C11Fire criteria · building type
Factory fire door
In a factory, fire doors sit in the walls separating the production hall from the warehouse, paint room, boiler room and administrative area. The compartment area depends on the hazard class: in medium hazard-3 and above, without a fire control system, 6,000 m² for production and 1,000 m² for storage. A hall with more than 50 people has at least two exits, three above 500 people and four above 1,000 people.
- Occupant count in production
- 10 m² per person
- Occupant count in a warehouse
- 30 m² per person
- Space with more than 50 / 500 / 1,000 people
- 2 / 3 / 4 exits
- Compartment in medium hazard-3 and above
- Production 6,000 · warehouse 1,000 m²
- Boiler room door
- At least 90 min, smoke-tight
01 Exits
How many exit doors should your factory hall have?
Enter the area and choose the area type and hazard class; the plan draws the exits and compartment lines. The hazard class is set by the fire load of the materials.
2Area type
3Hazard class
3exitsminimum · this hall
8,000 m² production area at 10 m² per person: 800 people. At least 3 exits, as far apart as possible. In medium hazard-3 and above, a production compartment is at most 6,000 m²: at least 2 compartments.
- Exits far apartAt least half the diagonal
- Opens in the escape directionAbove 50 occupants
- Compartment lineWhen the area limit is exceeded
- No limit if single-storeyIn medium hazard 1 and 2
Source: BYKHY 39(2), 39(3), 47(2), Annex 4, Annex 5/A
02 What the door needs
What is checked on factory doors?
First the door in the wall separating production from the warehouse, then the exit door opening from the hall to the outside; tap a tab to fix the view.
1 / 2 · Door between production and warehouseThe warehouse is on fire; the production side is clear.
- DoorThe door in the wall separating the warehouse is fire-rated; it carries the wall's rating.
- WallWhere areas cannot be separated, the rule of the highest hazard class applies to the whole building.
- DirectionThe door of a crowded area opens in the escape direction.
Source: BYKHY 18(1), 24(7), 47(2), Annex 4
2 / 2 · Exit door from the hall to the outsideThe camera is outside, in the yard; the fire is in the production hall.
- DirectionThe exit door opens outwards, in the escape direction; it opens by hand and is never kept locked.
- NumberAt least 2 exits in a hall with more than 50 people, 3 above 500 and 4 above 1,000.
- DistanceIn a single space with two exits, at least half the diagonal between the exits.
Source: BYKHY 39(2), 39(3), 47(2)
03 Factory plan
How are areas separated in a factory?
Factory floor plan: production hall, warehouse, paint room, administrative area and boiler room. Tap a rule; its location on the plan is drawn in orange.
Warehouse separated from production by a fire wall
If areas of different hazard classes cannot be separated by a suitable partition, the rules of the highest class apply to the whole building. A warehouse compartment is at most 1,000 m² in medium hazard-3 and above, and 5,000 m² in medium hazard-1 and 2.
ExampleOn the plan, the warehouse is separated from the production hall by a fire wall with a double-leaf door in the middle.
Source: BYKHY 18(1), Annex 4
Two, three or four exits in a crowded hall
Every space with more than 50 occupants has at least two exits; three above 500, four above 1,000. In a high-hazard space the threshold for two exits is 25 people. Production areas are counted at 10 m² per person.
ExampleOn the plan, two exits in the production hall, to the west and north.
Source: BYKHY 39(2), Annex 5/A
At least half the diagonal between exits
Where two exits are required in a single undivided space, the distance between them cannot be less than half the space's diagonal in a building without sprinklers, or a third of it in a sprinklered building.
ExampleOn the plan, the line joining the west and north exits.
Source: BYKHY 39(3)
At most 30 m in two directions in production
In industrial buildings the travel distance is 15 m in one direction (25 m with sprinklers) and 30 m in two directions (60 m with sprinklers). In a building that does not produce highly flammable materials, these distances may be increased by half.
ExampleOn the plan, the route from the south-east of the hall to the west exit.
Source: BYKHY Annex 5/B
Paint and solvent room is a high-hazard area
Places where flammable liquids are produced and stored are high-hazard areas. In such an area the travel distance is 10 m in one direction (20 m with sprinklers) and 20 m in two directions (35 m with sprinklers).
ExampleOn the plan, the paint room is in the north-west corner of the hall, with its door opening onto production.
Source: BYKHY 17(1)(c), Annex 5/B
Boiler room 120 min partition, 90 min door
A factory boiler room is separated by 120-minute partitions; its door resists fire for at least 90 minutes, is smoke-tight and self-closing. A boiler room above 350 kW or 100 m² has two exit doors.
ExampleOn the plan, the boiler room is next to the administrative area.
Source: BYKHY 54(2), 54(5)
04 Four locations
Where are fire doors used in a factory?
Four situations in industrial buildings; choose a location and the requirements for its door are marked alongside.
