S120Fire criteria · duration
EI120 fire resistance
EI120 shows that a wall, glass partition or glass maintains its integrity (E) and insulation (I) for 120 minutes in a fire. The walls of an escape stair and a fire safety lobby, the partitions of a boiler room and shaft walls in a high-rise building need at least 120 minutes; for a door in these walls the regulation specifies 90 minutes.
- The letters in EI120
- E integrity · I insulation
- Stair and lobby walls
- At least 120 min
- The door in this wall
- At least 90 min
- Boiler room partition
- At least 120 min
- Polflam EI120 glass
- 35 / 40 mm
01 How many minutes?
How many minutes must your wall and door resist?
Choose the location; the scale compares the duration required for the glazed wall and the door with the limits of the FR90 door and the EI120 glass.
1Location
2Wall rating, min
120minutesminimum · glazed wall
The wall separating a stair core needs at least 120 minutes and its door at least 90; the door also does not let smoke through. An EI120 partition is enough for the glazed wall and an EI90 door for the door.
- Glass wall EI120Glass 35 / 40 mm
- Door 90 minFR90 door
- Smoke-tight doorRequired by the article
- The partition's own reportFramed or frameless
Source: BYKHY 25(2), 25(3), 34(2), 38(3), 54(2), 54(5), 57(3)
02 Glazed wall
What to look for in a 120-minute glazed wall
First the glazed wall of a stair core, then the fire safety lobby; tap a view and it stays where it is.
1 / 2 · Glazed wall of a stair coreCamera on the stair landing; fire on the office floor.
- WallThe glazed wall separating the stair resists fire for at least 120 minutes; in a framed partition the glass is 35 or 40 mm.
- DoorThe door in the wall needs at least 90 minutes and does not let smoke through.
- JunctionThe door and the glazed wall are on the same line; each carries its own class with its own report.
Source: BYKHY 38(3); Polflam catalogue
2 / 2 · Glazed wall of a fire safety lobbyCamera in the lobby; fire in the floor corridor.
- WallThe lobby is separated from the other parts by a wall of at least 120 minutes; in a glazed wall the glass is of this class too.
- DoorThe lobby door must resist for one and a half hours; its closer shuts the door automatically, and the door also holds back smoke.
- MaterialThe lobby's walls, ceiling and floor are made of non-combustible material.
Source: BYKHY 34(2), 47(3)
03 Building section
Where are the 120-minute walls in a building?
The building in the section has five storeys and a basement: the stair and the lobby on each floor, a vertical shaft, the boiler room and fuel store in the basement, and the fire wall facing the neighbouring building. Tap one of the rules; its place is drawn in orange in the section.
What does EI120 tell you?
The letter E stands for integrity and the letter I for insulation. A glazed wall in class EI120 maintains these two properties for 120 minutes in a fire.
ExampleLobby wall on the third floor in the section: EI 120.
Source: BYKHY Annex 3/A
Wall separating the stair 120, its door 90
An escape stair is separated from the other parts by a wall of at least 120 minutes; a door opening in this wall resists fire for at least 90 minutes and does not let smoke through.
ExampleThe stair wall running from the basement to the roof is 120; its doors are 90.
Source: BYKHY 38(3)
Fire safety lobby wall 120, its door 90
The wall separating the lobby from the floors resists fire for two hours and the lobby door for one and a half hours; the door does not let smoke through. In a glazed lobby wall the glass is also in the 120-minute class.
ExampleThe lobby on every floor in the section: wall 120, door 90.
Source: BYKHY 34(2)
Shaft wall in a high-rise building 120, its hatch 90
In high-rise buildings, the walls of refuse, communication, document and technical equipment shafts resist fire for at least 120 minutes and their hatches for at least 90; neither lets smoke through.
ExampleVertical shaft in the section: wall 120, hatch on every floor 90.
Source: BYKHY 25(3)
Boiler room and fuel store partition 120
A boiler room is separated from the rest of the building by partitions of at least 120 minutes; the partition between it and the fuel store is also 120 minutes.
ExampleThe partitions on both sides of the boiler room in the basement: 120.
Source: BYKHY 54(2), 56(1)
Door and glass in a 240-minute fire wall: 120
A door and a fixed light in a fire wall carry at least half the wall's resistance; in a 240-minute wall this is 120 minutes.
ExampleThe ground-floor door needs 120 minutes, half of the 240-minute wall.
Source: BYKHY 25(1), 25(2)
04 Four locations
Where are 120-minute glass partitions used?
Four buildings, four partitions; choose a location and the duration required there appears beside it.
Fire side
Escape side
- In a shopping centre kitchen A kitchen on the food court floor is separated from the other parts of the building by a partition of at least 120 minutes; if the partition is glazed, EI120 glass is used. BYKHY 57(3)120 Shopping centre page
- In a boiler room The partition enclosing a boiler room needs 120 minutes and its exit door 90; the separation from the fuel store is also a 120-minute partition. BYKHY 54(2), 56(1)120 Boiler room door page
- In a factory fire wall Fixed glass and a door in a 240-minute fire wall carry 120 minutes, half the wall's duration. BYKHY 25(2)120 Factory and warehouse page
- At a residential basement entrance In a residential building, a basement whose entrance, exit and shafts are separated from the upper floors by a 120-minute partition is not counted in the total building height. BYKHY 48(7)120
05 Your project
Which walls in your project must be 120 minutes?
