C6Fire criteria · location
Hotel fire door
A hotel room door opening onto an internal corridor resists fire for at least 30 minutes and is self-closing; the wall between room and corridor resists fire for at least 60 minutes. An unventilated internal corridor is divided by a smoke barrier every 30 m, or every 45 m in a hotel with sprinklers; the door in the smoke barrier resists fire for at least 60 minutes and is smoke-tight.
- Fire resistance of the room door
- At least 30 minutes
- Wall between room and corridor
- At least 60 minutes
- Smoke barrier and its door
- At least 60 min, smoke-tight
- Smoke barrier spacing
- 30 m · with sprinklers 45 m
- Gap under the door
- At most 4 mm
01 Smoke barrier
How many smoke barriers does a hotel corridor need?
A smoke barrier is a fire-resisting partition with a door that divides an unventilated internal corridor. Enter the length of your corridor; the plan divides itself.
2Sprinklers
3Corridor ventilation
2smoke barriersminimum · this corridor
A 75 m internal corridor without sprinklers or ventilation is divided into 3 sections of no more than 30 m; each section is 25 m.
The smoke barrier and the door within it resist fire for at least 60 minutes; the door is smoke-tight and self-closing.
Source: Turkish Fire Regulation (BYKHY) 50(1)(c), 50(6)(a)
02 What the door needs
What should you check on a smoke barrier door?
First the smoke barrier seen from the corridor, then the underside of the door and the device that holds it open; tap a tab to fix the view.
1 / 2 · Smoke barrier seen from the corridorThe other half of the corridor is on fire; this side is clear.
- DoorResists fire for at least 60 minutes and is smoke-tight.
- Up to the ceilingThe smoke barrier, including the wall enclosing the corridor, continues up to the ceiling and tightly seals any gaps in between.
- Door closerThe leaves are self-closing and close off the opening completely.
Source: BYKHY 50(6)(a), 50(6)(ç)
2 / 2 · Underside of the door and hold-open deviceThe gap under the door and the device that holds the door open.
- Door bottomThe gap between leaf and floor is at most 4 mm; the frame sits tightly in the wall.
- Hold-open deviceThe door is normally closed; it may be held open by an electromagnetic device connected to the detection system.
- GlassIn an unglazed door, at least 25% of the leaf is vision glass; a glazed door falls outside this requirement.
Source: BYKHY 50(6)(c), 50(6)(ç), 50(6)(d)
03 Room door
What should a hotel room door be like?
Hotel floor plan: internal corridor, rooms on both sides, a suite, a housekeeping room and two escape stairs. Tap a rule; the relevant wall, door or route on the plan turns orange.
Room to corridor: 60 minutes fire resistance
Bedrooms are separated from the internal corridor by a wall that resists fire for at least 60 minutes. Where rooms are entered from an external corridor, the wall also resists fire for at least 60 minutes; non-combustible ventilation openings whose sill is at least 1.1 m above the corridor floor are excepted.
ExampleOn the plan, the walls on both sides of the internal corridor are 60-minute walls along their full length.
Source: BYKHY 50(1)(a), 50(2)(a)
Room door: 30 minutes fire resistance, self-closing
Doors opening onto the internal corridor resist fire for at least 30 minutes and are fitted with a self-closing device. The same requirement applies to room doors opening onto an external corridor.
ExampleOn the plan, every room door opening onto the corridor is 30-minute and fitted with a door closer.
Source: BYKHY 50(1)(b), 50(2)(b)
At most 15 m from the furthest point of the room to the door
If the distance from the furthest point of the room or suite to the exit door does not exceed 15 m, one door is enough; if it does, there are at least two doors located far apart. In a fully sprinklered hotel this distance may not exceed 20 m.
ExampleOn the plan, the 13.60 m suite has doors at both ends; from every point, a door is less than 15 m away.
Source: BYKHY 50(3)
Travel distance is measured from the room door to the stair
Travel distance is measured from the room's exit door to the escape stair, the external escape walkway or the door opening to the outside. Where the corridor offers escape in one direction, it is measured from the furthest room door; where it offers two directions, from each room's door.
ExampleOn the plan, there is escape in two directions: from the suite's two doors to two separate stairs.
Source: BYKHY 50(4), 50(5)
Other rooms opening onto the corridor at the same level
Other rooms opening onto the bedroom corridor, and spaces that form part of the corridor and could endanger escape, have the same compartment properties as the bedrooms.
ExampleOn the plan, the housekeeping room opening onto the corridor is also separated by a 60-minute wall and a 30-minute door.
Source: BYKHY 50(1)(ç)
At least two exits on every floor
In a hotel with more than 20 beds in total or more than two storeys, every floor has at least two exits. In a hotel with fewer than 20 beds and a building height under 15.50 m, a single stair is enough if it is protected or pressurised.
ExampleOn the plan, there is an escape stair at each end of the corridor.
Source: BYKHY 50(1)(a)
04 Four locations
Where are smoke barriers found in a hotel?
Four situations in the corridors of accommodation buildings; choose a location and the requirements for the door there are marked alongside.
