C14Fire criteria · building status
In new and existing buildings Fire doors
Under the Turkish Fire Regulation (BYKHY), a building whose permit design was approved before 19 December 2007 counts as an existing building. In a new building, the stair door's fire resistance is set by the storeys the stair serves; in an existing building, by the total building height: at least 60 minutes below 30.50 m, at least 90 minutes above. In a building converted into a hotel, nursery or healthcare facility, the new building provisions apply.
- Counts as existing
- Design approved before 19.12.2007
- What sets fire resistance in a new building
- Storeys served
- What sets fire resistance in an existing building
- Total building height · 30.50 m
- Door size in a new building
- At least 80 × 200 cm
- Door size in an existing building
- At least 70 × 190 cm
01 Which rule
Does the new or the existing building rule apply to your building?
Enter the design approval date, any change of use, and the number of storeys and basements. The section draws the two rules side by side; the one applied turns orange. A storey height of 3.50 m is assumed.
1Design approval
2Use
60minutesexisting building rule · minimum
Existing building: the rating is set by the total building height. Total height ≈ 24.5 m, below 30.50 m: the stair door resists fire for at least 60 minutes and is smoke-tight.
- 70 × 190 cmMinimum door size
- Opens in the escape directionAbove 50 occupants
- Opens without a handleAbove 100 people on a floor
- Lobby exemptionIf it opens onto a corridor with doors
Source: BYKHY 47(1)(2)(3)(5), 138(1)(4), 139(1), 149(1)(b), 157
02 What the door needs
What is checked on doors in an existing building?
First the door fitted to the old stair, then the window next to the external escape stair; tap a tab to fix the view.
1 / 2 · Stair door in an existing buildingThe camera is on the landing of the old stair.
- DoorBelow 30.50 m it resists fire for at least 60 minutes, above for at least 90 minutes; smoke-tight.
- Lever handleAn escape route door opens by hand and is never kept locked.
- SizeThe door cannot be narrower than 70 cm or lower than 190 cm.
Source: BYKHY 157(1), 157(2)
2 / 2 · Window next to the external stairThe camera is on the landing of the external stair.
- WindowAn opening within 1.8 m is converted on every floor to material resisting fire for at least 60 minutes.
- StairPermitted up to a building height above ground of 51.50 m in residential buildings and 30.50 m in other buildings.
- DoorOpens by hand and is never kept locked; in a room with more than 50 people it opens in the escape direction.
Source: BYKHY 153(1), 153(2), 157(2)
03 Existing building
How are doors arranged in an existing building?
Ground floor of an older building: corridor, hall, rooms, internal stair and an external escape stair on the rear facade. Choose a rule and its location on the plan is drawn in orange.
Stair door 60 or 90 minutes, at least 70 × 190 cm
In an existing building the stair door is smoke-tight; it resists fire for at least 60 minutes if the building is lower than 30.50 m, otherwise for at least 90 minutes. The door is at least 70 × 190 cm.
ExampleOn the plan, the door from the corridor to the stair.
Source: BYKHY 157(1)
Door of a hall with more than 50 people opens in the escape direction
The exit door of a room with more than 50 occupants opens in the escape direction; an escape route door opens by hand and is never kept locked.
ExampleOn the plan, both doors of the hall open onto the corridor.
Source: BYKHY 157(2)
Door on a route through a room is self-closing
In a building with no more than 50 people per floor, the stair may be reached through a room: the room door is self-closing and unlocked; at most 9 m from the room door to the stair.
ExampleOn the plan, the route from the corridor through a room to the external stair.
Source: BYKHY 146(3)(b)
No lobby required for a stair opening onto a corridor with doors
If the stair door opens onto a corridor or lobby that contains no flammable substances and is separated from the occupied areas by doors, a safety lobby is not required.
ExampleOn the plan, the corridor separated from the rooms by doors.
Source: BYKHY 149(1)(b)
Window within 1.8 m of the external stair 60 minutes
An unprotected opening within 1.8 m to the sides of the external stair is converted on every floor to material resisting fire for at least 60 minutes, or the stair is placed in a 60-minute enclosure.
ExampleOn the plan, the office window next to the external stair.
Source: BYKHY 153(2)
Ground landing separated from the basement stair by a door
So that people escaping do not go down into the basement, the ground landing is separated from the basement stair by a door or a similar barrier; visible directional signage is also accepted.
ExampleOn the plan, the door between the landing and the flight down to the basement.
Source: BYKHY 156(3)
04 Four locations
Where do fire doors differ between new and existing buildings?
Building changing use, route through a room, basement stair and new building; choose a location and the requirements are marked alongside.
Fire side
Escape side
- In a building changing use If an existing building is converted into a hotel, nursery, healthcare facility or another use listed in 138(1), the existing-building allowances do not apply; doors are chosen under the new building provisions. BYKHY 138(1), 139(1)6090
- On an escape route through a room If the escape stair is reached through a room, the room door is self-closing and kept unlocked. If the room's walls and door resist fire for at least 60 minutes and the door is also smoke-tight, the travel distance ends at the room door. BYKHY 146(3)(b)60
- At the head of the basement stair So that people escaping from upper floors do not head into the basement, the stair's ground landing is separated from the basement stair by a door or a similar physical barrier; visible directional signage is also accepted instead of a barrier. BYKHY 156(3)Door Fire escape stair door page
- In a new building In a new building, the escape stair and safety lobby doors are smoke-tight; if the stair serves fewer than 4 storeys they resist fire for at least 60 minutes, and if it serves a basement or more than 4 storeys, for at least 90 minutes. BYKHY 47(3)6090 Fire escape stair door page
05 Your project
Which fire doors does your building need?