The answers to these four questions separate the 120-minute walls from the 90-minute doors.
- 01
What does the glazed wall separate?
Stair, lobby, boiler room or kitchen: in all four the wall needs 120 minutes.
- 02
Is there a door in the wall?
90 minutes is enough for the door of a stair, lobby or boiler room.
- 03
Is it in a fire wall?
Fixed glass and doors carry half the wall's duration: 120 in a 240-minute wall.
- 04
Framed or frameless?
Both can be made as EI120; in a frameless partition the panes join without mullions.
Send your plan and we will mark the 120-minute walls together. A floor plan and the partition locations are enough.
Send the plan06 Products
Which glazed systems are made as EI120?
Aliplast FR90 profile and Polflam glass: 120 minutes in a glazed wall and fixed glass; in a door the class goes up to EI90.
BR + FR90
Frameless partition
The panes join without mullions; BR EI120 glass is 50 mm. Frameless glass partition
FR90
Fixed glass partition
Framed partition up to 120 minutes; glass 35 or 40 mm. Fixed partition
FR90
Door with side lights
The fixed glass beside the door goes up to 120 minutes; the door is class EI90 in FR90. With side lights
For a door in a 120-minute wall, the regulation specifies 90 minutes. EI90 fire door
Abay Yapı Sistemleri
Trusted for 30 years.
We make EI120 glass partitions with Aliplast FR90 profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul





- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Glass partitions and fixed-glass lines from our reference projects.
Projects where we have installed glass walls and partitions; below, the doors on the same lines. Tap a photo to enlarge it and use the arrows to move on.
07 Document set
Which document states the 120 minutes of an EI120 partition?
The partition's duration is in the test document for its own type; the thickness and class of the glass are in the Polflam declaration.
Four checks at handover
- Class. The partition's document must state at least EI 120.
- Type. The document must cover the partition's own type: framed or frameless.
- Size. The partition to be built must not exceed the height and glass size tested in the document.
- Door. The 90 minutes of the door in the wall are shown in a separate document.
- Test resultPolflam BR EI120 + Aliplast FR90Frameless partition · EI 120Document centre
- DeclarationPolflam EI120 glass35 / 40 mmDocument centre
- CatalogueAliplast FR90 partitionEI 30 – EI 120Document centre
- AuthorisationAliplast manufacturing authorisationAbay Yapı's manufacturing authorisationDocument centre
Source: Aliplast and Polflam documents
Request the documents for your 120-minute partitions. The documents are compiled for the partition's type and size.
Document centre08 FAQ
About EI120 fire resistance
Which wall needs 120 minutes and which door 90 can be seen on the plan. Send your plan and we will sort them out together.
What does EI120 mean?
EI120 describes a wall, partition or glass that does not lose its integrity (E) and insulation (I) for two hours in a fire; the meanings of the letters are in the regulation's Annex 3/A table.
Source: BYKHY Annex 3/A
Where is EI120 mandatory?
Walls separating an escape stair and a fire safety lobby, boiler room partitions, the separation between the fuel store and the boiler room, kitchen partitions and shaft walls in a high-rise building need at least 120 minutes.
Source: BYKHY 25(3), 34(2), 38(3), 54(2), 56(1), 57(3)
How many minutes should a door in a 120-minute wall resist?
For a door in the 120-minute wall of a stair, lobby or boiler room, the regulation specifies at least 90 minutes. Where the door itself needs 120 minutes is a 240-minute fire wall.
Source: BYKHY 25(2), 34(2), 38(3), 54(5)
How thick is EI120 fire glass?
In a framed partition Polflam EI120 glass is 35 or 40 mm; in a frameless partition Polflam BR EI120 glass is 50 mm. The partition's class is set by the report in which glass and profile were tested together.
Source: Polflam catalogue
Can a frameless glass partition be EI120?
Yes. A partition whose panes join without mullions has been tested for 120 minutes with Polflam BR EI120 glass and an Aliplast FR90 perimeter profile.
Source: Polflam BR EI120 + Aliplast FR90 test result
How many minutes should a boiler room wall resist?
The partitions separating a boiler room from the rest of the building resist fire for at least 120 minutes; the partition between it and the fuel store is also 120 minutes. The exit doors need 90 minutes.
Source: BYKHY 54(2), 54(5), 56(1)
What does separating the basement with a 120-minute partition achieve?
In a residential building, a basement whose entrance, exit and shafts are separated from the upper floors by a 120-minute floor slab or partition is not counted in the total building height and is assessed separately for fire safety measures.
Source: BYKHY 48(7)
→ Quote
Tell us about your EI120 partitions.
Write the partition's location, length and height: our technical team will determine whether it should be framed or frameless, the class and the document set, and get back to you.