01Door type · one of 4 types
Single-leaf glazed fire door
A single-leaf glazed fire door is used for openings between 80 and 120 cm: the regulation requires an escape door's opening (clear opening width) to be at least 80 cm, and no more than 120 cm on a single-leaf door. In the fire test, Aliplast FR90 let no flame or smoke through for 103 minutes; we make these doors with Polflam glass up to 1.65 × 2.87 m.
Panic barOpens without a handle · BYKHY 47(5)
Aluminium frame and leafThe frame around the glass
DaylightFrom the office windows into the corridor
- Maximum size
- 1.65 m wide × 2.87 m high
- Fire test
- No flame or smoke through for 103 min · ITB 2020
- Profile
- Aliplast FR65 · FR90
- Glass
- Polflam fire-resistant glass, 20–35 mm
- When
- Opening 80–120 cm · floors with up to 500 people
01 When single leaf
What opening width is a single leaf enough for?
The regulation sets two limits on the opening a single-leaf door provides: a minimum of 80 and a maximum of 120 cm (47(1), 47(4)). The number of people on the floor decides which width is enough; tap a condition or drag the line.
Which opening a single leaf can serve · number of people on the floor and high-rise building
The regulation counts the door as part of the escape route and measures its width with the door fully open (33(5)). For an opening wider than 120 cm, see the double-leaf glazed fire door.
Single leaf is enough
A single-leaf door can provide this opening.
BYKHY 47(4)02 Components
What parts make up a single-leaf door?
The laboratory tests the door as a whole, not part by part: the frame, glass, hinges and lock go through the same test in the same furnace. Tap one of the numbers.
- Frame and leafThe aluminium frame is fixed to the wall and the single leaf swings within it. Profile depth is 65 mm on FR65 and 90 mm on FR90. The leaf fire-tested was 1,340 × 2,535 mm.
- Fire-resistant glassThe test door had 35 mm Polflam 90 glass. Depending on the duration the project requires, 20 mm (30 min), 25 mm (60 min) or 32 mm (90 min) glass is fitted; the glass transmits 85–87% of light.
- HingeIt connects the leaf to the frame and sets the direction the door opens; where more than 50 people use the space, that direction is towards the escape side. WALA hinges were used in the test.BYKHY 47(2)
- Lever handle and lockThe lock must not hold the door shut during escape; the door must open by hand at any time. Where more than 100 people are on a floor, a panic bar replaces the lever handle. A SOBINCO lock was used in the test.BYKHY 47(2), 47(5)
- Door closerThe arm and body above the leaf close it again, whoever lets the door go. The regulation requires this on stair and lobby doors. A GEZE TS 5000 was used in the test.BYKHY 47(3)
On a single leaf, the choice of lever handle or panic bar, lock, door closer and colour is made from the hardware covered by the fire report.
03 Sizes
What sizes can a single-leaf fire door be made in?
In the scale drawing, a 1.75 m person stands next to the largest overall size of a single leaf. You can switch between the two profile systems and the door fire-tested in the laboratory.
The outside dimension of the frame (overall size), the frame's inner opening (net opening) and the clear opening width are three separate values. The sizes a report covers follow from the size of the door fire-tested in the laboratory. Fire door sizes
Abay Yapı Sistemleri
Trusted for 30 years.
We make single-leaf glazed fire doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Single-leaf and other installations from our reference projects.
Single-leaf doors are at the top; glass partitions and other door types are below. Tap a photo to open it.
04 Test results
How long did the door last in the fire test?
The Aliplast FR90 single-leaf door was placed in the furnace and fire-tested at ITB, the authorised laboratory in Poland. Two doors were tested: one opening towards the furnace, one opening away from it. Tap a bar.
- Integrity · 103 minutes
- Neither door let flames or hot gases through during the test; the test ended at the 103rd minute with no failure.
- Thermal insulation (EI2 method) · 92 minutes
- The temperature rise on the escape-side surface stayed below the limit for 92 minutes. This is the result of the weaker of the two doors; the other door completed 103 minutes.
