Fire door requirements
A fire door, when closed, resists the passage of smoke, heat and flame for a set time. How many minutes that time must be, and whether the door must be smoke-tight or self-closing, is set by the Turkish Fire Regulation (BYKHY) according to where the door is: 30 minutes for a hotel room door, 90 minutes for a boiler room, for example.
Stair doorThe number of storeys sets the duration
Floor doorFire behind the glass
- Fire resistance
- 30 · 60 · 90 min
- Deciding factor
- Door location
- Stair
- New / existing building
- Regulation
- BYKHY
01 Your door
How many minutes must your door resist fire?
Choose the door's location; the duration, properties and article the regulation requires will appear.
Where is the door? Tap a number on the section or the list.All locations
Fire side
Escape side
Escape stair · New · fewer than 4 storeys
- SSmoke-tight
- CSelf-closing
In a new building, the door of an escape stair serving fewer than 4 storeys resists the passage of smoke, heat and flame in a fire for at least 60 minutes. Article 38(3) states at least 90 minutes for escape stair doors in general; the two articles are read together.
Source: BYKHY 47(3), 38(3)
Our doors: Single leafDouble leaf
Escape stair · New · basement or more than 4 storeys
- SSmoke-tight
- CSelf-closing
If the stair serves basement floors or more than 4 storeys, its door resists fire for at least 90 minutes, is smoke-tight and is self-closing.
Source: BYKHY 47(3)
Our doors: Single leaf
Escape stair · Existing · below 30.50 m
- SSmoke-tight
- CSelf-closing
In an existing building, the building height counts, not the number of storeys: below 30.50 m, the stair door resists fire for at least 60 minutes and is smoke-tight.
Source: BYKHY 157(1), 157(3)
Our doors: Single leafDouble leaf
Escape stair · Existing · 30.50 m and above
- SSmoke-tight
- CSelf-closing
If the building height is 30.50 m or more, the stair door in an existing building also resists fire for at least 90 minutes and is smoke-tight.
Source: BYKHY 157(1), 157(3)
Our doors: Single leaf
Fire safety lobby · All buildings
- SSmoke-tight
- CSelf-closing
The fire safety lobby in front of the escape stair is separated from other areas by walls resisting fire for at least 120 minutes and a smoke-tight door resisting fire for at least 90 minutes. Lobby doors are self-closing.
Source: BYKHY 34(2), 47(3)
Our doors: Single leaf
Fire safety lobby · Office tower above 51.50 m
- SSmoke-tight
- CSelf-closing
An office building whose total height exceeds 51.50 m has at least one firefighting lift, and a fire safety lobby is built in front of the escape stair; the lift opens into this lobby. The lobby door resists fire for at least 90 minutes.
Source: BYKHY 34(7), 63(2), 34(2)
Our doors: Single leaf
Fire safety lobby · High-rise building
- SSmoke-tight
- CSelf-closing
In a building more than 21.50 m high above ground and more than 30.50 m in total height, escape routes and stairs are at least 120 cm wide. The lobby in front of the firefighting lift is 6–10 m²; its door resists fire for at least 90 minutes and is smoke-tight.
Source: BYKHY 4(1)(ccc), 33(2), 63(3), 34(2)
Our doors: Single leaf
Compartment boundary · All buildings
- Smoke- and heat-tight boundary
A fire compartment is separated on every side, ceiling and floor included, by elements resisting fire for at least 60 minutes. No unrated opening may exist between compartments; doors and glazing on the boundary carry the same duration.
Source: BYKHY 4(1)(tt), 24(7)
Our doors: Single leafDouble leafFixed glass partition
Compartment boundary · Hospital ward floor
- Smoke- and heat-tight boundary
In a hospital, every in-patient floor larger than 300 m² is divided into at least two fire compartments, or a protected horizontal evacuation area is provided. A door crossing the ward corridor carries the line's duration of at least 60 minutes.
