C13Fire criteria · building type

Fire doors in high-rise buildings

The Turkish Fire Regulation (BYKHY) defines a high-rise building as one whose building height above ground exceeds 21.50 m and whose total building height exceeds 30.50 m. In such a building, escape routes and stairs are at least 120 cm wide; the safety lobby door resists fire for at least 90 minutes and is smoke-tight. When the building exceeds 51.50 m, a firefighting lift with a lobby in front of it is required.

High-rise building fire doors Turkey – firefighting lift lobby
Safety lobby door on a tower floor
High-rise building definition
Building 21.50 m · total 30.50 m
Escape route and stair width
At least 120 cm
Safety lobby door, fire resistance
At least 90 minutes
Shaft hatch, fire resistance
At least 90 minutes
Firefighting lift
When the building exceeds 51.50 m

01 Height

Is your building a high-rise building?

Enter the number of storeys, basements and storey height. The section draws the two measurements separately: building height above ground from ground level to eaves, and total building height including basements.

3Storey height

4Use

Yeshigh-rise buildingboth heights above the limit

Building height ≈ 35 m, total height ≈ 42 m. Both measurements exceed the limit: high-rise building. The stair door is smoke-tight and resists fire for at least 90 minutes.

  • 120 cm widthEscape route and stair
  • Shaft hatch 90 minSmoke-tight
  • Open external stairNot permitted
  • One compartment per 3 storeysStoreys above the threshold
  • Firefighting lift and lobbyWhen the building exceeds 51.50 m

Source: BYKHY 4(1), 24(4), 25(3), 33(2), 42(3), 47(3), 48(5), 63(2)

10 storeys · 2 basements
3-storey compartmentHeight exceeding the limit

02 What the door needs

What is checked on doors in a high-rise building?

First the door of the lobby in front of the firefighting lift, then the escape stair door; tap a tab to fix the view.

High-rise building fire doors Turkey – lift lobby on a tower floor

1 / 2 · Firefighting lift lobbyThe camera is in the corner of the lobby; the fire starts at the end of the floor corridor.

Door≥ 90 minWall≥ 120 min

  1. DoorThe lobby door resists fire for at least 90 minutes, is smoke-tight and self-closing.
  2. Glazed wallThe wall separating the lobby from other areas resists fire for at least 120 minutes.
  3. LiftThe firefighting lift opens into this lobby; the lobby also gives access to the escape stair.

Source: BYKHY 34(2), 34(7), 47(3), 63(3)

03 Tower floor

Where do doors go in a tower core?

Core plan of a tower floor: two escape stairs, the firefighting lift and its lobby, a services shaft and a lift lobby. Choose a rule; its location in the core is marked in orange.

Escape route and stair at least 120 cm

In high-rise buildings, escape routes and stairs cannot be narrower than 120 cm. Widths are measured as clear widths.

ExampleOn the plan, the flights of the two stairs.

Source: BYKHY 33(2), 33(5)

stairstairlobbyshaftlift lobbyfirefighting lift ↑TOWER FLOOR CORE PLANK0 – 5 m≥ 1.20145236
120-minute wallEscape stairEscape route

04 Three locations

Where are fire doors used in a high-rise building?

Tower floor, residential tower and existing building; choose a location and the requirements for its door are marked alongside.

High-rise building fire doors Turkey – tower office floor compartment High-rise building fire doors Turkey – residential tower corridor High-rise building fire doors Turkey – stair in an older office building Fire side Escape side
60Compartment line and its door at least 60 minutesBYKHY 4(1)(tt), 24(7)
3At most three storeys per compartment above the thresholdBYKHY 24(4)
2Two protected escape stairs in a residential building above 30.50 mBYKHY 48(5)
90Safety lobby door at least 90 minutes, smoke-tightBYKHY 34(2)
60·90In an existing building, stair door 60 or 90 minutes, limit 30.50 mBYKHY 157(1)
Compartment line on a tower floorRequired here
  1. Compartment line on a tower floor The glazed line cutting across the tower floor and its double-leaf door form a compartment boundary: they resist fire for at least 60 minutes, and the resistance continues at the junctions. In a non-residential building whose height above ground exceeds 21.50 m, a compartment on the storeys above that height is at most three storeys. BYKHY 24(4), 24(7), 4(1)(tt)60 Fire compartment page
  2. In a residential tower A residential building with a total height above 30.50 m has two alternative escape stairs, both protected; at least one has a safety lobby or pressurisation; above 51.50 m both stairs have lobbies and are pressurised. The lobby door resists fire for at least 90 minutes and is smoke-tight. BYKHY 48(5)(c), 48(5)(ç), 34(2)90
  3. In an existing high-rise building In an existing building, the total building height determines the stair door's rating. In a building 30.50 m or taller, the escape stair door resists fire for at least 90 minutes and is smoke-tight; in a lower building, at least 60 minutes. BYKHY 157(1)6090 New and existing buildings page

05 Your project

Which fire doors does your high-rise building need?

These four answers determine the lobby, stair and compartment doors.

  1. 01

    How many metres are the building height and total height?

    The two measurements in the definition: building height above ground, from ground level to eaves, 21.50 m; total building height including basements, 30.50 m.

