C2Fire criteria · location
Emergency exit door
An emergency exit door is the door on the escape route through which people leave the building in a fire. Under the Turkish Fire Regulation (BYKHY), it has a clear width of at least 80 cm and a height of 200 cm, has no threshold and is never kept locked. In a space with more than 50 people it opens in the direction of escape; at ground-level exits it opens by pushing, without a lever handle.
Panic barNo handle, opens by pushing
No thresholdThe floor runs level under the door
- Clear width
- At least 80 cm
- Height
- At least 200 cm
- Threshold
- None
- Lock
- Not fitted
- Opening force
- At most 110 N
01 Number of exits
How many emergency exit doors must a space have?
The number of exits is set by the number of people in the space. Choose the number of people.
2exitsminimum · by the number of people in the space
Unless stated otherwise, every building has at least 2 exits. In a new building, at least 2 exits are required in every space with more than 50 people, or more than 25 people in a high-hazard space; in an existing building the limit is 60 people. In a single undivided space, the distance between two exits is at least half the diagonal without sprinklers, and at least one third with sprinklers.
Source: BYKHY 39(1), 39(2), 39(3), 150(1)(a)
3exitsminimum · by the number of people in the space
A space with more than 500 people has at least 3 exits; in an existing building the limit is 600 people. Exits are placed as far apart as possible.
Source: BYKHY 39(2), 39(3), 150(1)(a)
4exitsminimum · by the number of people in the space
A space with more than 1000 people has at least 4 exits; in an existing building the limit is also 1000 people.
Source: BYKHY 39(2), 150(1)(a)
When a single exit is enough: in a ground-floor shop with fewer than 50 people and less than 25 m from the furthest point to the external door, a single exit is enough (32(8)).
02 What the door needs
What requirements apply to an emergency exit door?
First from inside, then from outside; tapping a tab fixes the view.
1 / 2 · From insideA fire has started behind the lobby; a person escaping leans on the panic bar and opens the door outwards.
- Panic barA ground-level exit opens in the direction of escape without a lever handle, with a force of no more than 110 N.
- LeafThe door opens by hand and is never kept locked; no lock or bolt that would obstruct escape is fitted.
- FloorAn escape route door has no threshold; revolving doors and turnstiles do not count as exit doors.
Source: BYKHY 30(4), 47(1), 47(2), 47(5), 47(6)
2 / 2 · From outsideThe door opens in the direction of escape, outwards: the hinges and door closers are visible on the outside.
- HingeIn a space with more than 50 people, the exit door opens in the direction of escape; for this door that means outwards.
- Between leavesFor a double leaf, the clear width is measured between the leaf faces with both leaves open at 90°.
- Door closerIf the door opens onto an external passage, it is fitted with a self-closing device and resists fire for at least 30 minutes.
Source: BYKHY 33(5), 37(2), 47(1), 47(2)
03 Width
How wide must an emergency exit door be?
The measure is not the door's outer size but the clear opening left when it is open.
- 1Single leaf 80–120 cmFor a single leaf, the clear width is measured between the frame and the face of the leaf opened to 90°; at least 80, at most 120 cm. Height at least 200 cm.BYKHY 47(1), 47(4)
- 2Route sized to the crowdWith 50–500 people on the floor, an escape route is at least 100 cm wide; with 501–2000 people at least 150 cm; with more, at least 200 cm.BYKHY 33(1)
- 3Double leafAn opening wider than 120 cm is provided with a double leaf; the clear width is measured between the leaf faces with both leaves open at 90°. Where a space needs two exits, each serves at least half the occupants.BYKHY 33(4), 33(5)
04 Where
What requirements does the place the emergency exit door opens onto bring?
Four locations: two require opening direction and handle-free opening, two require fire resistance. Tap a location to highlight the required properties.
Fire side
Escape side
- Final exit out of the building All escape route doors leading from the stair to a safe area at ground level open in the direction of escape without a lever handle. In spaces with more than 50 people, the exit door opens in the direction of escape, outwards. BYKHY 47(2), 47(5)
- Exit from a crowded hall A hall with an occupant load of more than 50 people has at least 2 exits, and the exit doors open in the direction of escape, out of the hall. If there are more than 500 people, at least 3 exits are needed. BYKHY 39(2), 47(2)
- Door onto an internal escape corridor Exit doors opening onto an internal escape corridor have fire resistance equivalent to doors opening onto an escape stair and are fitted with a self-closing device. BYKHY 36(1)(b)(1)
- Door onto an external passage An external passage may be used as the escape route instead of an internal corridor. An exit door opening onto an external passage resists fire for at least 30 minutes and is self-closing. BYKHY 37(1), 37(2)30
05 Your project
Which rule applies to the exit door in your project?
