C1Fire criteria · location
Fire escape stair door
A fire escape stair door stays closed when a fire breaks out and resists the passage of smoke, heat and flame into the stair for a set time. Under the Turkish Fire Regulation (BYKHY), in a new building this time is at least 60 minutes if the stair serves fewer than 4 storeys, and at least 90 minutes if it serves a basement or more than 4 storeys. The door is smoke-tight and self-closing.
Floor doorClosed, fire behind
- Fire resistance
- At least 60 · 90 min
- Smoke
- Tight
- Closing
- Self-closing
- Sizes
- ≥ 80 × 200 cm
- Lock
- Not fitted
01 Fire resistance
How many minutes must a fire escape stair door resist fire?
The minimum time the door, closed during a fire, must resist the passage of smoke, heat and flame. Choose your building.
60minutesfire resistance, minimum
In a new building, the door of a stair serving fewer than 4 storeys resists the passage of smoke, heat and flame in a fire for at least 60 minutes; it is self-closing.
Source: BYKHY 47(3)
90minutesfire resistance, minimum
If the stair serves more than 4 storeys, its door resists the passage of smoke, heat and flame in a fire for at least 90 minutes; it is self-closing.
Source: BYKHY 47(3)
90minutesfire resistance, minimum
If the stair also serves basement floors, its doors resist fire for at least 90 minutes. A stair serving more than 4 storeys including the basement is entered on basement floors through a fire safety lobby (except for special cases in residential buildings).
Source: BYKHY 47(3), 46(2)(a)
60minutesfire resistance, minimum
In an existing building, the measure is the building height, not the number of storeys: below 30.50 m, stair doors resist fire for at least 60 minutes, are smoke-tight and are self-closing.
Source: BYKHY 157(1), 157(3)
90minutesfire resistance, minimum
If the building height is 30.50 m or more, stair doors in an existing building also resist fire for at least 90 minutes and are smoke-tight.
Source: BYKHY 157(1), 157(3)
Read together: 38(3) requires escape stair doors in general to resist fire for at least 90 minutes. Let's check together whether 60 minutes suits your project.
- 1Floor door: glazed fire door, self-closing
- 2Stair enclosure: protected escape stair
- 3Escape direction: from floor to stair
DrawingSection A-A BuildingNew building · 3 storeysNew building · 6 storeysNew building · 3 storeys + basementExisting · 17.50 mExisting · 35.00 m DoorAt least 60 minAt least 90 minAt least 90 minAt least 60 minAt least 90 min Article47(3)47(3)47(3), 46(2)(a)157(1), 157(3)157(1), 157(3)
Storey height taken as 3.50 m; the scale is the same for all options.
02 What the door needs
What other requirements apply to a stair door?
First the stair side, then the floor side; tapping a tab fixes the view.
1 / 2 · From the stair sideThe door opens from the floor into the stair; the door closer and hinges are visible on the stair side. Behind the glass the floor is on fire; the stair is empty.
- Door closerThe door is fitted with a self-closing device; it does not stay open.
- Frame and edgesThe door must be smoke-tight: when closed, smoke must not pass around the edges into the stair.
- Lever handleThe door opens by hand and is never kept locked. No lock, bolt or similar device that would obstruct escape is fitted.
- FloorAn escape route door has no threshold; the stair entrance is level with the floor landing.
Source: BYKHY 47(1), 47(2), 47(3), 30(4), 40(1)
2 / 2 · From the floor sideA fire has started at the end of the corridor; the door is pushed open in the direction of escape, towards the stair.
- Panic barIf there are more than 100 people on the floor, the door must open in the direction of escape without using a lever handle.
- LeafClear width at least 80 cm, height at least 200 cm. In an existing building at least 70 × 190 cm.
- Opening directionIn spaces with more than 50 people, the exit door opens in the direction of escape. The door must open with a force of no more than 110 N.
Source: BYKHY 47(1), 47(2), 47(5), 47(6), 157(1)
03 Opening
How does the door open onto the stair landing?
Floor corridor, door and landing in plan. Numbers alongside.
- 1Opens towards escapeIn spaces with more than 50 people, the exit door opens in the direction of escape; for a stair door this is towards the landing.BYKHY 47(2)
- 2Clear widthMeasured between the frame and the face of the leaf opened to 90°: at least 80 cm, at most 120 cm for a single leaf.BYKHY 47(1), 47(4)
- 3Landing not narrowedA door opening onto the landing may never be positioned so that it narrows the escape route by more than 1/3.BYKHY 41(5)
- 4Same level, no thresholdThe stair entrance is level with the floor landing; the door has no threshold.BYKHY 40(1), 47(1)
04 Where
Which stair doors does this rule cover?
Four locations, each with the fire behind the glass. Tap a location to highlight the required properties.
Fire side
Escape side
- Door from floor to stair The escape stair is separated from other areas by walls resisting fire for at least 120 minutes and a smoke-tight door resisting fire for at least 90 minutes. For a stair serving fewer than 4 storeys in a new building, at least 60 minutes is stated for the door; the two articles are read together. BYKHY 38(3), 47(3)6090
- Fire safety lobby door The fire safety lobby leading to the stair is separated by walls resisting fire for at least 120 minutes and a smoke-tight door resisting fire for at least 90 minutes. Lobby doors have the same fire resistance duration as stair doors; they are self-closing. BYKHY 34(2), 34(6), 47(3)90 Fire safety lobby page
- Door separating the basement The ground-floor landing of the stair is separated from the basement stair by a door or similar barrier, or clear signage is provided, so that people escaping from upper floors do not go down into the basement. Doors of a stair serving a basement resist fire for at least 90 minutes. BYKHY 46(2)(b), 47(3)
- Door onto an external escape stair Within 3 m to the sides of and below an open external escape stair, there may be no door or window less protected than the stair. Open external stairs are not permitted in buildings more than 21.50 m high above ground. BYKHY 42(2), 42(3)
05 Your project
Which rule applies to your project?
