of materials resistant to fire for 60 minutes to protect it from effects such as smoke and heat coming from these openings.

    Source: BYKHY 153(2) · mevzuat.gov.tr

  153. So that people escaping from upper floors do not go down to the basement, the stair's ground landing is separated from the basement stair by a door or similar physical barrier, or visible signage is provided.

    Official text
    To prevent occupants leaving the upper floors in an emergency from going down to the basement floor, the ground-level landing of the stair is separated from the basement stair by a door or a similar physical barrier, or suitable visible signage is provided.

    Source: BYKHY 156(3) · mevzuat.gov.tr

  154. In an existing building too, the exit door of a space with more than 50 people opens in the direction of escape; the door opens by hand and is not kept locked; revolving doors and turnstiles cannot be exit doors.

    Official text
    The leaves of escape route doors must not obstruct the movement of occupants, and exit doors in spaces with more than 50 occupants must open in the direction of escape. Escape route doors must be openable by hand and must not be kept locked. Revolving doors and turnstiles cannot be used as exit doors.

    Source: BYKHY 157(2) · mevzuat.gov.tr

  155. In existing buildings too, doors are fitted with self-closing devices and allow firefighters to enter from outside.

    Official text
    Doors must be fitted with self-closing devices, and firefighters or staff must be able to enter from outside when necessary.

    Source: BYKHY 157(3) · mevzuat.gov.tr

  156. In existing buildings, ground-level exit doors, and stair doors too if there are more than 100 people on a floor, open without using a handle, by a panic bar or similar device; opening force at most 110 N.

    Official text
    All escape route doors opening from the stair onto a safe area at natural ground level, and escape stair doors where the number of occupants on a floor exceeds 100, must be openable without using the door handle, by a panic bar or similar device. Doors are designed to open with a force of at most 110 N.

    Source: BYKHY 157(4) · mevzuat.gov.tr

  157. In existing buildings, a fire hose cabinet is mandatory in boiler rooms over 500 kW.

    Official text
    in enclosed car parks and in boiler rooms with a thermal capacity over 500 kW, a fire hose cabinet is mandatory.

    Source: BYKHY 164(2) · mevzuat.gov.tr

  158. R load-bearing, E integrity, I insulation, W radiation, M mechanical resistance, C self-closing, S smoke leakage.

    Official text
    Annex 3/A Fire Resistance Symbols of Building Elements R Load-bearing capacity E Integrity I Insulation W Radiation M Mechanical resistance C Self-closing S Smoke leakage

    Source: BYKHY Annex 3/A · mevzuat.gov.tr

  159. Unsprinklered office: basement >10 m 90, <10 m 60; ground/upper floors under 5 m 30, under 21.50 m 60, under 30.50 m 90, over 30.50 m not permitted. Sprinklered: 60, 60, 30, 30, 60, 120.

    Official text
    Annex 3/C Fire Resistance Durations by Building Use Class — 4. Office Buildings: no sprinkler system 90 | 60 | 30 | 60 | 90 | Not permitted; with sprinkler system 60 | 60 | 30 | 30 | 60 | 120.

    Source: BYKHY Annex 3/C (office) · mevzuat.gov.tr

  160. A compartment wall separating different uses is REI 60 or Annex 3/C (whichever is greater); other compartment walls per Annex 3/C. A compartment wall separating buildings is at least 60.

    Official text
    Fire Compartment Walls (separating different use functions within the building) REI 60 or see Annex 3c (whichever is greater). Fire Compartment Walls (other than those specified in No. 6) REI see Annex 3c. (2) Raised to at least 60 minutes for fire compartment walls separating buildings.

    Source: BYKHY Annex 3/B 6–7 · mevzuat.gov.tr

  161. Residential unlimited; accommodation 4,000, healthcare 1,500, education 6,000, office 8,000, commercial 2,000, food, drink and entertainment 4,000, other assembly 6,000, industrial OT-3+ 6,000 / OT-1-2 15,000, storage OT-3+ 1,000 / OT-1-2 5,000 m², enclosed car park no limit. With fire control systems (1) twice, (2) unlimited, (3) no limit if single-storey.