These four answers settle the new-or-existing question and the doors' ratings.
- 01
In which year was your design approved?
A building whose permit design was approved before 19 December 2007 counts as an existing building.
- 02
Is the building's use changing?
In a building converted to a use such as a hotel, nursery or healthcare facility, the new building provisions apply.
- 03
How many metres is the total building height?
In an existing building, the 30.50 m limit including basements decides whether the stair door resists fire for 60 or 90 minutes.
- 04
Were measures taken under the previous regulation?
In an existing building where measures complying with the 2002 regulation have been taken, the principle is that no additional measures are required.
Let's determine your existing building's doors together. Send the design approval year, section and floor plans; our technical team will check which rule applies.
Send the project06 Glazed door
Can a fire door in an existing building be glazed?
The door fitted to the old stair, the line cutting the corridor and the window next to the external stair are made with Aliplast profiles and Polflam glass.
Stair door
Single leaf
Glazed door replacing the floor door of an old stair. Single leaf
Corridor and hall
Double leaf
Wide door cutting the corridor in a building changing use. Double leaf
Next to the external stair
Fire-resistant glass
Fixed glass converting the window opening to 60-minute material. Fire-resistant glass
In an older building the door is measured and made to fit the existing wall opening; the smoke-tightness requirement for the stair door is also addressed in the quotation. Fire escape stair door
Abay Yapı Sistemleri
Trusted for 30 years.
We make stair, corridor and window lines for existing buildings with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul


- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Doors in renovated buildings from our reference projects.
Top: our single-leaf doors at stair entrances; bottom: corridor doors and partitions. Tap to enlarge; browse with the arrows.
07 Document set
Which documents are required for renewed doors in an existing building?
The stair door meets the 60 or 90 minutes derived from the total building height, the window glass meets 60 minutes; the rating and size are documented at handover.
Four checks at handover
- Rating. The door's reported rating must not be shorter than the 60 or 90 minutes derived from the total building height.
- Smoke. The report must also show the door's smoke-tightness class.
- Size. In an existing building the door must be at least 70 cm wide and at least 190 cm high.
- Closing. The stair door must be delivered with a self-closing device.
- ClassificationClassification report for the stair doorWith rating and smoke classRequest it
- ClassificationClassification report for the window glass60 minutes, with glass sizeRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingConnection details to the existing wallDWGRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for the doors to be renewed. Documents are prepared separately for the stair door and the window glass.
Request the document set08 FAQ
About fire doors in new and existing buildings
Whether a building counts as existing, and the doors' ratings, are finalised in the design approval and the fire brigade's opinion. Share the approval year and plans; let's read the applicable rule together.
What does existing building mean, and which buildings count as existing?
Structures, buildings, facilities and premises whose designs submitted with the building permit application were approved by the authority before 19 December 2007 are existing buildings under the regulation. The existing building provisions in Part Ten of the regulation apply to them.
Source: BYKHY 138(4), 138(1)
How many minutes of fire resistance should the stair door have in an existing building?
The criterion is the total building height including basements. In an existing building below 30.50 m the stair door resists fire for at least 60 minutes, and at 30.50 m and above for at least 90 minutes; in both cases it is smoke-tight.
Source: BYKHY 157(1), 4(1)(bbb)
How is the stair door chosen in a new building?
In a new building the criterion is the storeys the stair serves. The door of a stair serving fewer than 4 storeys resists fire for at least 60 minutes, and that of a stair serving a basement or more than 4 storeys for at least 90 minutes; the door is smoke-tight and self-closing.
Source: BYKHY 47(3)
Is it mandatory to replace the fire door in an older building?
In an existing building where measures complying with the 2002 fire regulation have been taken, the principle is that no additional measures are required under the new regulation; the owner may take additional measures if they wish. On matters not made clear in Part Ten, the opinion of the authority issuing the building permit is the basis.
Source: BYKHY 138(2), 144(1)
Which rules apply if the building's use changes?
If an existing building is converted into a healthcare facility, residential healthcare institution, nursery, primary school, dormitory, entertainment venue or accommodation facility, or if hazardous substances are to be kept in it, the other parts of the regulation apply rather than the existing building provisions.
Source: BYKHY 138(1), 139(1)
Is a fire safety lobby mandatory in an existing building?
If the stair door opens onto a corridor or lobby that contains no flammable substances and is separated from the occupied areas by doors, a lobby is not required. In a non-residential building with a total height above 30.50 m, if the stair is entered directly without passing through an area such as a lobby, corridor or hall, and the stair is not pressurised, article 34 applies to the lobby.
Source: BYKHY 149(1)(a), 149(1)(b)
What should the window next to an external escape stair be like?
In an existing building, unprotected windows and openings within 1.8 m to the sides of the external stair are converted on every floor to material resisting fire for 60 minutes. The other option is to place the stair inside a protected enclosure surrounded by 60-minute material.
Source: BYKHY 153(2)
→ Quote
Tell us about your building and its doors.
Design approval year, number of storeys and basements, use: our technical team will determine which rule applies, the door class and the document set, and get back to you.