Source: BYKHY 49(1)(b), 24(7)
Compartment boundary · Shopping centre atrium
- Smoke- and heat-tight boundary
In a commercial building, a compartment is at most 2,000 m² without fire control systems; doors and glass partitions crossing the shopping centre atrium carry the line's duration. In crowded areas the door opens in the direction of escape.
Source: BYKHY Annex 4, 24(7), 47(2)
Compartment boundary · Factory warehouse
- Smoke- and heat-tight boundary
In a factory, storage is separated from production by a fire-rated wall; a storage compartment of medium hazard-3 or above is at most 1,000 m² without a fire control system. The door in the wall carries the wall's duration.
Source: BYKHY 18(1), Annex 4, 24(7)
Our doors: Double leafSingle leafFixed glass partition
Compartment boundary · School corridor
- Smoke- and heat-tight boundary
In an educational building, a compartment is at most 6,000 m² without a fire control system; a door crossing the school corridor carries the line's duration. Doors of classrooms larger than 75 m² open in the direction of escape.
Source: BYKHY Annex 4, 24(7), 47(2)
Our doors: Double leafSingle leafFixed glass partition
Fire wall
- SSmoke-tight
- CSelf-closing
Where a door or fixed glazing in a fire wall cannot be avoided, it resists fire for at least half the wall's fire resistance duration. As a fire wall separating adjoining buildings is rated for at least 90 minutes, a door here resists fire for at least 45 minutes; it is self-closing and smoke-tight.
Source: BYKHY 25(1), 25(2)
Our doors: With side lightsFixed glass partition
Hotel internal corridor · Room door
- CSelf-closing
In hotels and dormitories, doors opening onto an internal corridor resist fire for at least 30 minutes and are fitted with a self-closing device.
Source: BYKHY 50(1)(b)
Our doors: Single leaf
Hotel internal corridor · Smoke-stop door
- SSmoke-tight
- CSelf-closing
Unventilated hotel internal corridors are divided by smoke-stop partitions. The smoke-stop partition resists fire for at least 60 minutes; the escape door within it also resists fire for at least 60 minutes and is smoke-tight; a smoke-tight door is self-closing.
Source: BYKHY 50(6)(a), 50(6)(c)
Our doors: Double leafWith side lights
Boiler room
- SSmoke-tight
- CSelf-closing
Boiler room exit doors resist fire for at least 90 minutes, are smoke-tight and are self-closing. A boiler room door cannot open directly onto an escape stair; it opens onto a common lobby or corridor.
Source: BYKHY 54(4), 54(5)
Our doors: Single leaf
External passage door
- CSelf-closing
An exit door opening onto an external passage resists fire for at least 30 minutes and is fitted with a self-closing device.
Source: BYKHY 37(2)
Our doors: Single leafDouble leaf
The final class is set by the project designer, the fire consultant and fire brigade approval. This tool is guidance, not legal advice.
02 All locations
How many minutes must a door resist fire in each location?
Nine rows in one table; each row states what the article explicitly requires. EI30 · EI60 · EI90 · EI120
| Door location | Fire resistance | What the article requires | BYKHY |
|---|---|---|---|
| Escape stair (new building) | At least 60 or 90 min | Smoke-tight, self-closing | 47(3) |
| Escape stair (existing building) | At least 60 or 90 min | Smoke-tight, self-closing | 157(1), 157(3) |
| Fire safety lobby | At least 90 min | Smoke-tight, self-closing | 34(2), 47(3) |
| Boiler room exit | At least 90 min | Smoke-tight, self-closing | 54(5) |
| Door in a fire wall | At least half the wall's duration | Smoke-tight, self-closing | 25(2) |
| Compartment boundary | At least 60 min | Smoke- and heat-tight boundary | 4(1)(tt), 24(7) |
| Smoke-stop door in a hotel corridor | At least 60 min | Smoke-tight, self-closing | 50(6)(a), 50(6)(c) |
| Hotel room to internal corridor | At least 30 min | Self-closing | 50(1)(b) |
| Exit onto an external passage | At least 30 min | Self-closing | 37(2) |
03 Letters on the certificate
What do the letters E, I, S and C on a fire door certificate mean?