    Official text
    The maximum compartment area required in buildings is given in Annex 4. Note: (1) If suitable fire control systems (automatic detection, sprinkler system, smoke extraction system and the like) are installed in buildings, the compartment area may be doubled. (2) If suitable fire control systems (automatic detection, sprinkler system, smoke extraction system and the like) are installed in buildings, the compartment area is unlimited.

    Source: BYKHY Annex 4 · mevzuat.gov.tr

  162. Offices, association premises, public libraries 10 m²/person; supermarkets and shops 5; hospital bedrooms 20; others in the table.

    Official text
    Annex 5/A Occupant Load Factor Table

    Source: BYKHY Annex 5/A · mevzuat.gov.tr

  163. Hospitals, care homes: one-way 15 m (25 with sprinklers), two-way 30 m (45 with sprinklers), dead-end corridor 15 m (20 with sprinklers). Other uses in the table.

    Official text
    Annex 5/B Maximum Travel Distances to Exits and Unit Widths

    Source: BYKHY Annex 5/B · mevzuat.gov.tr

Source: Regulation on the Fire Protection of Buildings, official full text (mevzuat.gov.tr) · summaries are our own

02 Door articles

What does the Regulation require of a fire door?

Duration, closing, dimensions, locking, opening direction: each is a separate article. Tap a number to open it in the finder.

Fire escape stair regulation, Turkey – door from the stair landing to the floor

1 / 2 · Escape stair doorRead the door article by article; tap a number to open it in the finder.

Article47Part3.

  1. Rating and smoke60 or 90 minutes in a new building, smoke-tight. 47(3)
  2. ClosingSelf-closing device; firefighters can enter from outside. 47(3) 157(3)
  3. Size and thresholdClear width at least 80 cm, height at least 200 cm; no threshold. 47(1)
  4. Lock and forceNo lock or bolt that blocks escape; opening force at most 110 N. 30(4) 47(6)

Source: BYKHY 30(4), 47(1), 47(3), 47(6), 157(3)

03 Parts

How is the Regulation organised?

171 articles, 12 parts. The orange parts directly concern doors and glass; tap a part to open its articles in the finder.

art. 1art. 171

  1. 1.General provisions, use and hazard classesart. 1–19
  2. 2.General fire safety of buildingsart. 20–29
  3. 3.Escape routes and escape stairsart. 30–52
  4. 4.Building sections and installationsart. 53–66
  5. 5.Electrical installations and systemsart. 67–84
  6. 6.Smoke control systemsart. 85–89
  7. 7.Fire extinguishing systemsart. 90–100
  8. 8.Hazardous substancesart. 101–123
  9. 9.Responsibility, teams, training, inspectionart. 124–137
  10. 10.Existing buildingsart. 138–166
  11. 11.Historic buildingsart. 167
  12. 12.Final provisionsart. 168–171

Source: official BYKHY text, part titles shortened

04 Read together

Which articles are read together?

For some questions one article is not enough; which one applies is assessed together in the project.

  1. 38(3)47(3)

    Stair door: 90 or 60?

    38(3) gives 90 minutes to the door separating the stair; 47(3) states 60 for a stair serving fewer than 4 storeys in a new building. The duration is settled by reading the two articles together.

    Fire escape stair door

  2. 47(3)157(1)

    New building or existing building?

    In a new building the duration is set by the number of storeys the stair serves; in an existing building by building height: under 30.50 m 60, above it 90 minutes.

    EI60 fire door

  3. 25(1)25(2)

    Fire wall and the door in it

    The wall separating adjoining buildings is designed to resist fire for at least 90 minutes; the door and fixed glazing in it carry half the wall's duration.

    Fire wall door

  4. 30(4)47(5)

    No locks and opening without a handle

    No lock that obstructs escape is fitted; on a crowded floor and at the ground exit, the door opens in the direction of escape without using a handle.

    Emergency exit door

05 Amendments

When has the Regulation changed?

Nine dates since 2007. The last three are at the top; all open with a single tap.

