C6Fire criteria · location

Hotel fire door

A hotel room door opening onto an internal corridor resists fire for at least 30 minutes and is self-closing; the wall between room and corridor resists fire for at least 60 minutes. An unventilated internal corridor is divided by a smoke barrier every 30 m, or every 45 m in a hotel with sprinklers; the door in the smoke barrier resists fire for at least 60 minutes and is smoke-tight.

Hotel fire door Turkey – double leaf with side lights in the lobby
Hotel lobby · Abay installation
Fire resistance of the room door
At least 30 minutes
Wall between room and corridor
At least 60 minutes
Smoke barrier and its door
At least 60 min, smoke-tight
Smoke barrier spacing
30 m · with sprinklers 45 m
Gap under the door
At most 4 mm

01 Smoke barrier

How many smoke barriers does a hotel corridor need?

A smoke barrier is a fire-resisting partition with a door that divides an unventilated internal corridor. Enter the length of your corridor; the plan divides itself.

2Sprinklers

3Corridor ventilation

2smoke barriersminimum · this corridor

A 75 m internal corridor without sprinklers or ventilation is divided into 3 sections of no more than 30 m; each section is 25 m.

The smoke barrier and the door within it resist fire for at least 60 minutes; the door is smoke-tight and self-closing.

Source: Turkish Fire Regulation (BYKHY) 50(1)(c), 50(6)(a)

stairstairHOTEL FLOOR PLAN · INTERNAL CORRIDOR · not to scaleK75 m · corridor–––
Smoke barrier60 min wallEscape stair

02 What the door needs

What should you check on a smoke barrier door?

First the smoke barrier seen from the corridor, then the underside of the door and the device that holds it open; tap a tab to fix the view.

Hotel fire door Turkey – smoke barrier in a corridor

1 / 2 · Smoke barrier seen from the corridorThe other half of the corridor is on fire; this side is clear.

Barrier≥ 60 minGap30 / 45 m

  1. DoorResists fire for at least 60 minutes and is smoke-tight.
  2. Up to the ceilingThe smoke barrier, including the wall enclosing the corridor, continues up to the ceiling and tightly seals any gaps in between.
  3. Door closerThe leaves are self-closing and close off the opening completely.

Source: BYKHY 50(6)(a), 50(6)(ç)

03 Room door

What should a hotel room door be like?

Hotel floor plan: internal corridor, rooms on both sides, a suite, a housekeeping room and two escape stairs. Tap a rule; the relevant wall, door or route on the plan turns orange.

Room to corridor: 60 minutes fire resistance

Bedrooms are separated from the internal corridor by a wall that resists fire for at least 60 minutes. Where rooms are entered from an external corridor, the wall also resists fire for at least 60 minutes; non-combustible ventilation openings whose sill is at least 1.1 m above the corridor floor are excepted.

ExampleOn the plan, the walls on both sides of the internal corridor are 60-minute walls along their full length.

Source: BYKHY 50(1)(a), 50(2)(a)

stairstairSUITEfloorofficeroominternal corridorHOTEL FLOOR PLAN · 1/200K0 – 5 m13.60 m123456
60 min wallEscape stairEscape route

04 Four locations

Where are smoke barriers found in a hotel?

Four situations in the corridors of accommodation buildings; choose a location and the requirements for the door there are marked alongside.

05 Your project

Which fire doors does your hotel need?

These four answers determine the number of smoke barriers and the room doors.

  1. 01

    How many rooms, beds and floors?

    20 beds and two storeys determine how many exits each floor needs; 100 rooms or 200 beds determine whether sprinklers are required.

  2. 02

    How long is the corridor?

    An unventilated internal corridor is divided by a smoke barrier every 30 m, or every 45 m in a building with sprinklers.

  3. 03

    Is the corridor ventilated?

    A corridor ventilated through openings in the external wall or by mechanical smoke extraction is assessed separately.

  4. 04

    How large are the suites?

    A suite whose furthest point is more than 15 m from the door has two doors located far apart.

Let's decide on the smoke barriers in your corridors together. Send the floor plan and the number of rooms and beds, and our technical team will review them.

Send the project

06 Glazed smoke barrier

Can a smoke barrier be glazed?

The smoke barrier's door and its partition up to the ceiling are made with Aliplast profiles and Polflam glass in the 60-minute class.

