EI60 fire door
EI60 shows that the door maintains both its integrity (E) and its insulation (I) for 60 minutes in a fire. In a new building, the door of an escape stair serving fewer than 4 storeys, a fire compartment line and a smoke barrier in a hotel corridor need at least 60 minutes. If the stair serves a basement or more than 4 storeys, 90 minutes is required.
- The letters in EI60
- E integrity · I insulation
- Stair, fewer than 4 storeys
- At least 60 min
- Compartment line
- At least 60 min
- Hotel smoke barrier
- At least 60 min
- Polflam EI60 glass
- 25 mm
01 Enough?
Is 60 minutes enough for your door?
Choose the door's location; the scale compares the required duration with an EI60 and an EI90 door.
1Location
Does it go down to a basement?
2Wall rating, min
60minutesminimum · this location
The escape stair serves 3 storeys: fewer than 4. The door needs at least 60 minutes; EI60 is enough.
- EI60 is enoughGlass 25 mm
- Smoke-tightRequired by the article
- Self-closingWith a closer
- Report for its own typeSingle or double
Source: BYKHY 4(1)(tt), 24(7), 25(2), 47(3), 50(6)(a), 157(1)
02 What the door needs
What to look for in a 60-minute door
First the floor door of an escape stair, then the smoke barrier in a hotel corridor; tap to hold the view.
1 / 2 · Floor door of an escape stairCamera on the stair; fire in the floor corridor.
- DurationIf the stair serves fewer than 4 storeys, the door resists fire for at least 60 minutes.
- CloserThe door is fitted with a self-closing device; the article also requires it to be smoke-tight.
- GlassAn EI60 glazed door uses Polflam EI60 glass: 25 mm.
Source: BYKHY 47(3); Polflam catalogue
2 / 2 · Smoke barrier in a hotel corridorThe far part of the corridor is on fire; this side is clear.
- DoorThe escape door in the barrier resists fire for at least 60 minutes; the article also requires it to be smoke-tight.
- Top glassThe barrier rises to the ceiling; the glass above is also part of the barrier.
- SpacingAn unventilated inner corridor is divided at intervals of 45 m, or 30 m in a building without sprinklers.
Source: BYKHY 50(6), 50(6)(a)
03 Building section
Where do 60 and 90 minutes part ways in a building?
A building with a ground floor and two upper floors: escape stair, compartment wall and fire wall towards the neighbouring building. Choose a rule; its place in the section shows in orange.
What does EI60 tell you?
In the regulation's symbol table, E is integrity and I is insulation. A door marked EI60 maintains its integrity for 60 minutes in a fire and insulates its unexposed face.
ExampleFirst-floor door of the stair in the section: EI 60.
Source: BYKHY Annex 3/A
60 minutes on a stair serving fewer than 4 storeys
In a new building, the escape stair door resists fire for at least 60 minutes if the stair serves fewer than 4 storeys. The article also requires the door to be smoke-tight and self-closing.
ExampleThe stair in the section serves the ground floor and two upper floors, i.e. three storeys: floor doors 60.
Source: BYKHY 47(3)
90 minutes on a stair going down to a basement
If the stair serves basement floors or more than 4 storeys, its doors resist fire for at least 90 minutes; in that case EI60 is not enough.
ExampleOn a stair going down to the basement drawn in dashed lines, the doors rise to 90 minutes.
Source: BYKHY 47(3)
At least 60 minutes on a compartment line
A fire compartment is separated on every side, including its floor and ceiling, by elements with at least 60 minutes of fire resistance. The resistance continues at the junctions of the line; no non-fire-rated opening is left in the line.
ExampleEvery floor door in the compartment wall in the section: 60.
Source: BYKHY 4(1)(tt), 24(7)
A door in a fire wall: half the wall's duration
If a door in a fire wall cannot be avoided, the door resists fire for at least half the wall's resistance; it is self-closing and smoke-tight.
ExampleDoor in the 120-minute fire wall towards the neighbouring building: at least 60.
Source: BYKHY 25(2)
Existing building lower than 30.50 m: 60 minutes
In existing buildings, escape stair doors resist fire for at least 60 minutes if the total building height is less than 30.50 m, and at least 90 minutes if it is 30.50 m or more, and are smoke-tight.
ExampleIf the three-storey building in the section is an existing building, 60 minutes is enough for the stair doors.
Source: BYKHY 157(1)
04 Four locations
Where are 60-minute fire doors used?
Four situations; choose a location and what is required of the door there is marked beside it.
Fire side
Escape side
- On an apartment block stair In a three-storey apartment block the stair serves fewer than 4 storeys; the floor doors resist fire for at least 60 minutes and are self-closing. BYKHY 47(3)60 Fire escape stair door page
- In a hospital compartment A ward floor over 300 m² is divided into compartments of at least half its size; the door crossing the line resists fire for at least 60 minutes. BYKHY 49(1)(b), 4(1)(tt)60 Hospital page
- In a hotel corridor The escape door in the smoke barrier dividing an unventilated hotel corridor resists fire for at least 60 minutes and is smoke-tight. BYKHY 50(6)(a)60 Hotel page
- In a warehouse fire wall A door in a 120-minute fire wall resists fire for half the wall's resistance, at least 60 minutes, and is self-closing. BYKHY 25(2)60 Fire wall door page
05 Your project
Does your project need EI60 or EI90?