  2. 02

    Does the building exceed 51.50 m?

    If it does, there is at least one firefighting lift with a 6–10 m² safety lobby in front of it on every floor.

  3. 03

    Is the building residential or another use?

    The three-storey compartment threshold is a building height of 21.50 m for non-residential and 30.50 m for residential buildings.

  4. 04

    Is it an existing building?

    In an existing building, the 30.50 m total building height decides whether the stair door resists fire for 60 or 90 minutes.

Let's count your tower's core doors together. Send your section and floor plans; our technical team will list the lobby and stair doors.

Send the project

06 Glazed door

Can a fire door in a high-rise building be glazed?

Lobby, stair and floor compartment doors are made with Aliplast profiles and Polflam glass.

  1. Lobby and stair

    Single leaf

    Floor door of the safety lobby and escape stair. Single leaf

  2. Floor compartment

    Double leaf

    Wide door dividing a tower floor into two compartments. Double leaf

  3. Glazed lobby wall

    120-minute glass partition

    Glazed wall resisting fire for 120 minutes, separating the lobby from the floor. Frameless glass partition

For lobby and stair doors the regulation requires smoke tightness as well as fire resistance; in the quotation both requirements are addressed together with the door's size. Fire safety lobby

Abay Yapı Sistemleri

Trusted for 30 years.

We make lobby, stair and floor doors for high-rise buildings with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
High-rise building fire door project Turkey – double leaf with panic bars, side and top lightsHigh-rise building fire door project Turkey – double leaf held open in a lift lobby
Lobby passage door · Double leaf · side and top lights
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Lobby and stair doors from our reference projects.

Top row: our doors at stair and lobby entrances; bottom row: doors and partitions at floor crossings. Tap a photo; browse with the arrows.

07 Document set

Which documents are required for fire doors in a high-rise building?

Lobby and stair doors meet at least 90 minutes, the compartment door meets the line's rating; the rating and closing arrangement are documented at handover.

Four checks at handover

  1. Rating. The reported rating of the lobby and stair doors must not be shorter than 90 minutes.
  2. Smoke. The lobby and stair door reports must state the smoke-tightness class.
  3. Closing. Doors must be delivered with a self-closing device.
  4. Panic. If there are more than 100 people on a floor, the lobby and stair doors must open in the escape direction without using a handle.
  • ClassificationClassification report for the lobby doorWith rating and smoke classRequest it
  • ClassificationClassification report for the stair doorWith leaf sizeRequest it
  • DeclarationDeclaration of performanceCE markedRequest it
  • DrawingLobby, door and glazed wall junction detailsDWGRequest it

Source: Turkish Construction Products Regulation 6(1), 10(2)

Request the tower's door documents. Documents are prepared separately for lobby, stair and compartment doors.

Request the document set

08 FAQ

About fire doors in high-rise buildings

In a high-rise building, the ratings of lobby, stair and shaft doors are finalised in the section and the fire brigade approval. Share your section and floor plans; let's list the lobby, stair and shaft doors with their classes.

0216 428 38 20Send a question

What is a high-rise building, and from what height does a building count as one?

The definition in the regulation: buildings whose building height above ground exceeds 21.50 m and whose total building height exceeds 30.50 m. Building height above ground is measured from the building's ground level reference point to the eaves level; total building height also includes basements, mezzanines and attic rooms.

Source: BYKHY 4(1)(ccc), 4(1)(h), 4(1)(bbb)

How many minutes of fire resistance should a fire door in a high-rise building have?

The safety lobby door resists fire for at least 90 minutes and is smoke-tight. Smoke tightness is also required on the stair door; on a stair serving a basement or more than four storeys, the door's rating is at least 90 minutes.

Source: BYKHY 34(2), 47(3)

How wide should an escape stair be in a high-rise building?

In high-rise buildings, escape routes and stairs cannot be narrower than 120 cm. The width is measured clear; at a door, this is the distance between the frame and the leaf opened to 90 degrees.

Source: BYKHY 33(2), 33(5)

Is a firefighting lift mandatory in a high-rise building?

If the total building height exceeds 51.50 m, at least one lift is a firefighting lift. In front of it on every floor there is a fire safety lobby that also leads to the escape stair; the lobby is no smaller than 6 m² and no larger than 10 m², and no dimension falls below 2 m.

Source: BYKHY 63(2), 63(3)

What should a services shaft hatch be like in a high-rise building?

The shaft hatch must resist fire for at least 90 minutes and be smoke-tight. The shaft and flue walls require at least 120 minutes; the rule applies to all refuse, communications, document and technical equipment shafts.

Source: BYKHY 25(3)

How many storeys can one compartment span in a high-rise building?

When the building height above ground exceeds 21.50 m in a non-residential building, or 30.50 m in a residential building, the storeys above that height are arranged with at most three storeys per fire compartment.

Source: BYKHY 24(4)

How many minutes of fire resistance should the stair door have in an existing high-rise building?

In existing buildings the limit is the total building height: in a building lower than 30.50 m the escape stair door resists fire for at least 60 minutes, in a building 30.50 m or taller for at least 90 minutes. In both cases the door is smoke-tight.

Source: BYKHY 157(1)