In a factory, fire doors sit in the walls separating the production hall from the warehouse, paint room, boiler room and administrative area. The compartment area depends on the hazard class: in medium hazard-3 and above, without a fire control system, 6,000 m² for production and 1,000 m² for storage. A hall with more than 50 people has at least two exits, three above 500 people and four above 1,000 people.

Factory fire doors Turkey – double leaf separating production hall from warehouse
Fire door between production and warehouse
Occupant count in production
10 m² per person
Occupant count in a warehouse
30 m² per person
Space with more than 50 / 500 / 1,000 people
2 / 3 / 4 exits
Compartment in medium hazard-3 and above
Production 6,000 · warehouse 1,000 m²
Boiler room door
At least 90 min, smoke-tight

01 Exits

How many exit doors should your factory hall have?

Enter the area and choose the area type and hazard class; the plan draws the exits and compartment lines. The hazard class is set by the fire load of the materials.

2Area type

3Hazard class

3exitsminimum · this hall

8,000 m² production area at 10 m² per person: 800 people. At least 3 exits, as far apart as possible. In medium hazard-3 and above, a production compartment is at most 6,000 m²: at least 2 compartments.

  • Exits far apartAt least half the diagonal
  • Opens in the escape directionAbove 50 occupants
  • Compartment lineWhen the area limit is exceeded
  • No limit if single-storeyIn medium hazard 1 and 2

Source: BYKHY 39(2), 39(3), 47(2), Annex 4, Annex 5/A

––PRODUCTION HALL · diagram
Exit doorCompartment lineBetween exits

02 What the door needs

What is checked on factory doors?

First the door in the wall separating production from the warehouse, then the exit door opening from the hall to the outside; tap a tab to fix the view.

Factory fire doors Turkey – door with side glass in a block wall

1 / 2 · Door between production and warehouseThe warehouse is on fire; the production side is clear.

Warehouse≤ 1,000 m²Production≤ 6,000 m²

  1. DoorThe door in the wall separating the warehouse is fire-rated; it carries the wall's rating.
  2. WallWhere areas cannot be separated, the rule of the highest hazard class applies to the whole building.
  3. DirectionThe door of a crowded area opens in the escape direction.

Source: BYKHY 18(1), 24(7), 47(2), Annex 4

03 Factory plan

How are areas separated in a factory?

Factory floor plan: production hall, warehouse, paint room, administrative area and boiler room. Tap a rule; its location on the plan is drawn in orange.

Warehouse separated from production by a fire wall

If areas of different hazard classes cannot be separated by a suitable partition, the rules of the highest class apply to the whole building. A warehouse compartment is at most 1,000 m² in medium hazard-3 and above, and 5,000 m² in medium hazard-1 and 2.

ExampleOn the plan, the warehouse is separated from the production hall by a fire wall with a double-leaf door in the middle.

Source: BYKHY 18(1), Annex 4

production hallstoragepaintofficesboilerFACTORY FLOOR PLAN · 1/1000K0 – 20 m532641
WallExit doorEscape route

04 Four locations

Where are fire doors used in a factory?

Four situations in industrial buildings; choose a location and the requirements for its door are marked alongside.

05 Your project

Which fire doors does your factory need?

These four answers determine the warehouse, exit and plant area doors.

  1. 01

    How many m² are production and storage?

    Production is counted at 10 m² per person, storage at 30 m²; the number of exits follows from this.

  2. 02

    Which hazard class?

    In medium hazard-3 and above, a compartment is 6,000 m² in production and 1,000 m² in storage.

  3. 03

    Are there flammable liquids or paint?

    An area with flammable liquids is a high-hazard area; the travel distance becomes shorter.

  4. 04

    Where are the boiler room and offices?

    The boiler room is separated from production by a 120-minute partition, the offices by a suitable partition.

Let's count your factory's area and exit doors together. Send your layout plan and area sizes; our technical team will review them.

Send the project

06 Glazed door

Can a factory fire door be glazed?

Warehouse crossing, administrative area and boiler room doors are made with Aliplast profiles and Polflam glass; the 90-minute door uses the FR90 system.