  1. Door in the smoke barrier

    Double leaf

    A double-leaf glazed door in the 60-minute class that closes off the corridor completely. Double leaf

  2. Wide corridor

    With side lights

    Where the corridor is wider than the door, a door with fixed glazing at the sides. With side lights

  3. Up to the ceiling

    Fixed glass partition

    Profiled fixed glazing from the top of the door up to the ceiling. Fixed partition

The article separately requires the door in the smoke barrier to be smoke-tight; this requirement is documented together with the door's number of leaves and size. Aliplast FR65

Abay Yapı Sistemleri

Trusted for 30 years.

We make smoke barriers for hotel corridors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Hotel fire door project Turkey – double leaf held open in a lift lobbyHotel fire door project Turkey – double leaf with panic bars, side and top lightsHotel fire door project Turkey – door and glass partition in a lift lobby
Lift lobby · Double leaf · top light
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Corridor and passage doors from our reference projects.

Top row: our double-leaf doors across corridors; below: single-leaf doors and doors with side lights. Tap a photo; browse with the arrows.

07 Document set

Which documents are required for a smoke barrier door?

The partition and door are rated 60 minutes, and the door must also be smoke-tight; at handover both are shown with documents.

Four checks at handover

  1. Partition and door. Both classification reports must show fire resistance of at least 60 minutes.
  2. Smoke class. The report for the door in the smoke barrier must include a smoke leakage class.
  3. Installation. Frame tight to the wall, at most 4 mm under the leaf, partition closed up to the ceiling.
  4. Hold-open device. If the door is to be held open, the hold-open device must be connected to the fire detection system.
  • ClassificationClassification report for the smoke barrier doorWith number of leaves and sizeRequest
  • ClassificationClassification report for the glazed partitionWith height and glass sizeRequest
  • DeclarationDeclaration of performanceCE markedRequest it
  • DrawingSmoke barrier, ceiling and wall junction detailsDWGRequest

Source: Turkish Construction Products Regulation 6(1), 10(2)

Request the smoke barrier's document set. The documents are sent with the type and size of the door and the partition.

Request the document set

08 FAQ

About hotel fire doors

The position of the smoke barriers and the room doors is set by the project architect, the fire consultant and the fire brigade approval. The rules are on this page; let's look together at how they apply to your hotel's plan.

0216 428 38 20Send a question

How many minutes should a hotel room door resist fire?

A hotel room door opening onto an internal corridor resists fire for at least 30 minutes and is fitted with a self-closing device. The wall between room and corridor resists fire for at least 60 minutes.

Source: BYKHY 50(1)(a), 50(1)(b)

When does a hotel corridor need a smoke barrier?

Internal corridors not ventilated by natural or mechanical means are divided by smoke barriers at 30 m intervals in a building without sprinklers and at 45 m intervals in a building with sprinklers. The smoke barrier resists fire for at least 60 minutes; the door within it also resists fire for at least 60 minutes and is smoke-tight.

Source: BYKHY 50(6)(a)

Can a smoke barrier door be held open?

Smoke-tight doors are normally kept closed. They may be held open if they can close automatically by means of an electromagnetic or electromechanical device operated by the detection system.

Source: BYKHY 50(6)(d)

How much gap can there be under a smoke barrier door?

The gap between leaf and floor is at most 4 mm; the frame sits tightly in the wall opening and the leaves close off the opening completely. The door may be single or double leaf; in an unglazed door, at least 25% of the leaf is vision glass.

Source: BYKHY 50(6)(c), 50(6)(ç)

How many doors should a hotel room have?

If the distance from the furthest point of the room or suite to the door does not exceed 15 m, one door is enough; if it does, there are at least two doors located far apart. In a fully sprinklered hotel this distance may not exceed 20 m.

Source: BYKHY 50(3)

How many exits should each floor of a hotel have?

In a hotel with more than 20 beds in total or more than two storeys, every floor has at least two exits. In a building with fewer than 20 beds and a building height under 15.50 m, a single stair is enough if it is protected or pressurised.

Source: BYKHY 50(1)(a)

Which hotels must have sprinklers?

Automatic sprinklers are mandatory in hotels, halls of residence and guesthouses in a building of more than one storey with more than 100 bedrooms or more than 200 beds, and in all residential accommodation facilities with a building height over 21.50 m.

Source: BYKHY 96(2)(ç)

→ Quote

Tell us about your hotel's doors.

Number of floors, rooms and beds, corridor length: our technical team will determine the smoke barriers, their class and the document set, and get back to you.

Call · 0216 428 38 20Email

Production
Istanbul

Quote form* required field

CallRequest a quote