C8Fire criteria · building type
Hospital fire door
In a hospital, the fire door stands on the compartment line that divides the ward floor. Every in-patient floor larger than 300 m² is divided into at least two fire compartments or protected horizontal evacuation areas; the line and the door within it resist fire for at least 60 minutes. Patients are moved in their beds to the adjoining section on the same floor; corridors are at least 2 m wide.
- Ward floor over 300 m²
- At least two compartments
- Fire resistance of the line and door
- At least 60 minutes
- Compartment area in healthcare
- Up to 1,500 m²
- Corridor width
- At least 2 m
- Travel distance (without sprinklers)
- One direction 15 m · two directions 30 m
01 Compartment
How many fire compartments should your ward floor be divided into?
A fire compartment is a section separated by walls and floors that resist fire for at least 60 minutes on every side. Enter the area of your ward floor; the plan divides itself.
2Fire control systems
2compartmentsminimum · this floor
A 1,800 m² ward floor is divided into at least two compartments; split equally, each is about 900 m².
The line and the door within it resist fire for at least 60 minutes. A protected horizontal evacuation area may be provided instead of a line.
Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4
02 What the door needs
What should you check on a hospital door?
First the door on the ward corridor and its hold-open device, then the entrance to the horizontal evacuation area where patients take refuge; tap a tab to fix the view.
1 / 2 · Compartment door and hold-open deviceThe other half of the corridor is on fire; this side is clear.
- DoorThe door on the line is fire-resistant; it carries the line's rating of at least 60 minutes.
- Hold-open deviceAn electromagnetic hold-open device keeps the door open; in a fire the system releases it and the door closes.
- CorridorA hospital corridor is at least 2 m wide; the door closes off the full width of the corridor.
Source: BYKHY 4(1)(tt), 24(7), 49(2), 82(1)(a)
2 / 2 · Entrance to the horizontal evacuation areaThe camera is in the section where patients take refuge; the fire is in the adjoining corridor.
- PartitionThe area resists fire for at least 60 minutes; the article also requires smoke passage to be prevented.
- DoorPatients pass through this door into the adjoining section; travel distance is measured up to this door.
- AreaWhen sizing the area, 2.8 m² is allowed per person.
Source: BYKHY 4(1)(s), 32(7), 49(1)(b)
03 Ward floor
How is a hospital ward floor divided?
Ward floor plan: corridor, patient rooms on both sides, an 18-bed ward, nurses' station, two compartments and two escape stairs. Tap a rule; the relevant part of the plan turns orange.
Ward floor over 300 m²: at least two compartments
In hospitals and care homes, every in-patient floor over 300 m² is divided into two or more compartments of at least half its size, or a protected horizontal evacuation area is provided. In healthcare, a compartment is at most 1,500 m².
ExampleOn the plan, the floor is split into compartments A and B by a line running west of the nurses' station.
Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4
The door on the line carries the line's rating
The walls and floors enclosing a compartment resist fire for at least 60 minutes; there may be no non-fire-resisting opening between two compartments. The door that cuts across the corridor also carries the line's rating, backed by its certificate.
ExampleOn the plan, the double-leaf door in the corridor is the only passage between A and B.
Source: BYKHY 4(1)(tt), 24(7)
Hospital corridors at least 2 m wide
In hospitals, corridors may not be less than 2 m wide. The rule applies to the ward floor corridor and to every other corridor in the hospital.
ExampleOn the plan, the corridor is 2.50 m; the compartment door closes off its full width.
Source: BYKHY 49(2)
Two doors far apart in a crowded patient room
A patient bedroom or suite with an occupant load of more than 15 people has two doors located far apart. If fire blocks one door, people leave by the other.
ExampleOn the plan, the doors of the 18-bed ward are at its two ends.
Source: BYKHY 49(1)(a)
Travel distance is measured to the horizontal evacuation door
Where there is a horizontal evacuation area that resists fire for at least 60 minutes with smoke passage prevented, travel distance is measured up to the exit door of the corridor leading to that area. In a hospital without sprinklers the limit is 15 m in one direction and 30 m in two directions; with sprinklers, 25 and 45 m.
ExampleOn the plan, the route from the furthest room door in B to the compartment door.
Source: BYKHY 32(7), Annex 5/B
From every section to a protected escape route
Every horizontal evacuation area gives access to at least one protected escape route. In a hospital, a dead-end corridor is at most 15 m long in a building without sprinklers and at most 20 m in a building with sprinklers.
ExampleOn the plan, A connects to the western escape stair and B to the eastern one.
Source: BYKHY 32(7), Annex 5/B
04 Four locations
Where are compartment doors found in healthcare buildings?
Four situations in hospitals and care homes; choose a location and the requirements for the door there are marked alongside.
Fire side
Escape side
- On a hospital bed floor The door that cuts across the corridor on the floor with the beds is part of the compartment line. On a floor over 300 m², patients are moved in their beds to the compartment on the other side of the line. BYKHY 49(1)(b), 24(7)60 Fire compartment page
- On an intensive care floor Intensive care is also a unit where patients are bedded. In progressive horizontal evacuation, patients move away from the fire into the adjoining compartment on the same floor that fire cannot pass. BYKHY 4(1)(s), 49(1)(b)60
- In care homes and nursing homes Care homes, nursing homes and rehabilitation centres are also healthcare buildings. In care homes for elderly and disabled people, the ward floor rules are the same as in a hospital. BYKHY 11(1)(b), 49(1)60
- From the section to the escape stair Every horizontal evacuation area gives access to at least one protected escape route. The escape stair door that opens onto the ward corridor is where that route begins. BYKHY 32(7)60 Fire escape stair door page
05 Your project
Which fire doors does your hospital need?
