GGuide · sizes

Fire door sizes

Under the Turkish Fire Regulation (BYKHY), an escape route door in a new building has a clear opening width of at least 80 cm and a height of at least 200 cm; the clear width of a single-leaf exit door cannot exceed 120 cm. In an existing building, an escape route door is at least 70 cm wide and 190 cm high. The largest size that can be made is set by the profile system.

Fire door sizes Turkey – single vs double leaf width
Single leaf and double leaf side by side
Minimum in a new building
80 × 200 cm
Minimum in an existing building
70 × 190 cm
Single leaf maximum
120 cm clear width
Dimension type
Clear width

01 Regulation

Which sizes does the regulation require for a fire door?

New and existing buildings differ: for a new building the regulation states clear width, for an existing building it states width.

SizesNew buildingExisting building
Door widthClear width at least 80 cmWidth at least 70 cm
Door heightAt least 200 cmAt least 190 cm
BasisBYKHY 47(1), 47(4)BYKHY 157(1)

In a new building, the clear width of a single-leaf exit door is between 80 cm and 120 cm; an escape route door has no threshold (BYKHY 47(1), 47(4)).

02 How it is measured

How is clear width measured?

It is measured between the open leaves, not from the door's overall size.

  1. 01

    On a single leaf

    The dimension between the door frame or rebate stop and the face of the leaf opened to 90 degrees.

  2. 02

    On a double leaf

    The dimension between the leaf faces with both leaves open to 90 degrees.

  3. 03

    Not the door's overall size

    Frame and leaf thickness are deducted; overall size, glass size and clear opening are all different.

  4. 04

    By number of occupants

    With 50–500 people on a floor, an escape route is at least 100 cm; with 501–2,000 people, at least 150 cm; in a high-rise building, at least 120 cm.

Source: BYKHY 47(4), 33(1), 33(2), 33(5)

03 Maximum size

What is the largest size a glazed fire door is made in?

The profile system sets the limit; the door's report sets the size valid for each rating.

  1. Single leaf

    FR90 single leaf

    An Aliplast FR90 single-leaf door is made up to 1,650 × 2,870 mm, FR65 up to 1,400 × 2,500 mm. Single leaf

  2. Double leaf

    FR90 double leaf

    An Aliplast FR90 double-leaf door is made up to 3,170 × 2,870 mm, FR65 up to 2,690 × 2,500 mm. Double leaf

  3. Table

    All size limits

    Frame depth, glass thickness, rating and partition sizes in one table. Technical file

04 FAQ

About fire door sizes

The door size depends on the number of people on the floor and the door's location. Send us the plan and we will determine the opening size and leaf layout together.

0216 428 38 20Send a question

What is the minimum size of a fire door in cm?

In a new building, an escape route door has a clear width of at least 80 cm and a height of at least 200 cm. In an existing building, an escape route door is at least 70 cm wide and at least 190 cm high.

Source: BYKHY 47(1), 157(1)

What is the maximum width of a single-leaf fire door in cm?

The clear width of a single-leaf exit door cannot be less than 80 cm or more than 120 cm. If a wider opening is needed, a double leaf is used.

Source: BYKHY 47(4)

How is clear width measured?

On a single leaf it is measured between the frame or rebate stop and the face of the leaf opened to 90 degrees; on a double leaf, between the leaf faces with both leaves open to 90 degrees.

Source: BYKHY 47(4), 33(5)

Can a fire door have a threshold?

Escape route doors must have no threshold; revolving doors and turnstiles also cannot be used as exit doors.

Source: BYKHY 47(1)

→ Quote

Send us your door sizes.

Width, height, leaves and rating: we will identify the right system and get back to you.

Call · 0216 428 38 20Email