These four answers change the size, direction and class of the exit door.
- 01
How many people are in the space?
In a space with more than 50 people, the door opens in the direction of escape and at least 2 exits are needed; at 500 and 1000 people the number of exits rises.
- 02
Where does the door open onto?
A door opening onto an escape stair, an internal escape corridor or an external passage is fire-rated and self-closing.
- 03
Is the building new or existing?
In an existing building, the 60 and 600 people limits apply to the number of exits; an escape route door is at least 70 × 190 cm.
- 04
Is the building a high-rise?
In high-rise buildings, escape routes and stairs are at least 120 cm wide.
Let's define the size and class of your exit doors together. Send us the plan and the number of people and our technical team will review it.
Send the project06 Glazed door
Can we make the emergency exit door glazed?
We make it with Aliplast profiles and Polflam glass, to the size of the opening.
Single leaf
80–120 cm opening
For exits where the clear width can be provided with a single leaf. Single leaf
Double leaf
Crowded exits
Openings wider than 120 cm, hall and building exits; up to 3.17 × 2.87 m. Double leaf
With side lights
Door in a wide opening
If the opening is wider than the door, the sides and top are closed with fixed glass. With side lights
Panic hardware is available on our Aliplast doors; exits that must be fire-rated use Aliplast FR90, or Aliplast FR65 indoors.
Abay Yapı Sistemleri
Trusted for 30 years.
We manufacture exit doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to the size of the opening.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Building and escape exits from our reference projects.
Top row: our exit doors opening out of buildings; below: lobby and stair passages. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a fire-rated exit door?
If the exit door opens onto a stair, an internal escape corridor or an external passage, its fire resistance is shown by documents.
Four checks at handover
- Fire resistance. The minutes in the report must not be less than the duration required where the door opens.
- Self-closing. In these locations the door is self-closing; look for the letter C on the certificate.
- Type and size. The report for a double-leaf exit must have been issued for a double-leaf door.
- Declaration and CE. A declaration of performance and CE marking issued for the door are required.
- ClassificationThe door's classification reportMatching the type and size of the door in the projectRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- AuthorisationAliplast manufacturing authorisationAuthorised manufacturer and distributor in TurkeyRequest it
- DrawingExit door sectionsDWGRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Ask for the exit door document set. Documents are sent together with the door's location and type.
Request the document set08 FAQ
About emergency exit doors
The final size and class are set by the project designer, the fire consultant and fire brigade approval. The rules here are a starting point; let's clarify together what they mean for your project.
When must an emergency exit door be fire-rated?
If the door opens onto an escape stair, it follows the stair door rules (at least 60 or 90 minutes); onto an internal escape corridor, fire resistance equivalent to the stair door; onto an external passage, at least 30 minutes. These doors are self-closing.
Source: BYKHY 47(3), 36(1)(b)(1), 37(2)
What size must an emergency exit door be?
Clear width at least 80 cm, height at least 200 cm. In a single-leaf door the clear width may not exceed 120 cm; a wider opening is made with a double leaf. In an existing building, an escape route door is at least 70 cm wide and 190 cm high.
Source: BYKHY 47(1), 47(4), 157(1)
How many emergency exits must a building have?
Unless stated otherwise, at least 2. In a new building, every space with more than 50 people has at least 2 exits, more than 500 people at least 3, and more than 1000 people at least 4. In a ground-floor shop with fewer than 50 people and less than 25 m to the external door, a single exit is enough.
Source: BYKHY 39(1), 39(2), 32(8)
Is a panic bar mandatory on an emergency exit door?
All escape route doors leading from the stair to a safe area at ground level, and stair, corridor and lobby doors when more than 100 people are on a floor, open in the direction of escape without a lever handle. For existing buildings, the regulation describes this as a panic handle or similar device.
Source: BYKHY 47(5), 157(4)
Does an emergency exit door open outwards?
In spaces with an occupant load of more than 50 people, the exit door opens in the direction of escape; at a building exit that means outwards. Door leaves must not obstruct the occupants' movement.
Source: BYKHY 47(2)
Can an emergency exit door be kept locked?
No. Escape route doors open by hand and are never kept locked; no lock, bolt or similar device that would obstruct free escape may be fitted.
Source: BYKHY 47(2), 30(4)
Does a revolving door count as an emergency exit?
No. Revolving doors and turnstiles cannot be used as exit doors; an escape route door also has no threshold.
Source: BYKHY 47(1)