  1. OG 26735 · BKK 2007/12937The Regulation was published and entered into force on the date of publication.
  2. 2009/15316 K.The broadest amendment: many provisions were revised, including the scope article.
  3. 2012/2958 K.Fire detection and extinguishing designs to be prepared separately from the building services designs.
  4. 2015/7401 K.Definitions updated: emergency, basement floor, external facade cladding.
  5. 2017/10459 K.A provision added for designs approved before 19.12.2007.
  6. 2018/11347 K.The scope provision on Turkish Armed Forces buildings changed.
  7. OG 31294 · Presidential Decision 3167The provisions on the legal basis article and on LPG vehicles entering enclosed car parks changed.
  8. OG 31665 · Presidential Decision 4825The Regulation was added to the Presidential Regulations section.
  9. OG 32943 · Provisional Article 4Deficiencies in existing buildings that require the supply of materials are remedied by 31.12.2025.

Source: amendment records in the official BYKHY text

06 Other legislation

Which legislation governs the door's documentation?

BYKHY sets the duration; construction products legislation governs the product's declaration and marking.

  1. Construction Products Regulation

    CE marking

    A CE mark cannot be affixed to a product without a declaration of performance.

    CE and G marking
  2. Regulation on the Criteria for Construction Products

    G mark

    A product without a harmonised technical specification is placed on the market with the G mark; a G Certificate or Declaration of Conformity is kept.

    Documents the fire brigade asks for
  3. Communiqué MHG/2017-13

    Classes follow the EU system

    The resistance durations in BYKHY Annex 3 are expressed in EU fire resistance classes (E, EI, C, S).

    Documents and compliance

Abay Yapı Sistemleri

Trusted for 30 years.

We manufacture doors and partitions in the class the Regulation requires, with Aliplast profiles and Polflam glass, in our workshop in Istanbul.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Fire protection regulation project Turkey – double leaf held open in a lift lobbyFire protection regulation project Turkey – glass partition and glazed doors in a stair hallFire protection regulation project Turkey – double leaf with panic bars, side and top lightsFire protection regulation project Turkey – glass partition between stair lobby and office
Lift lobby · Double leaf · top light
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Projects we have delivered in the class the Regulation requires.

Doors and partitions we have installed on escape routes, lobbies and compartment lines. Tap an image to enlarge it, use the arrows to browse.

07 FAQ

About the fire regulation

How an article applies to your project depends on the number of storeys, the building type and the door's location. Send us your project; let's mark the relevant articles together.

0216 428 38 20Send a question

Which is the fire regulation in Turkey?

The regulation governing fire safety in buildings is the Turkish Fire Regulation (Regulation on the Fire Protection of Buildings, BYKHY). It was published in the Official Gazette No. 26735 of 19 December 2007; it consists of 12 parts and 171 articles.

Source: BYKHY citation details

Where can the fire regulation PDF be downloaded?

From this page: the full official text as of 1 July 2025, with a reference cover page at the front. The Regulation entered into force on its publication date, 19 December 2007; the current, binding text is published on mevzuat.gov.tr.

Source: BYKHY 170, Provisional Article 4

What changed in the fire regulation in 2025?

Provisional Article 4 was added in the Official Gazette No. 32943 of 1 July 2025: deficiencies in existing buildings that require materials to be supplied are to be remedied by 31 December 2025, after which the permitting authority inspects.

Source: BYKHY Provisional Article 4

Does the fire regulation apply to existing buildings?

Part 10 (articles 138–166) sets separate provisions for existing buildings. For example, in an existing building the rating of a stair door is set by building height, not by the number of storeys.

Source: BYKHY 138–166, 157(1)

How does the Regulation define a fire door?

It is defined as a door, hatch or shutter that, when kept closed, resists the passage of smoke, heat and flame for a set time. The article governing the door's location sets what that time is.

Source: BYKHY 4(1)(şş)

Who is responsible for complying with the fire regulation?

The list of those responsible is wide: the permitting authority, investor, building owner, employer, the architects and engineers who design and build the project, contractor, manufacturer and building inspection.

Source: BYKHY 6(1)

Is an occupancy permit issued for a building that breaches the Regulation?

No. If the design does not comply with the Regulation, no permit is issued; if non-compliant work is found in a new building, no occupancy permit is issued until the deficiencies are remedied.

Source: BYKHY 5(1)