C10Fire criteria · building type
Shopping centre fire door
In a shopping centre, the fire door stands on the compartment line that divides the shopping floor and at the entrances to the escape stairs. In a commercial building, a compartment is at most 2,000 m² where there are no fire control systems; the door on the line carries the line's fire rating. The exit door of a shop with more than 50 occupants opens in the escape direction and is not kept locked; revolving doors and turnstiles do not count as exits.
- Occupant calculation in shops
- 5 m² per person
- Door of a shop for over 50 people
- Opens in the escape direction
- Revolving door and turnstile
- Not counted as an exit
- Compartment area in commercial use
- Up to 2,000 m²
- Travel distance (without sprinklers)
- One direction 15 m · two directions 45 m
01 Exit width
How wide should your shop's exit doors be?
Enter the sales area and choose where the door opens; the plan draws the opening at the calculated width.
2Where does the door open?
150cmtotal exit width · minimum
300 people; at an exit opening outside, 100 people pass per 50 cm unit. Total exit width at least 150 cm; each escape route at least 100 cm.
- Opens in the escape directionAbove 50 occupants
- Revolving doors do not countNor do turnstiles
- Never kept lockedOpens by hand
- Compartment 2,000 m²Above this, divided or systems added
Source: Turkish Fire Regulation (BYKHY) 32(2), 33(1), 47(1), 47(2), Annex 4, Annex 5/A, Annex 5/B
02 What the door needs
What should you check on a shopping centre door?
First the compartment door across the corridor, then the revolving door at the main entrance and the exit doors beside it; tap a tab to fix the view.
1 / 2 · Door on the compartment lineThe other half of the shopping centre is on fire; this side is clear.
- DoorThe door on the line is fire-resistant; it carries the line's rating at the junctions too.
- DirectionIn a section with more than 50 occupants, the door opens in the escape direction.
- Glazed partitionThe sides and top of the door are also part of the line; no non-fire-resisting opening is left on the line.
Source: BYKHY 24(7), 47(2), Annex 4
2 / 2 · Exit doors at the main entranceThe camera is outside, on the square; the fire is in the entrance hall.
- Revolving doorRevolving doors and turnstiles cannot be used as exit doors.
- Side doorThe exit door opens outwards, in the escape direction; it opens by hand and is not kept locked.
- LockDoors kept locked for security are opened by the emergency control system in a fire.
Source: BYKHY 47(1), 47(2), 82(1)(d)
03 Shopping centre floor
How are the doors arranged on a shopping centre floor?
Shopping centre ground floor: concourse, atrium, shops, large store, main entrance and two escape stairs. When a rule is selected, its location on the plan is drawn in orange.
Compartment in commercial use at most 2,000 m²
In a commercial building, a fire compartment is at most 2,000 m²; if suitable fire control systems such as detection, sprinklers and smoke extraction are installed, the limit is lifted. The door and glazed partition on the line carry the line's rating.
ExampleOn the plan, a line running west of the large store divides the floor in two.
Source: BYKHY Annex 4, 24(7)
Atrium at least 90 m², smoke controlled
An atrium section is permitted only in low and medium hazard occupancies; the atrium area is in principle not less than 90 m². A smoke curtain of at least 45 cm is provided around a smaller void on every floor; the atrium has smoke control.
ExampleOn the plan, the atrium in the middle of the concourse is about 130 m².
Source: BYKHY 24(5)
The door of a crowded shop opens in the escape direction
The exit door of a space with more than 50 occupants opens in the escape direction, opens by hand and is not kept locked. Since 5 m² per person is used for shops, a shop over 250 m² exceeds this limit.
ExampleOn the plan, the large store's double-leaf door opens towards the concourse.
Source: BYKHY 47(2), Annex 5/A
Revolving doors and turnstiles do not count as exits
Revolving doors and turnstiles cannot be used as exit doors. An escape route door has no threshold; its clear width is at least 80 cm and its height at least 200 cm.
ExampleOn the plan, at the main entrance there is an outward-opening door on each side of the revolving door.
Source: BYKHY 47(1)
In shops, at most 45 m in two directions
In shops, the travel distance limit is 45 m in two directions (60 m with sprinklers) and 15 m in one direction (25 m with sprinklers). Dead-end corridors are at most 15 m, or 20 m with sprinklers.
ExampleOn the plan, the route from the furthest corner of the large store to the east stair.
Source: BYKHY Annex 5/B
At least two independent escape stairs in shops
Shops, stores and warehouses have at least two independent escape stairs or other exits. A single stair is enough only in a building lower than 21.50 m, with fewer than 50 people on the floor and three further conditions all met.
ExampleOn the plan, two escape stairs, one in the north and one at the east end.
Source: BYKHY 52(1)
04 Four locations
Where else are fire doors found in a shopping centre?
Four situations in shopping centres; choose a location and the requirements for the door and partition there are marked alongside.