The regulation's durations are written on the certificate with these letters and the minutes, for example EI60 S C. The difference between E, EW and EI
- E
Flame-tight
Throughout the fire, the door stops flames and hot gases passing to the other side.
- I
Blocks heat
The surface on the escape side does not heat up either, so people passing it are protected. EI shows both together.
- S
Smoke-tight
When closed, smoke does not pass around the edges or between the leaves.
- C
Self-closing
The door closer shuts the door every time; it does not stay open.
04 Responsibility
What happens if a fire door does not comply with the regulation, and who is responsible?
Two articles bind every stage of the project.
- BYKHY 5(1)
Building permit and occupancy permit
If the design does not comply with the regulation, no building permit is issued. If a new building is found not to have been built in compliance, no occupancy permit is issued until the deficiencies are remedied.
- BYKHY 6(1)
Responsible parties
The permit-issuing authority, investor, building owner, employer, the architects and engineers in design and construction, contractor, manufacturer and building inspection.
Abay Yapı Sistemleri
Trusted for 30 years.
We manufacture the fire door and glass partition each location requires with Aliplast profiles and Polflam glass in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Doors from our reference projects in the locations the regulation covers.
Work we have completed on stairs, lobbies, escape exits and compartment boundaries. Tap a photo to enlarge it; browse with the arrows.
05 Document set
Which document shows that the door meets the requirement?
The duration and properties the regulation requires must appear in the door's own classification report and declaration of performance.
Four checks at handover
- Fire resistance. The minutes in the report must not be less than the duration the door's location requires.
- S and C. If the location requires smoke tightness or self-closing, these letters must appear on the certificate.
- Type and size. The door tested in the report must be the same type as the project door and no smaller.
- Declaration and CE. The declaration of performance and CE marking must be issued for the door itself.
- ClassificationThe door's classification reportMatching the type and size of the door in the projectRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- AuthorisationAliplast manufacturing authorisationAuthorised manufacturer and distributor in TurkeyRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Ask for your project's document set. Document details: for the fire brigade and occupancy permit.
Request the document set06 FAQ
About fire door requirements
The final class is set by the project designer, the fire consultant and fire brigade approval. Ask us how it applies to your project.
What is a fire door?
Under the regulation, a fire door is a door, hatch or shutter that, when kept closed, resists the passage of smoke, heat and flame for a set time. That time varies with the door's location.
Source: BYKHY 4(1)(şş)
How many minutes must a fire door resist fire?
There is no single duration; the door's location decides. A door from a hotel room to the corridor resists fire for at least 30 minutes, a compartment boundary for at least 60, and a fire safety lobby or boiler room door for at least 90 minutes. An escape stair door is 60 or 90 minutes, depending on the building.
Source: BYKHY 50(1)(b), 4(1)(tt), 34(2), 54(5), 47(3)
What is a fire compartment?
An area within a building separated smoke- and heat-tight on every side, ceiling and floor included, by elements resisting fire for at least 60 minutes. No unrated opening may be left between compartments.
Source: BYKHY 4(1)(tt), 24(7)
What is a high-rise building?
A building more than 21.50 m high above ground and more than 30.50 m in total height. In existing buildings, the 30.50 m limit also decides whether the stair door must resist fire for 60 or 90 minutes.
Source: BYKHY 4(1)(ccc), 157(1)
What happens if a compliant fire door is not installed?
If the design does not comply with the regulation, no building permit is issued. If a new building is found not to have been built in compliance with the regulation, no occupancy permit or operating licence is issued until the deficiencies are remedied.
Source: BYKHY 5(1)
Who is responsible for the fire door?
The permit-issuing authorities, investors, building owners, employers, the architects and engineers in design and construction, contractors, manufacturers and building inspection are responsible for applying the regulation.
Source: BYKHY 6(1)
Must a smoke-tight door be single-leaf?
It can be single- or double-leaf. It must be self-closing, the leaves must close the opening completely, and the gap between leaf and floor must not exceed 4 mm.
Source: BYKHY 50(6)(c)