C12Fire criteria · building type
School fire door
In a school, fire doors sit on the compartment line dividing the corridor, at the entrance to the escape stair and at the sports hall exits. A classroom is counted at 1.5 m² per person; a classroom larger than 75 m² holds more than 50 people, has two doors, and the doors open in the escape direction. In an education building, a compartment is at most 6,000 m² unless a fire control system is installed.
- Occupant count in a classroom
- 1.5 m² per person
- Classroom with more than 50 people
- Two doors, opening in the escape direction
- Occupant count in a sports hall
- 3 m² per person
- Compartment area in education
- At most 6,000 m²
- Travel distance (without sprinklers)
- One direction 15 m · two directions 45 m
01 Number of doors
How many doors should your classroom have?
Enter the room's area and choose its type; the plan shows the number of doors and the direction the leaf opens.
2Room
2doorsminimum · this room
90 m² classroom at 1.5 m² per person: 60 people. At least 2 exits, far apart; the doors open in the escape direction. Total exit width at least 80 cm; each exit provides at least half of it.
- Opens in the escape directionAbove 50 occupants
- Doors far apartAt least half the diagonal
- Each door halfOf the total width
- Emergency lightingRequired in education buildings
Source: BYKHY 33(1), 33(4), 39(2), 39(3), 47(2), 72(2)(a), Annex 5/A, Annex 5/B
02 What the door needs
What is checked on school doors?
First the compartment door dividing the corridor, then the sports hall exit to the yard; tap a tab to fix the view.
1 / 2 · Compartment door in the corridorThe other half of the corridor is on fire; this side is clear.
- DoorThe door cutting across the corridor carries the compartment line's rating of at least 60 minutes.
- Upper glassThe glass above the door, up to the ceiling, is part of the line; no opening is left in the line.
- DirectionAt the exit from a crowded area the door opens in the escape direction and is never kept locked.
Source: BYKHY 4(1)(tt), 24(7), 47(2), Annex 4
2 / 2 · Sports hall exit doorThe camera is in the school yard; the fire is in the sports hall.
- DirectionThe door opens outwards, in the escape direction; it opens by hand.
- Number3 m² per person in a sports hall; two exits in a hall larger than 150 m².
- LightingEmergency lighting is required in education buildings.
Source: BYKHY 39(2), 47(2), 72(2)(a), Annex 5/A
03 School floor
How are doors arranged on a school floor?
School floor plan: corridor, classrooms, a large classroom, a sports hall and two escape stairs. Choose a rule; its counterpart on the plan turns orange.
1.5 m² per person in a classroom
For escape calculations, classrooms, computer rooms and seminar rooms are counted at 1.5 m² per person. A classroom larger than 75 m² therefore holds more than 50 people.
ExampleThe large classroom on the plan is 148 m²: counted as 99 people.
Source: BYKHY 32(1), Annex 5/A
Two doors far apart in a classroom with more than 50 people
Every room with more than 50 occupants has at least two exits. In a single undivided room, the distance between the two exits cannot be less than half the diagonal without sprinklers, or a third of it with sprinklers.
ExampleOn the plan, the large classroom's doors are at opposite ends of the room.
Source: BYKHY 39(2), 39(3)
A crowded classroom's door opens in the escape direction
The exit door of a room with an occupant load above 50 opens in the escape direction, that is, towards the corridor. The door opens by hand and is never kept locked.
ExampleOn the plan, both doors of the large classroom open onto the corridor; those of the small classrooms open inwards.
Source: BYKHY 47(2)
Compartment at most 6,000 m² in an education building
In education facilities a fire compartment is at most 6,000 m²; if suitable fire control systems are installed, the area limit is lifted. The door cutting across the corridor carries the line's rating.
ExampleOn the plan, the line cutting the corridor west of the sports hall.
Source: BYKHY Annex 4, 24(7)
At most 45 m in two directions in a school
In school and education buildings the travel distance is 45 m in two directions (75 m with sprinklers) and 15 m in one direction (30 m with sprinklers); a dead-end corridor is at most 15 m, or 20 m with sprinklers.
ExampleOn the plan, the route from the corner of the eastern classroom to the eastern stair.
Source: BYKHY Annex 5/B
3 m² per person in a sports hall
Multi-purpose sports facilities are counted at 3 m² per person; a hall larger than 150 m² holds more than 50 people and needs at least two exits. If the occupant count exceeds 500, three exits are needed.
ExampleOn the plan, the sports hall's two outward-opening exits and its door to the corridor.
Source: BYKHY Annex 5/A, 39(2)
04 Four locations
Where are fire doors used in a school?
Four situations in education buildings; choose a location and the requirements for its door are marked alongside.