Fire side
Escape side
- In a shopping centre cinema In a mixed-use building, at least half of the number and capacity of the exits required for a cinema, theatre or concert hall is provided within its own compartment. BYKHY 51(2)60
- In the food court kitchen A shopping centre kitchen is separated from the rest of the building by partitions that resist fire for at least 120 minutes; the extract hood has automatic extinguishing, gas detection and gas shut-off installations. BYKHY 57(1), 57(3)120 EI120 · 120 minutes page
- From an enclosed car park into the shopping centre An enclosed car park is a separate section whose walls and floors have the properties of compartment walls. Sprinklers are also mandatory in an enclosed car park with an area over 600 m². BYKHY 24(2), 96(2)(c)60 Fire compartment page
- From the service corridor to the stair The storage and service areas behind the shops are also in the commercial class. The door from the service corridor into the escape stair is smoke-tight and resists fire for 60 or 90 minutes. BYKHY 13(2), 47(3)6090 Fire escape stair door page
05 Your project
Which fire doors does your shopping centre need?
These four answers determine the compartment, shop and plant area doors.
- 01
How many m² are the shops?
5 m² per person is used; the door of a shop over 250 m² opens in the escape direction.
- 02
How large is the floor area?
In commercial use a compartment is at most 2,000 m²; with suitable fire control systems the limit is lifted.
- 03
How many floors, and how many m² in total?
Sprinklers are mandatory in multi-storey shops and shopping premises with a total area over 2,000 m².
- 04
Is there a cinema, food court or car park?
Each is separated under its own rule: cinema exits, kitchen partitions, car park walls.
Let's list the compartment and exit doors of your shopping centre together. Send the floor plans and shop areas, and our technical team will review them.
Send the project06 Glazed door
Can a shopping centre fire door be glazed?
The compartment door and partition across the concourse, and the service and stair doors, are made with Aliplast profiles and Polflam glass.
Concourse line
Double leaf
A glazed door across a wide concourse, opening in the escape direction. Double leaf
Wide concourse
With side lights
Where the concourse is wider than the door opening, a door with fixed glazing on both sides. With side lights
Above the door
Fixed glass partition
Profiled glazing that closes the top of the door up to the concourse ceiling. Fixed partition
The rating of the line and the opening direction of the door are documented together with the door's size and number of leaves. Aliplast FR65
Abay Yapı Sistemleri
Trusted for 30 years.
We make compartment and exit doors for shopping centres with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul


- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Wide passage doors from our reference projects.
Top row: our double-leaf and side-light doors suited to dividing a concourse; below: single-leaf and service doors. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for shopping centre fire doors?
The door on the line meets the line's rating and the exit door meets the calculated width; at handover both are shown with documents.
Four checks at handover
- Rating. The rating in the classification report of the door on the line must not be shorter than the line's rating.
- Direction. The door of a crowded section must open in the escape direction and be openable by hand.
- Lock. Any security lock must be connected to the emergency control system.
- Width. The clear width of the doors must meet the calculated exit width.
- ClassificationClassification report for the compartment doorWith number of leaves and sizeRequest
- ClassificationClassification report for the concourse partitionWith height and glass sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingLine, ceiling and shopfront junction detailsDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for the shopping centre doors. The set is prepared for the location, rating and size of each door.
Request the document set08 FAQ
About shopping mall fire doors
In a shopping centre, the compartment lines and exit widths are finalised in the architectural design and the fire brigade approval. Send the plans; let's mark the direction and class of each door together.
How many minutes should a shopping centre fire door resist fire?
The door on the compartment line carries the line's rating; a compartment resists fire for at least 60 minutes. The escape stair door resists fire for 60 or 90 minutes and is smoke-tight; kitchen partitions resist fire for at least 120 minutes.
Source: BYKHY 4(1)(tt), 24(7), 47(3), 57(3)
What is the maximum size of a compartment in a shopping centre?
2,000 m² in a commercial building. If suitable fire control systems such as detection, sprinklers and smoke extraction are installed, the compartment area in a commercial building is unlimited.
Source: BYKHY Annex 4
Which way should a shop door open?
The exit door of a shop with more than 50 occupants opens in the escape direction. Since 5 m² per person is used for shops, this means shops over 250 m²; the door opens by hand and is not kept locked.
Source: BYKHY 47(2), Annex 5/A
Is an exit door needed next to the revolving door at a shopping centre entrance?
Revolving doors and turnstiles cannot be used as exit doors; at the main entrance, exit is provided by hinged doors. These doors open outwards, open by hand and are not kept locked.
Source: BYKHY 47(1), 47(2)
How wide should a shop's exit door be?
The number of people is divided by the number of people who can pass through a 50 cm unit and multiplied by 0.5 m. For shops, 5 m² per person is used; 100 people pass per unit at an exit opening outside and 80 at internal doors. No exit may be narrower than 80 cm.
Source: BYKHY 33(1), 32(2), Annex 5/A, Annex 5/B
Are sprinklers mandatory in a shopping centre?
An automatic sprinkler system is mandatory in multi-storey shops and in shopping, commercial and entertainment premises with a total area over 2,000 m².
Source: BYKHY 96(2)(d)
What should an atrium in a shopping centre be like?
The atrium area is in principle not less than 90 m², and natural or mechanical smoke control is provided in the atrium. A void smaller than 90 m² is surrounded on every floor by a smoke curtain at least 45 cm deep.
Source: BYKHY 24(5)
→ Quote
Tell us about your shopping centre's doors.
Number of floors, floor area, compartment lines, shop areas: our technical team will determine the doors, their class and the document set, and get back to you.