Fire side
Escape side
- In a city hotel's internal corridor If a windowless internal corridor is not ventilated through openings in the external wall or by mechanical smoke extraction, in a hotel without sprinklers it is divided by a smoke barrier at least every 30 m. BYKHY 50(1)(c), 50(6)60
- In a large hotel with sprinklers Sprinklers are mandatory in a hotel of more than one storey with over 100 rooms or 200 beds. In a building with sprinklers, the smoke barrier spacing rises to 45 m. BYKHY 96(2)(ç), 50(6)60
- In a student hall of residence Student halls of residence are also accommodation buildings. In parts used as dormitories, the same room door and smoke barrier rules apply as in hotel corridors. BYKHY 10(1), 50(1), 50(6)60
- From the section to the escape stair Every section separated by smoke barriers has direct, unobstructed access to an exit, an escape stair or an external escape walkway. BYKHY 50(6)(b)60 Fire escape stair door page
05 Your project
Which fire doors does your hotel need?
These four answers determine the number of smoke barriers and the room doors.
- 01
How many rooms, beds and floors?
20 beds and two storeys determine how many exits each floor needs; 100 rooms or 200 beds determine whether sprinklers are required.
- 02
How long is the corridor?
An unventilated internal corridor is divided by a smoke barrier every 30 m, or every 45 m in a building with sprinklers.
- 03
Is the corridor ventilated?
A corridor ventilated through openings in the external wall or by mechanical smoke extraction is assessed separately.
- 04
How large are the suites?
A suite whose furthest point is more than 15 m from the door has two doors located far apart.
Let's decide on the smoke barriers in your corridors together. Send the floor plan and the number of rooms and beds, and our technical team will review them.
Send the project06 Glazed smoke barrier
Can a smoke barrier be glazed?
The smoke barrier's door and its partition up to the ceiling are made with Aliplast profiles and Polflam glass in the 60-minute class.
Door in the smoke barrier
Double leaf
A double-leaf glazed door in the 60-minute class that closes off the corridor completely. Double leaf
Wide corridor
With side lights
Where the corridor is wider than the door, a door with fixed glazing at the sides. With side lights
Up to the ceiling
Fixed glass partition
Profiled fixed glazing from the top of the door up to the ceiling. Fixed partition
The article separately requires the door in the smoke barrier to be smoke-tight; this requirement is documented together with the door's number of leaves and size. Aliplast FR65
Abay Yapı Sistemleri
Trusted for 30 years.
We make smoke barriers for hotel corridors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul



- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Corridor and passage doors from our reference projects.
Top row: our double-leaf doors across corridors; below: single-leaf doors and doors with side lights. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a smoke barrier door?
The partition and door are rated 60 minutes, and the door must also be smoke-tight; at handover both are shown with documents.
Four checks at handover
- Partition and door. Both classification reports must show fire resistance of at least 60 minutes.
- Smoke class. The report for the door in the smoke barrier must include a smoke leakage class.
- Installation. Frame tight to the wall, at most 4 mm under the leaf, partition closed up to the ceiling.
- Hold-open device. If the door is to be held open, the hold-open device must be connected to the fire detection system.
- ClassificationClassification report for the smoke barrier doorWith number of leaves and sizeRequest
- ClassificationClassification report for the glazed partitionWith height and glass sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingSmoke barrier, ceiling and wall junction detailsDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the smoke barrier's document set. The documents are sent with the type and size of the door and the partition.
Request the document set08 FAQ
About hotel fire doors
The position of the smoke barriers and the room doors is set by the project architect, the fire consultant and the fire brigade approval. The rules are on this page; let's look together at how they apply to your hotel's plan.
How many minutes should a hotel room door resist fire?
A hotel room door opening onto an internal corridor resists fire for at least 30 minutes and is fitted with a self-closing device. The wall between room and corridor resists fire for at least 60 minutes.
Source: BYKHY 50(1)(a), 50(1)(b)
When does a hotel corridor need a smoke barrier?
Internal corridors not ventilated by natural or mechanical means are divided by smoke barriers at 30 m intervals in a building without sprinklers and at 45 m intervals in a building with sprinklers. The smoke barrier resists fire for at least 60 minutes; the door within it also resists fire for at least 60 minutes and is smoke-tight.
Source: BYKHY 50(6)(a)
Can a smoke barrier door be held open?
Smoke-tight doors are normally kept closed. They may be held open if they can close automatically by means of an electromagnetic or electromechanical device operated by the detection system.
Source: BYKHY 50(6)(d)
How much gap can there be under a smoke barrier door?
The gap between leaf and floor is at most 4 mm; the frame sits tightly in the wall opening and the leaves close off the opening completely. The door may be single or double leaf; in an unglazed door, at least 25% of the leaf is vision glass.
Source: BYKHY 50(6)(c), 50(6)(ç)
How many doors should a hotel room have?
If the distance from the furthest point of the room or suite to the door does not exceed 15 m, one door is enough; if it does, there are at least two doors located far apart. In a fully sprinklered hotel this distance may not exceed 20 m.
Source: BYKHY 50(3)
How many exits should each floor of a hotel have?
In a hotel with more than 20 beds in total or more than two storeys, every floor has at least two exits. In a building with fewer than 20 beds and a building height under 15.50 m, a single stair is enough if it is protected or pressurised.
Source: BYKHY 50(1)(a)
Which hotels must have sprinklers?
Automatic sprinklers are mandatory in hotels, halls of residence and guesthouses in a building of more than one storey with more than 100 bedrooms or more than 200 beds, and in all residential accommodation facilities with a building height over 21.50 m.
Source: BYKHY 96(2)(ç)