- Thermal insulation (EI1 method) · 71 minutes
- Insulation was also measured by a second method (EI1): 71 minutes for the weaker door, 85 for the other. The report gives the results of both methods together.
Test door: 1,450 × 2,600 mm, 35 mm Polflam 90 glass, WALA hinges, SOBINCO lock, GEZE TS 5000 door closer.
Required fire resistance by location
"Lobby": the fire safety lobby in front of an escape stair. Where the table says "smoke-tight", the door's documents show this property separately with the letter S. Source: official text of the BYKHY.
05 Where it is used
Where are single-leaf glazed fire doors used?
Four locations, four scenes. See which side the single-leaf door holds the fire on, and what the regulation requires of the door in each location.
Fire side
Escape side
- Office escape corridor Exit doors opening onto an internal escape corridor have the same fire resistance as escape stair doors and are self-closing. A glazed door carries the office's daylight into the corridor. BYKHY 36(1)(b)Same as the stair Emergency exit door page
- Stair door in a small building In a new building, the door of an escape stair serving fewer than 4 storeys is rated for at least 60 minutes, smoke-tight and self-closing. BYKHY 47(3)60 Fire escape stair door page
- Exit to an external escape route An exit door opening from the building onto an external escape route is rated for at least 30 minutes and self-closing. BYKHY 37(2)30 Emergency exit door page
- Fire safety lobby The fire safety lobby in front of an escape stair is separated by a smoke-tight door rated for at least 90 minutes; the lobby floor area is 3–6 m². BYKHY 34(2), 34(3)90 Fire safety lobby page
06 Document set
Which documents should you ask for with a single-leaf door?
The test results above are from the FR90 single leaf's test report. The door is delivered with a metal identification plate fixed to its frame, together with these documents.
Metal plateClass · system · serial no · glass
- Test reportFR90 single leaf · ITB 2020No flame or smoke through for 103 min · Polflam 90 glassRequest
- AuthorisationAliplast manufacturing authorisationAbay's authorisation to manufacture this systemRequest
- Glass documentPolflam fire-resistant glassDeclaration of performance (DoP) · covers the glass only, not a substitute for the door's reportRequest
- DrawingFR65 / FR90 single-leaf sectionsArchitectural drawing file (DWG)Request
Request the document set for your project. Documents are shared together with company and project details.
Request the document set07 FAQ
About single-leaf fire doors
If your question is not here, ask our technical team.
What is the maximum width of a single-leaf fire door?
On a single-leaf exit door the clear opening width is at least 80 and at most 120 cm. The door's overall size is larger than this; with Aliplast FR90 the largest single-leaf door is 1,650 × 2,870 mm.
Source: BYKHY 47(4)
How long does a single-leaf glazed fire door resist fire?
In the fire test, Aliplast FR90 let no flame or smoke through for 103 minutes; insulation lasted 92 minutes. The regulation sets the duration by the door's location: the stair door of a new building with fewer than 4 storeys must be rated for at least 60 minutes, and the door of a stair serving a basement or more than 4 storeys for at least 90 minutes.
Source: BYKHY 47(3)
Should I choose a single-leaf or double-leaf door?
Look at the opening you need. With 50–500 people on a floor, the escape route is at least 100 cm and a single leaf is enough. With 501–2000 people, at least 150 cm is required; that width can only be achieved with two leaves.
Source: BYKHY 33(1), 47(4)
Does a single-leaf fire door need a panic bar?
It depends on the door's location and the number of people on the floor. It is always required on escape doors opening from the building to a safe area at ground level. Where more than 100 people are on a floor, the stair, corridor and lobby doors on that floor must also open by pushing, without turning a lever handle.
Source: BYKHY 47(5)
Which way should a fire door open?
Where more than 50 people are in a space, the exit door must open in the direction of escape. An escape door must always open by hand; it cannot be kept locked.
Source: BYKHY 47(2)
What determines the price of a single-leaf fire door?
Size and fire resistance duration affect the price of a single leaf most: the longer the duration, the thicker the glass (20, 25, 32 mm). Add to these the profile system (FR65 or FR90), lever handle or panic bar, door closer, quantity and installation. Send us the door's location and size and we will come back with a quote within the scope of the documents.