These four answers determine the compartment lines and their doors.
- 01
How many m² are the ward floors?
Every in-patient floor over 300 m² is divided into at least two compartments; in healthcare a compartment is at most 1,500 m².
- 02
Are there fire control systems?
If suitable systems such as detection, sprinklers and smoke extraction are installed, the compartment area can rise to 3,000 m².
- 03
Where will the beds pass?
Corridors are at least 2 m wide; the compartment door closes off the corridor from side to side.
- 04
Will the doors stand open during the day?
A door that stands open is connected to an electromagnetic hold-open device that the emergency control system releases in a fire.
Let's draw the compartment lines of your ward floors together. Send your floor plans and bed numbers and our technical team will review them.
Send the project06 Glazed door
Can a hospital compartment door be glazed?
The door across the ward corridor and the partition above it are made with Aliplast profiles and Polflam glass in the 60-minute class.
Bed passage
Double leaf
A glazed door that closes off a ward corridor over 2 m wide with two leaves. Double leaf
Wide corridor
With side lights
Where the corridor is wider than the door opening, a door with fixed glazing on both sides. With side lights
Above the door
Fixed glass partition
Profiled fixed glazing that closes the line up to the ceiling. Fixed partition
In a horizontal evacuation area, the article also requires smoke passage to be prevented; this requirement is documented together with the door's number of leaves and size. Aliplast FR65
Abay Yapı Sistemleri
Trusted for 30 years.
We make hospital compartment doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul


- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Wide doors across corridors from our reference projects.
Top row: our double-leaf and side-light doors suited to moving beds; below: single-leaf and partition installations. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a hospital compartment door?
The line and its door resist fire for at least 60 minutes; at handover, the rating, the door size and the hold-open connection are shown with documents.
Four checks at handover
- Door and partition. The classification report for the door and the partition must show fire resistance of at least 60 minutes.
- Size. The leaf size covered by the report must suit the width of the ward corridor.
- Installation. Partition tight to the ceiling and wall; continuous at the junctions of the line.
- Hold-open device. The hold-open device of a door kept open must be connected to the emergency control system.
- ClassificationClassification report for the compartment doorWith number of leaves and sizeRequest
- ClassificationClassification report for the top and side glazed partitionWith height and glass sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingLine, ceiling and wall junction detailsDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the compartment door's document set. The set is prepared for the type and size of the door and partition.
Request the document set08 FAQ
About hospital fire doors
In a hospital, the position of the lines is finalised in the architectural design, the fire consultant's report and the fire brigade approval. Send your floor plans; let's work out the number and class of doors together.
How many minutes should a hospital fire door resist fire?
The compartment line dividing the ward floor and the horizontal evacuation area resist fire for at least 60 minutes; the door on the line is also fire-resistant and carries the line's rating. The ratings of escape stair and fire safety lobby doors are set in their own articles.
Source: BYKHY 4(1)(tt), 24(7), 32(7)
How many compartments should a hospital ward floor be divided into?
Every in-patient floor larger than 300 m² is divided into at least two compartments, or a protected horizontal evacuation area is provided. In a healthcare building a compartment is at most 1,500 m²; with suitable fire control systems, 3,000 m².
Source: Turkish Fire Regulation (BYKHY) 49(1)(b), Annex 4
What is horizontal evacuation?
It means occupants moving away from the fire and taking refuge in the adjoining compartment on the same floor that fire cannot pass. A horizontal evacuation area resists fire for at least 60 minutes and the article requires smoke passage to be prevented; 2.8 m² per person is used when sizing the area.
Source: BYKHY 4(1)(s), 32(7), 49(1)(b)
How wide must a hospital corridor be?
In hospitals, corridors may not be less than 2 m wide. The dimension applies to the ward floors and to every other corridor in the hospital.
Source: BYKHY 49(2)
Can a hospital fire door be held open?
Doors that must close in a fire may normally be held open with an electromagnetic hold-open device. In a fire, the emergency control system releases these devices automatically.
Source: BYKHY 82(1)(a)
What is the maximum travel distance in a hospital?
In a hospital without sprinklers, 15 m for one-way escape and 30 m for two-way escape; with sprinklers, 25 m and 45 m. Where there is a horizontal evacuation area, the distance is measured up to the exit door of the corridor leading to that area.
Source: BYKHY Annex 5/B, 32(7)
How many doors should a crowded patient room have?
Every patient bedroom or suite with an occupant load of more than 15 people has two doors located far apart. The same rule applies to care homes and nursing homes.
Source: BYKHY 49(1)(a)
→ Quote
Tell us about your hospital's doors.
Number of floors, ward floor areas, number of beds: our technical team will determine the compartment doors, their class and the document set, and get back to you.
- Phone
- +90 216 428 38 20
- abay@abayyapi.com
- Production
- Istanbul