These four questions decide how the rule applies to your project.
- 01
Is the building new or existing?
How many minutes the door must resist fire is set by the number of storeys in a new building and by the building height in an existing one.
- 02
Does the stair go down to the basement?
The door of a stair serving a basement resists fire for at least 90 minutes; a lobby may be needed in the basement.
- 03
How many people are on the floor?
In a space with more than 50 people, the door opens in the direction of escape; if there are more than 100 people on the floor, it opens without a lever handle.
- 04
Is there a lobby in front of the stair?
In a building with a firefighting lift that exceeds 51.50 m, a fire safety lobby in front of the stair is mandatory.
Which class and document set does your project need? Send us the plan or the number of storeys and our technical team will review your project.
Send the project06 Glazed door
Can we make the fire escape stair door glazed?
We make it with Aliplast profiles and Polflam glass, to each project's dimensions.
Single leaf
80–120 cm opening
Aliplast FR90 held back flames and smoke for 103 minutes in the fire test. Single leaf
Double leaf
Wide opening
For stair and lobby entrances where a single leaf is not enough; up to 3.17 × 2.87 m. Double leaf
With side lights
Door and fixed glass
If the opening in the stair wall is wider than the door, the side is closed with fixed glass. With side lights
Internal doors resisting fire for up to 60 minutes use Aliplast FR65; doors resisting fire for 90 minutes, inside or outside, use Aliplast FR90.
Abay Yapı Sistemleri
Trusted for 30 years.
We manufacture stair and lobby doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Stair and lobby doors from our reference projects.
Top row: our doors at stairs, lobbies and escape passages; below: our other work. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a fire escape stair door?
For a stair door, the fire resistance duration alone is not enough: smoke tightness and self-closing must also appear on the certificate.
Four checks at handover
- Fire resistance. The door's class in the report must meet the 60 or 90 minutes the stair requires.
- Smoke and closing. Smoke tightness (S) and self-closing (C) must be stated separately on the certificate.
- Size and type. The door's type and size must match the one tested in the report; a single-leaf report does not cover a double-leaf door.
- Declaration and CE. The door's declaration of performance and CE marking are required.
- ClassificationThe door's classification reportMatching the type and size of the door in the projectRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- AuthorisationAliplast manufacturing authorisationAuthorised manufacturer and distributor in TurkeyRequest it
- DrawingDoor sectionsDWGRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Ask for the stair door document set. Documents are sent together with the door type and project details.
Request the document set08 FAQ
About fire escape stair doors
The final class is set by the project designer, the fire consultant and fire brigade approval. This page is guidance; ask us how it applies to your project.
How many minutes must a fire escape stair door resist fire?
The duration is the minimum time the door, closed during a fire, must resist the passage of smoke, heat and flame. In a new building: at least 60 minutes if the stair serves fewer than 4 storeys, at least 90 minutes if it serves basement floors or more than 4 storeys. For the door separating the escape stair from other areas, 38(3) states at least 90 minutes; the two articles are read together.
Source: BYKHY 4(1)(şş), 47(3), 38(3)
Must a fire escape stair door be smoke-tight?
Yes. In both new and existing buildings, the escape stair door is smoke-tight and self-closing. These properties are shown separately on the certificate alongside the duration.
Source: BYKHY 47(3), 157(1), 157(3)
How many minutes must a fire escape stair door resist fire in an old building?
In an existing building, the building height counts, not the number of storeys: below 30.50 m the door resists fire for at least 60 minutes, at 30.50 m and above for at least 90 minutes. The door is at least 70 cm wide and 190 cm high.
Source: BYKHY 157(1)
Can a fire escape stair door be locked?
No. No lock, bolt or similar device may be fitted to doors in a way that obstructs escape; the door opens by hand and is never kept locked. The exception is premises housing people with intellectual disabilities, detainees or inmates, where authorised staff are always on duty and able to move the occupants.
Source: BYKHY 30(4), 47(2)
Is a panic bar mandatory on a fire escape stair door?
If more than 100 people are on a floor, the escape stair door must open in the direction of escape without using a door handle. For existing buildings, the regulation describes this as a panic handle or similar device.
Source: BYKHY 47(5), 157(4)
Which way does a fire escape stair door open?
In spaces with an occupant load of more than 50 people, the exit door opens in the direction of escape. A door opening onto the stair landing may not be positioned so that it narrows the escape route by more than 1/3.
Source: BYKHY 47(2), 41(5)
What size must a fire escape stair door be?
In a new building, clear width at least 80 cm and height at least 200 cm; in a single-leaf door the clear width may not exceed 120 cm. Clear width is measured between the frame and the face of the leaf opened to 90°.
Source: BYKHY 47(1), 47(4)
→ Quote
Tell us about your stair doors.
Number of storeys, whether the building is new or existing, door size: our technical team will determine the class and document set and get back to you.
- Phone
- +90 216 428 38 20
- abay@abayyapi.com
- Production
- Istanbul