C5Fire criteria · location
Boiler room door
A boiler room door is rated for at least 90 minutes, is smoke-tight and self-closing. It opens not directly onto an escape stair but onto a common lobby or corridor. A boiler room with a heat output of 50–350 kW has at least one exit door; one over 100 m² or 350 kW has at least two, positioned opposite each other.
- Fire resistance of the door
- At least 90 min, smoke-tight
- Wall fire resistance
- At least 120 minutes
- Door closing
- Self-closing
- Where the door opens
- Common lobby or corridor
- Number of exit doors
- Over 100 m² or 350 kW: 2
01 How many doors
How many exit doors should a boiler room have?
The number of doors is set by the boilers' total heat output (kW) and the boiler room's floor area. Enter both values; the plan changes with the number of doors.
1exit door is enoughminimum · this boiler room
250 kW and 80 m²: a boiler room between 50 and 350 kW and not exceeding 100 m² has at least one exit door.
Every door is rated for at least 90 minutes, smoke-tight and self-closing.
- ExtinguisherIn every boiler room, 6 kg
- Fire hose cabinetMandatory above 350 kW
- Mechanical smoke extractionMandatory above 2,000 m²
Source: BYKHY 54(5), 54(8), 94(1)(b)(1), 88(3)
02 What the door needs
What should you check in a boiler room door?
First the boiler room door from the corridor, then the second exit of a large boiler room; tapping a tab locks the view.
1 / 2 · From the corridorThere is a fire in the boiler room; the door is closed and the corridor is clear.
- DoorRated for at least 90 minutes and smoke-tight.
- Door closerThe door is self-closing; it is not left open.
- Meter and valveGas meter, main valve and switchboard outside the boiler room, in the corridor.
Source: BYKHY 54(5), 55(2), 55(3)
2 / 2 · Second exitThe door at the far end of a large boiler room opens onto the common lobby.
- Second doorIn a boiler room over 100 m² or 350 kW, a second exit, opposite the first.
- WallThe partitions enclosing the boiler room are rated for at least 120 minutes.
- Common lobbyThe door opens onto a common lobby or corridor, not onto the stair.
Source: BYKHY 54(2), 54(4), 54(5)
03 Where it opens
Where does a boiler room door open?
Basement floor plan: a 146 m² boiler room, common corridor, escape stair and fuel store. When you tap a rule, its location is drawn in orange on the plan.
The door opens onto a common lobby or corridor, not onto the stair
A boiler room door does not open directly onto an escape stair or a general-use stair; it must always open onto a common lobby or corridor. The stair is reached through this lobby or corridor.
ExampleOn the plan both doors open onto the common corridor and common lobby; the stair door is in the corridor.
Source: BYKHY 54(4)
The walls are rated for at least 120 minutes
The boiler room is separated from the rest of the building by partitions rated for at least 120 minutes and is located centrally, in one piece. Its walls and floor slabs have the quality of compartment walls; no building movement joint passes through the boiler room.
ExampleOn the plan the boiler room is enclosed by hatched 120-minute walls; the movement joint runs beside the fuel store to the west.
Source: BYKHY 54(2), 24(2)
Two doors in a large boiler room, opposite each other
A boiler room over 100 m² or 350 kW has at least two exit doors, placed as far as possible opposite each other. Every door is rated for at least 90 minutes, is smoke-tight and self-closing.
ExampleOn the plan the 146 m² boiler room has one door to the north and one to the east.
Source: BYKHY 54(5)
The fuel store is separated by a 120-minute partition
The fuel store is a separate space protected by fire-rated partitions and is separated from the boiler room by a partition rated for 120 minutes. The store has ventilation and a bund holding at least one third of the tank capacity.
ExampleOn the plan the liquid fuel store is west of the boiler room; the wall between them is rated for 120 minutes.
Source: BYKHY 56(1)
Meter, main valve and switchboard outside the boiler room
In a boiler room using natural gas or LPG, the meters are placed outside. The main gas shut-off valve, main circuit breaker and main electrical switchboard are outside the boiler room, in an easily accessible place. A boiler room using LPG is not built in a basement.
ExampleOn the plan the meter, valve and switchboard are beside the door, in the common corridor.
Source: BYKHY 55(2), 55(3), 55(10)
Fresh air and exhaust air ducts in addition to the flue
In a boiler room, fresh air and exhaust air ducts are built in addition to the flue. A separate flue is preferably used for each boiler.
ExampleOn the plan D is the flue, T the fresh air duct, K the exhaust air duct.
Source: BYKHY 54(3), 58(1), 58(2)
04 Four locations
Where is a boiler room most often located in a building?
Wherever the boiler room is, its door meets the same requirements. Choose a location; the door's requirements are marked alongside.
