C8Fire criteria · building type

Hospital fire door

In a hospital, the fire door stands on the compartment line that divides the ward floor. Every in-patient floor larger than 300 m² is divided into at least two fire compartments or protected horizontal evacuation areas; the line and the door within it resist fire for at least 60 minutes. Patients are moved in their beds to the adjoining section on the same floor; corridors are at least 2 m wide.

Hospital fire door Turkey – double leaf with side lights on a ward corridor
Ward floor corridor · Abay installation
Ward floor over 300 m²
At least two compartments
Fire resistance of the line and door
At least 60 minutes
Compartment area in healthcare
Up to 1,500 m²
Corridor width
At least 2 m
Travel distance (without sprinklers)
One direction 15 m · two directions 30 m

01 Compartment

How many fire compartments should your ward floor be divided into?

A fire compartment is a section separated by walls and floors that resist fire for at least 60 minutes on every side. Enter the area of your ward floor; the plan divides itself.

2Fire control systems

2compartmentsminimum · this floor

A 1,800 m² ward floor is divided into at least two compartments; split equally, each is about 900 m².

The line and the door within it resist fire for at least 60 minutes. A protected horizontal evacuation area may be provided instead of a line.

Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4

stairstairPATIENT WARD PLAN · not to scaleK1,800 m² · patient ward floor––
Compartment line60 min wallEscape stair

02 What the door needs

What should you check on a hospital door?

First the door on the ward corridor and its hold-open device, then the entrance to the horizontal evacuation area where patients take refuge; tap a tab to fix the view.

Hospital fire door Turkey – ward floor compartment crossing

1 / 2 · Compartment door and hold-open deviceThe other half of the corridor is on fire; this side is clear.

Door≥ 60 minCorridor≥ 2 m

  1. DoorThe door on the line is fire-resistant; it carries the line's rating of at least 60 minutes.
  2. Hold-open deviceAn electromagnetic hold-open device keeps the door open; in a fire the system releases it and the door closes.
  3. CorridorA hospital corridor is at least 2 m wide; the door closes off the full width of the corridor.

Source: BYKHY 4(1)(tt), 24(7), 49(2), 82(1)(a)

03 Ward floor

How is a hospital ward floor divided?

Ward floor plan: corridor, patient rooms on both sides, an 18-bed ward, nurses' station, two compartments and two escape stairs. Tap a rule; the relevant part of the plan turns orange.

Ward floor over 300 m²: at least two compartments

In hospitals and care homes, every in-patient floor over 300 m² is divided into two or more compartments of at least half its size, or a protected horizontal evacuation area is provided. In healthcare, a compartment is at most 1,500 m².

ExampleOn the plan, the floor is split into compartments A and B by a line running west of the nurses' station.

Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4

stairstair18-bed roomnursesCOMPARTMENT ACOMPARTMENT BPATIENT WARD PLAN · 1/250K0 – 5 m123456
60 min wallEscape stairEscape route

04 Four locations

Where are compartment doors found in healthcare buildings?

Four situations in hospitals and care homes; choose a location and the requirements for the door there are marked alongside.

05 Your project

Which fire doors does your hospital need?

These four answers determine the compartment lines and their doors.

  1. 01

    How many m² are the ward floors?

    Every in-patient floor over 300 m² is divided into at least two compartments; in healthcare a compartment is at most 1,500 m².

  2. 02

    Are there fire control systems?

    If suitable systems such as detection, sprinklers and smoke extraction are installed, the compartment area can rise to 3,000 m².

  3. 03

    Where will the beds pass?

    Corridors are at least 2 m wide; the compartment door closes off the corridor from side to side.

  4. 04

    Will the doors stand open during the day?

    A door that stands open is connected to an electromagnetic hold-open device that the emergency control system releases in a fire.

Let's draw the compartment lines of your ward floors together. Send your floor plans and bed numbers and our technical team will review them.

Send the project

06 Glazed door

Can a hospital compartment door be glazed?

The door across the ward corridor and the partition above it are made with Aliplast profiles and Polflam glass in the 60-minute class.

