C9Fire criteria · building type
Office building fire door
In an office building, the fire door stands first and foremost at the entrance to the escape stair. This door is smoke-tight and self-closing; if it serves fewer than 4 floors it resists fire for at least 60 minutes, and if it serves a basement or more than 4 floors, for at least 90 minutes. An office building has at least two independent escape stairs; in an office tower over 51.50 m, a fire safety lobby is built in front of the stair.
- Stair door, fewer than 4 floors
- At least 60 minutes
- Basement or more than 4 floors
- At least 90 minutes
- Escape stair
- At least two, independent
- Lobby door above 51.50 m
- At least 90 min, smoke-tight
- Compartment area in offices
- Up to 8,000 m²
01 Number of floors
How many minutes should the stair door in your office building resist fire?
Enter the number of floors, the basements and the area of one floor; the section shows the rules that change with height. A floor height of 3.50 m is assumed in the calculation.
90minutesstair door · minimum
12 floors and 2 basements, building height ≈ 49 m. At least two independent escape stairs are required. The stair door resists fire for at least 90 minutes.
- Two escape stairsUnless the single-stair conditions are met
- One compartment every three floorsFloors above 21.50 m
- SprinklersOnce the building exceeds 30.50 m
- Fire safety lobby, firefighting liftOnce the building exceeds 51.50 m
Source: Turkish Fire Regulation (BYKHY) 47(3), 52(1), 24(4), 96(2)(a), 34(7), 63(2), Annex 5/A
02 What the door needs
What should you check on an office building door?
First the floor door of the escape stair, then, in a high-rise office tower, the door of the fire safety lobby in front of the stair; tap a tab to fix the view.
1 / 2 · Escape stair doorThe camera is in the stair; the fire is on the office floor.
- DoorResists fire for at least 60 or 90 minutes; the article requires it to be smoke-tight.
- Door closerThe door is self-closing; the fire brigade can enter from outside when needed.
- WidthClear width at least 80 cm, height at least 200 cm; the door has no threshold.
Source: BYKHY 47(1), 47(3)
2 / 2 · Fire safety lobby doorThe camera is in the fire safety lobby; the fire is on the office floor.
- DoorThe lobby door resists fire for at least 90 minutes; the article requires it to be smoke-tight.
- WallThe lobby is enclosed by walls that resist fire for at least 120 minutes and contain no combustible material.
- LiftThe firefighting lift opens into this lobby; the lobby is 6–10 m², with every side at least 2 m.
Source: BYKHY 34(2), 34(4), 34(7), 63(3)
03 Office floor
What should the stairs and lobbies on an office floor be like?
Office tower floor plan: open-plan office, meeting room, core, two escape stairs and fire safety lobbies in front of them. Tap a rule; its location on the plan turns orange.
At least two independent escape stairs in an office building
An office building has at least two independent escape stairs or other exits. If the building is lower than 21.50 m, fewer than 50 people are on the floor and three further conditions are met, a single stair is enough.
ExampleOn the plan, there is an escape stair at each end of the floor.
Source: BYKHY 52(1)
Stair door smoke-tight, 60 or 90 minutes fire resistance
The escape stair door is smoke-tight and self-closing; if it serves fewer than 4 floors it resists fire for at least 60 minutes, and if it serves a basement or more floors, for at least 90 minutes.
ExampleOn the plan, both stair doors open from the lobby into the stair, in the escape direction.
Source: BYKHY 47(3)
Fire safety lobby in front of the stair in a high-rise office tower
In a building with a firefighting lift and a building height over 51.50 m, a fire safety lobby is built in front of the escape stair. The lobby wall resists fire for at least 120 minutes and its door for at least 90 minutes; the door is smoke-tight.
ExampleOn the plan, there is a lobby in front of each stair; two doors, from the office into the lobby and from the lobby into the stair.
Source: BYKHY 34(2), 34(7)
Firefighting lift lobby 6–10 m²
In a building with a height over 51.50 m, at least one lift is a firefighting lift. The lobby in front of it also gives access to the escape stair; its area may be no less than 6 m² and no more than 10 m², and no side may be shorter than 2 m.
ExampleOn the plan, the west lobby is 3.00 × 3.00 m, i.e. 9 m²; the firefighting lift opens into this lobby.
Source: BYKHY 63(2), 63(3), 34(4)
In offices, at most 45 m for two-way escape
In an office building, the distance from the furthest point to an exit with two-way escape is 45 m without sprinklers and 75 m with sprinklers; with one-way escape it is 15 m and 30 m. A dead-end corridor may not exceed 15 m, or 20 m in a building with sprinklers.
ExampleOn the plan, the route from the north-east corner to the east lobby.
Source: BYKHY Annex 5/B
The door of a crowded room opens in the escape direction
The exit door of a space with an occupant load over 50 people opens in the escape direction and is not kept locked. An escape door has a clear width of at least 80 cm and a height of at least 200 cm; there is no threshold.
ExampleOn the plan, the meeting room door opens towards the open-plan office.
Source: BYKHY 47(1), 47(2)
04 Four locations
Where else are fire doors found in an office building?
Four situations in office buildings; choose a location and the requirements for the door there are marked alongside.