Fire side
Escape side
- Between production and warehouse The warehouse is separated from the production hall by a fire-rated wall, and the door in the wall carries the wall's rating. A warehouse compartment in medium hazard-3 or above cannot exceed 1,000 m². BYKHY 18(1), 24(7), Annex 460 Fire compartment page
- In the paint and solvent room A room where flammable liquids are used and stored is a high-hazard area. The travel distance from the room to an exit cannot exceed 10 m in one direction; a room with more than 25 people has two exits. BYKHY 17(1)(c), Annex 5/B, 39(2)High hazard
- Between the administrative area and production Offices and production are different uses. If the two areas cannot be separated by a partition suited to the higher hazard class, the high-hazard rules apply to the whole building. BYKHY 18(1)60 Fire compartment page
- In the factory boiler room The boiler room is separated from other parts by partitions resisting fire for 120 minutes. Its exit door resists fire for at least 90 minutes and is smoke-tight. BYKHY 54(2), 54(5)90 Boiler room door page
05 Your project
Which fire doors does your factory need?
These four answers determine the warehouse, exit and plant area doors.
- 01
How many m² are production and storage?
Production is counted at 10 m² per person, storage at 30 m²; the number of exits follows from this.
- 02
Which hazard class?
In medium hazard-3 and above, a compartment is 6,000 m² in production and 1,000 m² in storage.
- 03
Are there flammable liquids or paint?
An area with flammable liquids is a high-hazard area; the travel distance becomes shorter.
- 04
Where are the boiler room and offices?
The boiler room is separated from production by a 120-minute partition, the offices by a suitable partition.
Let's count your factory's area and exit doors together. Send your layout plan and area sizes; our technical team will review them.
Send the project06 Glazed door
Can a factory fire door be glazed?
Warehouse crossing, administrative area and boiler room doors are made with Aliplast profiles and Polflam glass; the 90-minute door uses the FR90 system.
Warehouse crossing
Double leaf
Wide glazed door in the wall separating production from the warehouse. Double leaf
Boiler and office
Single leaf
Door at the boiler room and administrative area crossing. Single leaf
Office to production
Fixed glass partition
Fire-resistant glass of the administrative area overlooking the production hall. Fixed partition
On a boiler room door the article also requires smoke tightness; this is documented together with the door's size. Boiler room door
Abay Yapı Sistemleri
Trusted for 30 years.
We make warehouse, boiler room and administrative area doors for factories with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Area-separating doors from our reference projects.
Top row: our single and double-leaf passage doors; bottom row: doors with side lights and partitions. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for fire doors in a factory?
Warehouse and administrative area doors meet the wall's rating, the boiler room door meets 90 minutes; the rating and direction are documented at handover.
Four checks at handover
- Rating. The reported rating must not be shorter than the rating of the wall the door sits in.
- Smoke. The boiler room door's report must state its smoke-tightness class.
- Direction. Doors of a crowded hall must open in the escape direction and open by hand.
- Installation. The joint between the frame and the block wall must be sealed without gaps.
- ClassificationClassification report for the warehouse doorWith number of leaves and sizeRequest it
- ClassificationClassification report for the boiler room doorWith rating and smoke classRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingFrame and block wall junction detailsDWGRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for factory doors. The set is prepared for each door's area, rating and size.
Request the document set08 FAQ
About factory fire doors
In a factory, the hazard class, compartment lines and exit locations are finalised with the design and the fire brigade approval. Send your layout plan; let's decide each door's location and class together.
How many minutes of fire resistance should a factory fire door have?
The door in a wall separating a warehouse or another use carries the wall's rating; a compartment resists fire for at least 60 minutes. The boiler room door resists fire for at least 90 minutes and is smoke-tight; the escape stair door is 60 or 90 minutes.
Source: BYKHY 4(1)(tt), 24(7), 54(5), 47(3)
How many exits should a factory have?
All buildings have at least two exits. Above 50 people in a space at least 2 exits are needed, above 500, 3 exits and above 1,000, 4 exits; in a high-hazard space the threshold is 25 people.
Source: BYKHY 39(1), 39(2)
What is the maximum compartment area in a factory?
In medium hazard-3 and above, 6,000 m² for production and 1,000 m² for storage; in medium hazard-1 and 2, 15,000 m² for production and 5,000 m² for storage. There is no limit if suitable fire control systems are installed, or if a medium hazard-1 or 2 building is single-storey.
Source: BYKHY Annex 4
How is the occupant count calculated in a factory?
Packing areas and factory production areas are counted at 10 m² per person; warehouses, stores and plant rooms at 30 m². For example, a 6,000 m² production hall counts as 600 people.
Source: BYKHY 32(1), Annex 5/A
Why is the paint room kept separate?
Places where flammable substances and liquids are produced or stored count as high-hazard areas. In these areas the travel distance is shorter; the occupant threshold for two exits is 25 instead of 50.
Source: BYKHY 17(1), Annex 5/B, 39(2)
How far apart should two exits be in a factory?
Where two exits are required in a single undivided space, the distance between them cannot be shorter than half the space's diagonal without sprinklers, or a third of it with sprinklers.
Source: BYKHY 39(3)
How many escape stairs should a factory have?
Factories and workshops have at least two independent escape stairs or other exits. A single stair requires all of the following together: a building lower than 21.50 m, fewer than 50 people per floor, a suitable travel distance, non-combustible construction and no use of highly flammable substances.