  1. Bed passage

    Double leaf

    A glazed door that closes off a ward corridor over 2 m wide with two leaves. Double leaf

  2. Wide corridor

    With side lights

    Where the corridor is wider than the door opening, a door with fixed glazing on both sides. With side lights

  3. Above the door

    Fixed glass partition

    Profiled fixed glazing that closes the line up to the ceiling. Fixed partition

In a horizontal evacuation area, the article also requires smoke passage to be prevented; this requirement is documented together with the door's number of leaves and size. Aliplast FR65

Abay Yapı Sistemleri

Trusted for 30 years.

We make hospital compartment doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Hospital fire door project Turkey – double leaf with panic bars, side and top lightsHospital fire door project Turkey – double leaf held open in a lift lobby
Lobby passage door · Double leaf · side and top lights
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Wide doors across corridors from our reference projects.

Top row: our double-leaf and side-light doors suited to moving beds; below: single-leaf and partition installations. Tap a photo; browse with the arrows.

07 Document set

Which documents are required for a hospital compartment door?

The line and its door resist fire for at least 60 minutes; at handover, the rating, the door size and the hold-open connection are shown with documents.

Four checks at handover

  1. Door and partition. The classification report for the door and the partition must show fire resistance of at least 60 minutes.
  2. Size. The leaf size covered by the report must suit the width of the ward corridor.
  3. Installation. Partition tight to the ceiling and wall; continuous at the junctions of the line.
  4. Hold-open device. The hold-open device of a door kept open must be connected to the emergency control system.
  • ClassificationClassification report for the compartment doorWith number of leaves and sizeRequest
  • ClassificationClassification report for the top and side glazed partitionWith height and glass sizeRequest
  • DeclarationDeclaration of performanceCE markedRequest it
  • DrawingLine, ceiling and wall junction detailsDWGRequest

Source: Turkish Construction Products Regulation 6(1), 10(2)

Request the compartment door's document set. The set is prepared for the type and size of the door and partition.

Request the document set

08 FAQ

About hospital fire doors

In a hospital, the position of the lines is finalised in the architectural design, the fire consultant's report and the fire brigade approval. Send your floor plans; let's work out the number and class of doors together.

0216 428 38 20Send a question

How many minutes should a hospital fire door resist fire?

The compartment line dividing the ward floor and the horizontal evacuation area resist fire for at least 60 minutes; the door on the line is also fire-resistant and carries the line's rating. The ratings of escape stair and fire safety lobby doors are set in their own articles.

Source: BYKHY 4(1)(tt), 24(7), 32(7)

How many compartments should a hospital ward floor be divided into?

Every in-patient floor larger than 300 m² is divided into at least two compartments, or a protected horizontal evacuation area is provided. In a healthcare building a compartment is at most 1,500 m²; with suitable fire control systems, 3,000 m².

Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4

What is horizontal evacuation?

It means occupants moving away from the fire and taking refuge in the adjoining compartment on the same floor that fire cannot pass. A horizontal evacuation area resists fire for at least 60 minutes and the article requires smoke passage to be prevented; 2.8 m² per person is used when sizing the area.

Source: BYKHY 4(1)(s), 32(7), 49(1)(b)

How wide must a hospital corridor be?

In hospitals, corridors may not be less than 2 m wide. The dimension applies to the ward floors and to every other corridor in the hospital.

Source: BYKHY 49(2)

Can a hospital fire door be held open?

Doors that must close in a fire may normally be held open with an electromagnetic hold-open device. In a fire, the emergency control system releases these devices automatically.

Source: BYKHY 82(1)(a)

What is the maximum travel distance in a hospital?

In a hospital without sprinklers, 15 m for one-way escape and 30 m for two-way escape; with sprinklers, 25 m and 45 m. Where there is a horizontal evacuation area, the distance is measured up to the exit door of the corridor leading to that area.

Source: BYKHY Annex 5/B, 32(7)

How many doors should a crowded patient room have?

Every patient bedroom or suite with an occupant load of more than 15 people has two doors located far apart. The same rule applies to care homes and nursing homes.

Source: BYKHY 49(1)(a)

→ Quote

Tell us about your hospital's doors.

Number of floors, ward floor areas, number of beds: our technical team will determine the compartment doors, their class and the document set, and get back to you.