Fire side
Escape side
- In a low-rise office building In a three-storey office building the stair serves fewer than 4 floors; its door resists fire for at least 60 minutes. If there is a basement, the rating rises to 90 minutes. BYKHY 47(3), 52(1)6090
- In bank and public buildings Banks, stock exchanges and public service buildings also count as office buildings. The number of escape stairs and the rating of the stair door follow the same rule as in an office building. BYKHY 12(1), 52(1)6090
- From an enclosed car park into the building The walls and floors of the car park have the properties of compartment walls. The door from the car park into the building is part of this line and carries its rating. BYKHY 24(2), 24(7)60 Fire compartment page
- In electrical and generator rooms The main electrical distribution room, transformer substation and generator room are enclosed spaces with a fire hazard; their walls have the properties of compartment walls and their doors are fire-resistant. BYKHY 24(2), 24(7)60
05 Your project
Which fire doors does your office building need?
These four answers determine the stair, lobby and plant room doors.
- 01
How many floors and basements?
A basement, or more than 4 floors, raises the stair door rating to 90 minutes.
- 02
What is the building height in metres?
The 21.50, 30.50 and 51.50 m thresholds bring in compartments, sprinklers and the fire safety lobby.
- 03
How many people will work on one floor?
In offices, 10 m² per person is used; 50 or more people on a floor rules out the single-stair option.
- 04
Is there a car park or plant room?
The doors of an enclosed car park and of electrical and generator rooms stand in a compartment wall.
Let's count the stair and lobby doors of your office tower together. Send the section and the typical floor plan, and our technical team will review them.
Send the project06 Glazed door
Can an office building fire door be glazed?
The stair and lobby doors, and the partition separating the lift lobby from the office, are made with Aliplast profiles and Polflam glass; the 90-minute door uses the FR90 system.
Stair and lobby
Single leaf
The floor door of the stair and of the fire safety lobby. Single leaf
Lift lobby
Double leaf
A wide glazed door separating the lift lobby from the open-plan office. Double leaf
Around the door
Fixed glass partition
Profiled glazing that closes the side and top of the door up to the ceiling. Fixed partition
For stair and lobby doors, the article also requires smoke tightness; this requirement is documented together with the door's size and number of leaves. Aliplast FR90
Abay Yapı Sistemleri
Trusted for 30 years.
We make stair and lobby doors for office buildings with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Office and office tower doors from our reference projects.
Top row: our single-leaf doors at stair and lobby entrances; below: lift lobby and corridor crossings. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for stair and lobby doors in an office building?
Stair door 60 or 90 minutes, lobby door 90 minutes; at handover, the rating, smoke class and door closer are shown with documents.
Four checks at handover
- Rating. The rating in the classification report must meet the rating required for the number of floors the stair serves.
- Smoke. The report for the stair and lobby door must include a smoke leakage class.
- Door closer. The door must be self-closing and openable by the fire brigade from outside.
- Size. Door opening at least 80 × 200 cm; no threshold.
- ClassificationClassification report for the stair and lobby doorWith rating and smoke classRequest
- ClassificationClassification report for the lift lobby partitionWith height and glass sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingDoor, wall and floor junction detailsDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for the stair and lobby doors. The set is prepared for the type, rating and size of the door.
Request the document set08 FAQ
About office building fire doors
In an office tower, the number of stairs and lobbies is finalised in the architectural design and the fire brigade approval. Send your section and typical floor plan; let's list the doors and their classes together.
How many minutes should a fire door in an office building resist fire?
An escape stair door resists fire for at least 60 minutes if it serves fewer than 4 floors, and for at least 90 minutes if it serves a basement or more than 4 floors. The fire safety lobby door resists fire for at least 90 minutes; a door in a compartment wall carries the wall's rating.
Source: BYKHY 47(3), 34(2), 24(7)
How many escape stairs should an office building have?
Office buildings have at least two independent escape stairs or other exits. A single stair requires all five conditions: building height below 21.50 m and fewer than 50 people on the floor; suitable travel distances; non-combustible construction products; no highly flammable materials.
Source: BYKHY 52(1)
When is a fire safety lobby mandatory in an office tower?
In a building with a height over 51.50 m, there is at least one firefighting lift and a fire safety lobby is built in front of the escape stair. The firefighting lift opens into this lobby; the lobby area is between 6 and 10 m².
Source: BYKHY 63(2), 34(7), 34(4)
When are sprinklers mandatory in an office building?
An automatic sprinkler system is installed in all non-residential buildings with a building height over 30.50 m. Sprinklers are also mandatory in an enclosed car park with an area over 600 m².
Source: BYKHY 96(2)(a), 96(2)(c)
How many people are counted on an office floor?
In escape calculations, 10 m² per person is used for offices. A 1,200 m² office floor therefore counts as 120 people.
Source: BYKHY 32(1), Annex 5/A
How are the floors of a high-rise office building divided?
In an office building taller than 21.50 m, the floors above this height are divided into fire compartments of three floors each. In an office building, a compartment is at most 8,000 m².
Source: BYKHY 24(4), Annex 4
Must the door opening into an enclosed car park be fire-resistant?
Yes. The walls and floors of the car park have the properties of compartment walls, and there may be no non-fire-resisting opening between compartments; the door into the building is also fire-resistant.
Source: BYKHY 24(2), 24(7)