Fire side
Escape side
- In the classroom corridor A long school corridor is divided by a compartment line; the door cutting the line and the glass above it carry the line's rating. BYKHY 24(7), Annex 460 Fire compartment page
- At the sports hall entrance A sports hall is counted at 3 m² per person; in a hall larger than 150 m² the doors open in the escape direction and there are at least two exits. BYKHY 39(2), 47(2), Annex 5/A3 m² / person Emergency exit door page
- At the escape stair entrance The door to the school's escape stair is self-closing and the article requires it to be smoke-tight. If the stair serves a basement or more than 4 storeys, the door resists fire for at least 90 minutes; if it serves fewer, 60 minutes. BYKHY 47(3)6090 Fire escape stair door page
- In nurseries Nurseries are also education facilities. If an existing building is converted into a nursery, the special provisions for existing buildings do not apply. BYKHY 11(1)(a), 138(1)60
05 Your project
Which fire doors does your school need?
These four answers determine the classroom, hall and corridor doors.
- 01
How many m² are the classrooms?
A classroom larger than 75 m² holds more than 50 people; two doors opening in the escape direction are needed.
- 02
Is there a sports or conference hall?
3 m² per person in a sports hall, 1.5 m² in a conference hall; the number of exits follows from this.
- 03
What is the total floor area?
Compartment at most 6,000 m² in an education building; the limit is lifted with suitable fire control systems.
- 04
Is the building new or being converted?
In an existing building converted into a school or nursery, the existing-building allowances do not apply.
Let's count your school's corridor and hall doors together. Send your floor plans and room areas; our technical team will review them.
Send the project06 Glazed door
Can a school fire door be glazed?
The compartment door cutting the corridor and the stair and sports hall doors are made with Aliplast profiles and Polflam glass.
Corridor line
Double leaf
Double-leaf glazed door cutting a school corridor. Double leaf
Stair entrance
Single leaf
Floor door of the escape stair. Single leaf
Above the door
Fixed glass partition
Glass closing the corridor line above the door up to the ceiling. Fixed partition
On a stair door the article also requires smoke tightness; this is documented together with the door's size. Fire escape stair door
Abay Yapı Sistemleri
Trusted for 30 years.
We make corridor, stair and sports hall doors for schools with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul


- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Corridor and hall doors from our reference projects.
Top row: our double-leaf doors cutting corridors; bottom row: single-leaf doors at stair and hall entrances. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for fire doors in a school?
The corridor door meets the line's rating, the stair door the 60- or 90-minute rating; the rating and opening direction are documented at handover.
Four checks at handover
- Rating. The corridor door's reported rating must not be shorter than the line's rating.
- Smoke. The stair door's report must state its smoke-tightness class.
- Direction. The door of a room with more than 50 people must open in the escape direction.
- Width. The clear opening of the leaves must cover the width derived from the room's occupant count.
- ClassificationClassification report for the corridor doorWith number of leaves and sizeRequest it
- ClassificationClassification report for the stair doorWith rating and smoke classRequest it
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingDoor, glass and ceiling junction detailsDWGRequest it
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for school doors. Documents are prepared separately for corridor, stair and hall doors.
Request the document set08 FAQ
About school fire doors
In a school, classroom doors, compartment lines and hall exits are finalised in the design and the fire brigade approval. Send your floor plans; let's decide the doors' direction and class together.
How many minutes of fire resistance should a school fire door have?
The compartment line dividing the corridor and its door resist fire for at least 60 minutes. The escape stair door is smoke-tight; it resists fire for 90 minutes if the stair serves a basement or more than 4 storeys, and 60 minutes if it serves fewer.
Source: BYKHY 4(1)(tt), 24(7), 47(3)
How many doors should a classroom have?
Classrooms are counted at 1.5 m² per person. A classroom up to 75 m² counts as at most 50 people and one door is enough; a larger classroom has at least two doors far apart.
Source: BYKHY Annex 5/A, 39(2)
Which way should a classroom door open?
The door of a classroom with more than 50 occupants opens towards the corridor, that is, in the escape direction. In a classroom for up to 50 people the door may open inwards; an escape route door is never kept locked under any circumstances.
Source: BYKHY 47(2)
What is the maximum compartment area in a school?
In education facilities a fire compartment is at most 6,000 m². If suitable systems such as detection, sprinklers and smoke extraction are installed, there is no area limit.
Source: BYKHY Annex 4
Is emergency lighting mandatory in a school?
Yes. Emergency lighting is required in education buildings; it switches on automatically when normal lighting fails and lights the escape routes.
Source: BYKHY 72(1), 72(2)(a)
How many exits should a sports hall have?
Multi-purpose sports facilities are counted at 3 m² per person. A hall larger than 150 m² needs at least two exits, and one larger than 1,500 m² at least three.
Source: BYKHY Annex 5/A, 39(2)
What is required to convert a building into a nursery or school?
If an existing building is to be used as a nursery or primary school, the regulation's special provisions for existing buildings do not apply; the general provisions are the basis.
Source: BYKHY 138(1)