These four answers set the duration.
- 01
How many storeys does the stair serve?
If fewer than 4, doors are 60 minutes; if more, 90; exactly 4 storeys is settled in the project.
- 02
Is there a basement?
The doors of an escape stair going down to a basement need 90 minutes.
- 03
Which line is the door on?
60 on a compartment line; on a fire wall, half the wall's duration.
- 04
In an existing building, how many metres high is it?
In an existing building lower than 30.50 m, 60 minutes is enough for the stair door.
Send your door list and we will sort out the durations together. A floor section and the door locations are enough; our technical team will review them.
Send the project06 Products
Which glazed doors are made as EI60?
Aliplast FR65 and FR90 profiles, Polflam EI60 glass.
FR65 · FR90
Single leaf
Stair and lobby doors, EI30 and EI60. Single leaf
FR90
Double leaf
A wide door crossing a compartment line; it has a 60-minute classification. Double leaf
Made by Abay
Automatic sliding
Automatic sliding door in class EI60. Automatic sliding
The glass of a 60-minute line outside the door carries the same duration. Fixed glass partition
Abay Yapı Sistemleri
Trusted for 30 years.
We make EI60 doors and partitions with Aliplast profiles and 25 mm Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Stair and corridor doors from our reference projects.
Doors we have installed at stair entrances and on lines that cut across corridors. Tap a photo; browse with the arrows.
07 Document set
Which document states the 60 minutes of an EI60 door?
The door's class is in the report issued for its own type; the thickness and class of the glass are in the Polflam declaration.
Four checks at handover
- Class. The report must state EI 60 or a longer duration.
- Type. The report for a double-leaf door must have been issued for a double leaf.
- Smoke. At stair and smoke barrier doors the article also requires smoke-tightness.
- Glass. The project uses the EI60 glass tested in the report.
- ClassificationFR90 double leaf · 60 minutesFIRES-CR-178-17-AUPEDocument centre
- ClassificationFR65 door and partitionEI 30 · EI 60Document centre
- DeclarationPolflam EI60 glass25 mmDocument centre
- AuthorisationAliplast manufacturing authorisationAbay Yapı's manufacturing authorisationDocument centre
Source: Aliplast and Polflam documents
Request the document set for your EI60 doors. The set is prepared for the door type and size.
Document centre08 FAQ
About EI60 fire doors
Whether a door is 60 or 90 minutes is settled in the project according to the storeys the stair serves and the line the door is on. Send your section and we will sort out the durations together.
What does EI60 mean?
EI60 shows that the door maintains its integrity (E) and insulation (I) for 60 minutes in a fire. The meaning of the letters is given in the regulation's symbol table; the number is minutes.
Source: BYKHY Annex 3/A
Where are EI60 fire doors mandatory?
In a new building, at least 60 minutes is required at the door of an escape stair serving fewer than 4 storeys, on a fire compartment line, at the door of a smoke barrier in a hotel corridor and at a door in a 120-minute fire wall. Doors where 30 minutes is enough are on the EI30 fire door page.
Source: BYKHY 4(1)(tt), 25(2), 47(3), 50(6)(a)
What is the difference between EI60 and EI90?
The difference is 30 minutes. If the escape stair serves a basement or more than 4 storeys, the door must resist at least 90 minutes; EI60 is not enough and an EI90 fire door is needed. In a glazed door, Polflam glass is 25 mm in EI60 and 32 mm in EI90.
Source: BYKHY 47(3); Polflam catalogue
How thick is EI60 fire glass?
Polflam EI60 glass is 25 mm thick. The 60 minutes of the door or partition, however, are shown by the report in which the glass was tested together with the profile.
Source: Polflam catalogue
How many minutes should an apartment block stair door resist?
On an apartment block stair that does not go down to a basement and serves fewer than 4 storeys, 60 minutes is enough for the door; if there is a basement or more than 4 storeys, the duration rises to 90 minutes. The article also requires this door to be smoke-tight and self-closing.
Source: BYKHY 47(3)
How many minutes should a stair door in an existing building resist?
In existing buildings, if the total building height is less than 30.50 m the stair door resists fire for at least 60 minutes, and if it is 30.50 m or more, at least 90 minutes; the door is smoke-tight and at least 70 cm wide and 190 cm high.
Source: BYKHY 157(1)
How many minutes should a door in a fire wall resist?
At least half the wall's resistance: at least 60 minutes in a 120-minute fire wall. The regulation also requires this door to close by itself and not to let smoke through.
Source: BYKHY 25(2)
→ Quote
Tell us about your EI60 doors.
The location, type and size of the doors: our technical team will determine whether 60 or 90 is needed, the class and the document set, and get back to you.
- Phone
- +90 216 428 38 20
- abay@abayyapi.com
- Production
- Istanbul