Fire side
Corridor
- In a residential basement An apartment block's central heating boiler is usually in the basement. The boiler room door opens onto the common corridor in the basement; the stair is reached through this corridor. BYKHY 54(2), 54(4), 54(5)90
- On the plant floor of an office building In office buildings the boiler room is often among the plant rooms in the basement. Its walls have the quality of compartment walls; its door opens onto the plant corridor. BYKHY 24(2), 54(2), 54(5)90 Office building page
- Heating plant on the roof floor A natural gas heating plant can also be installed on the roof floor; a boiler room using LPG is not built in a basement. The door of a rooftop boiler room also opens onto the common lobby or corridor on the roof floor. BYKHY 54(4), 55(10)90
- Large heating plant in a hospital or hotel A boiler room over 100 m² or 350 kW has at least two exit doors, positioned opposite each other. Above 350 kW a fire hose cabinet is also mandatory. BYKHY 54(5), 94(1)(b)(1)90 Hospital page
05 Your project
Which door does your boiler room need?
These four answers set the number, location and type of doors.
- 01
What is the boilers' total heat output in kW?
The 350 kW threshold changes the number of doors and the fire hose cabinet requirement.
- 02
How many m² is the boiler room?
A boiler room over 100 m² has at least two exit doors.
- 03
Which fuel is used?
With natural gas and LPG the meter, valve and switchboard are outside; with liquid fuel the store is separated by a 120-minute partition.
- 04
Where does the door open?
The door opens onto a common lobby or corridor, not onto the stair; door locations are read from the plan.
Let us specify your boiler room doors together. Send the basement plan, boiler output and fuel type; our technical team will review them.
Send the project06 Glazed door
Can a boiler room door be glazed?
The door and, where needed, a glazed partition are made with Aliplast profiles and Polflam glass to the rating the boiler room requires.
Boiler room door
Up to EI90
Aliplast FR90 single-leaf glazed door for the boiler room's 90-minute exit door. Single leaf
Large heating plant
Double leaf
FR90 double-leaf glazed door for wide boiler room entrances. Double leaf
Boiler room wall
EI120 glass
If glass is needed in the boiler room wall, a 120-minute partition with Polflam BR glass. Frameless glass partition
Smoke-tightness is a requirement of the article for this door; the document set is also checked against the door type and size. Aliplast FR90
Abay Yapı Sistemleri
Trusted for 30 years.
We make boiler room doors with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Single and double-leaf fire doors from our reference projects.
Top row: our single-leaf glazed fire doors; bottom row: double-leaf and wide passage doors. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a boiler room door?
The door must meet the 90-minute, smoke-tightness and self-closing requirements; each is shown with certification.
Four checks at handover
- Rating. The classification report must state a fire resistance of at least 90 minutes for the door.
- Smoke. The same report must also include a smoke-tightness class.
- Self-closing. The door closer must be the same as the hardware the door was tested with.
- Declaration and CE. A declaration of performance and CE marking for the door.
- ClassificationDoor classification reportWith type and sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- HardwareDoor closer and lock listHardware as testedRequest
- DrawingDoor and wall junction detailsDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for the boiler room door. Documents are sent together with the door type and size.
Request the document set08 FAQ
About boiler room doors
The number and location of boiler room doors are set by the project architect, the mechanical engineer and fire brigade approval. The rules are on this page; let us look together at how they apply to your boiler room.
How many minutes must a boiler room door resist fire?
Boiler room exit doors are rated for at least 90 minutes, are smoke-tight and self-closing. The boiler room walls are rated for at least 120 minutes.
Source: BYKHY 54(5), 54(2)
How many doors should a boiler room have?
A boiler room with a heat output of 50–350 kW has at least one door. A boiler room with a floor area over 100 m² or a heat output over 350 kW has at least two exit doors, positioned as far as possible opposite each other.
Source: BYKHY 54(5)
Where should a boiler room door open?
A boiler room door does not open directly onto an escape stair or a general-use stair; it must always open onto a common lobby or corridor.
Source: BYKHY 54(4)
What should the boiler room walls be like?
The boiler room is separated from the rest of the building by partitions rated for at least 120 minutes and is located centrally, in one piece. Its walls and floor slabs have the quality of compartment walls; no building movement joint passes through the boiler room.
Source: BYKHY 54(2), 24(2)
Is a fire hose cabinet required in a boiler room?
A fire hose cabinet is mandatory in a boiler room with a heat output over 350 kW; in existing buildings this threshold is 500 kW. Every boiler room has at least one 6 kg multi-purpose dry chemical powder extinguisher.
Source: BYKHY 94(1)(b)(1), 164(2), 54(8)
Where are the meter and valve in a natural gas boiler room?
The meters are placed outside the boiler room. The main shut-off valve, main circuit breaker and main electrical switchboard are outside the boiler room, in an easily accessible place. A gas detector is used in the boiler room; a boiler room using LPG is not built in a basement.
Source: BYKHY 55(2), 55(3), 55(5), 55(10)
How is the fuel store separated from the boiler room?
The fuel store is a separate space protected by fire-rated partitions and is separated from the boiler room by a partition rated for 120 minutes. The store has ventilation and a bund that will hold at least one third of the tank capacity.
Source: BYKHY 56(1)