  1. Warehouse crossing

    Double leaf

    Wide glazed door in the wall separating production from the warehouse. Double leaf

  2. Boiler and office

    Single leaf

    Door at the boiler room and administrative area crossing. Single leaf

  3. Office to production

    Fixed glass partition

    Fire-resistant glass of the administrative area overlooking the production hall. Fixed partition

On a boiler room door the article also requires smoke tightness; this is documented together with the door's size. Boiler room door

Abay Yapı Sistemleri

Trusted for 30 years.

We make warehouse, boiler room and administrative area doors for factories with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Factory fire door project Turkey – bronze-framed single leaf at an escape exitFactory fire door project Turkey – single leaf and glass partition in an open-plan officeFactory fire door project Turkey – single leaf with side light at a corridor entranceFactory fire door project Turkey – anthracite single leaf with panic bar
Building exit door · Single leaf
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Area-separating doors from our reference projects.

Top row: our single and double-leaf passage doors; bottom row: doors with side lights and partitions. Tap a photo; browse with the arrows.

07 Document set

Which documents are required for fire doors in a factory?

Warehouse and administrative area doors meet the wall's rating, the boiler room door meets 90 minutes; the rating and direction are documented at handover.

Four checks at handover

  1. Rating. The reported rating must not be shorter than the rating of the wall the door sits in.
  2. Smoke. The boiler room door's report must state its smoke-tightness class.
  3. Direction. Doors of a crowded hall must open in the escape direction and open by hand.
  4. Installation. The joint between the frame and the block wall must be sealed without gaps.
  • ClassificationClassification report for the warehouse doorWith number of leaves and sizeRequest it
  • ClassificationClassification report for the boiler room doorWith rating and smoke classRequest it
  • DeclarationDeclaration of performanceCE markedRequest it
  • DrawingFrame and block wall junction detailsDWGRequest it

Source: Turkish Construction Products Regulation 6(1), 10(2)

Request the document set for factory doors. The set is prepared for each door's area, rating and size.

Request the document set

08 FAQ

About factory fire doors

In a factory, the hazard class, compartment lines and exit locations are finalised with the design and the fire brigade approval. Send your layout plan; let's decide each door's location and class together.

0216 428 38 20Send a question

How many minutes of fire resistance should a factory fire door have?

The door in a wall separating a warehouse or another use carries the wall's rating; a compartment resists fire for at least 60 minutes. The boiler room door resists fire for at least 90 minutes and is smoke-tight; the escape stair door is 60 or 90 minutes.

Source: BYKHY 4(1)(tt), 24(7), 54(5), 47(3)

How many exits should a factory have?

All buildings have at least two exits. Above 50 people in a space at least 2 exits are needed, above 500, 3 exits and above 1,000, 4 exits; in a high-hazard space the threshold is 25 people.

Source: BYKHY 39(1), 39(2)

What is the maximum compartment area in a factory?

In medium hazard-3 and above, 6,000 m² for production and 1,000 m² for storage; in medium hazard-1 and 2, 15,000 m² for production and 5,000 m² for storage. There is no limit if suitable fire control systems are installed, or if a medium hazard-1 or 2 building is single-storey.

Source: BYKHY Annex 4

How is the occupant count calculated in a factory?

Packing areas and factory production areas are counted at 10 m² per person; warehouses, stores and plant rooms at 30 m². For example, a 6,000 m² production hall counts as 600 people.

Source: BYKHY 32(1), Annex 5/A

Why is the paint room kept separate?

Places where flammable substances and liquids are produced or stored count as high-hazard areas. In these areas the travel distance is shorter; the occupant threshold for two exits is 25 instead of 50.

Source: BYKHY 17(1), Annex 5/B, 39(2)

How far apart should two exits be in a factory?

Where two exits are required in a single undivided space, the distance between them cannot be shorter than half the space's diagonal without sprinklers, or a third of it with sprinklers.

Source: BYKHY 39(3)

How many escape stairs should a factory have?

Factories and workshops have at least two independent escape stairs or other exits. A single stair requires all of the following together: a building lower than 21.50 m, fewer than 50 people per floor, a suitable travel distance, non-combustible construction and no use of highly flammable substances.

Source: BYKHY 52(1)