C12Fire criteria · building type

School fire door

In a school, fire doors sit on the compartment line dividing the corridor, at the entrance to the escape stair and at the sports hall exits. A classroom is counted at 1.5 m² per person; a classroom larger than 75 m² holds more than 50 people, has two doors, and the doors open in the escape direction. In an education building, a compartment is at most 6,000 m² unless a fire control system is installed.

School fire doors Turkey – glass partition closing a corridor with lockers
Compartment door in a school corridor
Occupant count in a classroom
1.5 m² per person
Classroom with more than 50 people
Two doors, opening in the escape direction
Occupant count in a sports hall
3 m² per person
Compartment area in education
At most 6,000 m²
Travel distance (without sprinklers)
One direction 15 m · two directions 45 m

01 Number of doors

How many doors should your classroom have?

Enter the room's area and choose its type; the plan shows the number of doors and the direction the leaf opens.

2Room

2doorsminimum · this room

90 m² classroom at 1.5 m² per person: 60 people. At least 2 exits, far apart; the doors open in the escape direction. Total exit width at least 80 cm; each exit provides at least half of it.

  • Opens in the escape directionAbove 50 occupants
  • Doors far apartAt least half the diagonal
  • Each door halfOf the total width
  • Emergency lightingRequired in education buildings

Source: BYKHY 33(1), 33(4), 39(2), 39(3), 47(2), 72(2)(a), Annex 5/A, Annex 5/B

–corridorROOM PLAN · diagram
Door opening in the escape directionWall

02 What the door needs

What is checked on school doors?

First the compartment door dividing the corridor, then the sports hall exit to the yard; tap a tab to fix the view.

School fire doors Turkey – corridor compartment crossing

1 / 2 · Compartment door in the corridorThe other half of the corridor is on fire; this side is clear.

Door≥ 60 minArea≤ 6,000 m²

  1. DoorThe door cutting across the corridor carries the compartment line's rating of at least 60 minutes.
  2. Upper glassThe glass above the door, up to the ceiling, is part of the line; no opening is left in the line.
  3. DirectionAt the exit from a crowded area the door opens in the escape direction and is never kept locked.

Source: BYKHY 4(1)(tt), 24(7), 47(2), Annex 4

03 School floor

How are doors arranged on a school floor?

School floor plan: corridor, classrooms, a large classroom, a sports hall and two escape stairs. Choose a rule; its counterpart on the plan turns orange.

1.5 m² per person in a classroom

For escape calculations, classrooms, computer rooms and seminar rooms are counted at 1.5 m² per person. A classroom larger than 75 m² therefore holds more than 50 people.

ExampleThe large classroom on the plan is 148 m²: counted as 99 people.

Source: BYKHY 32(1), Annex 5/A

stairstairsports hallstaff room · storageSCHOOL FLOOR PLAN · 1/500K0 – 10 m148 m² · 99 people123456
WallEscape stairEscape route

04 Four locations

Where are fire doors used in a school?

Four situations in education buildings; choose a location and the requirements for its door are marked alongside.

05 Your project

Which fire doors does your school need?

These four answers determine the classroom, hall and corridor doors.

  1. 01

    How many m² are the classrooms?

    A classroom larger than 75 m² holds more than 50 people; two doors opening in the escape direction are needed.

  2. 02

    Is there a sports or conference hall?

    3 m² per person in a sports hall, 1.5 m² in a conference hall; the number of exits follows from this.

  3. 03

    What is the total floor area?

    Compartment at most 6,000 m² in an education building; the limit is lifted with suitable fire control systems.

  4. 04

    Is the building new or being converted?

    In an existing building converted into a school or nursery, the existing-building allowances do not apply.

Let's count your school's corridor and hall doors together. Send your floor plans and room areas; our technical team will review them.

Send the project

06 Glazed door

Can a school fire door be glazed?

The compartment door cutting the corridor and the stair and sports hall doors are made with Aliplast profiles and Polflam glass.

  1. Corridor line

    Double leaf

    Double-leaf glazed door cutting a school corridor. Double leaf

  2. Stair entrance

    Single leaf

    Floor door of the escape stair. Single leaf

  3. Above the door

    Fixed glass partition

    Glass closing the corridor line above the door up to the ceiling. Fixed partition

On a stair door the article also requires smoke tightness; this is documented together with the door's size. Fire escape stair door

Abay Yapı Sistemleri

Trusted for 30 years.

We make corridor, stair and sports hall doors for schools with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
School fire door project Turkey – double leaf held open in a lift lobbySchool fire door project Turkey – double leaf with panic bars, side and top lights
Lift lobby · Double leaf · top light
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Corridor and hall doors from our reference projects.

Top row: our double-leaf doors cutting corridors; bottom row: single-leaf doors at stair and hall entrances. Tap a photo; browse with the arrows.

07 Document set

Which documents are required for fire doors in a school?

The corridor door meets the line's rating, the stair door the 60- or 90-minute rating; the rating and opening direction are documented at handover.

Four checks at handover

  1. Rating. The corridor door's reported rating must not be shorter than the line's rating.
  2. Smoke. The stair door's report must state its smoke-tightness class.
  3. Direction. The door of a room with more than 50 people must open in the escape direction.
  4. Width. The clear opening of the leaves must cover the width derived from the room's occupant count.
  • ClassificationClassification report for the corridor doorWith number of leaves and sizeRequest it
  • ClassificationClassification report for the stair doorWith rating and smoke classRequest it
  • DeclarationDeclaration of performanceCE markedRequest it
  • DrawingDoor, glass and ceiling junction detailsDWGRequest it

Source: Turkish Construction Products Regulation 6(1), 10(2)

Request the document set for school doors. Documents are prepared separately for corridor, stair and hall doors.

Request the document set

08 FAQ

About school fire doors

In a school, classroom doors, compartment lines and hall exits are finalised in the design and the fire brigade approval. Send your floor plans; let's decide the doors' direction and class together.

0216 428 38 20Send a question

How many minutes of fire resistance should a school fire door have?

The compartment line dividing the corridor and its door resist fire for at least 60 minutes. The escape stair door is smoke-tight; it resists fire for 90 minutes if the stair serves a basement or more than 4 storeys, and 60 minutes if it serves fewer.

Source: BYKHY 4(1)(tt), 24(7), 47(3)

How many doors should a classroom have?

Classrooms are counted at 1.5 m² per person. A classroom up to 75 m² counts as at most 50 people and one door is enough; a larger classroom has at least two doors far apart.

Source: BYKHY Annex 5/A, 39(2)

Which way should a classroom door open?

The door of a classroom with more than 50 occupants opens towards the corridor, that is, in the escape direction. In a classroom for up to 50 people the door may open inwards; an escape route door is never kept locked under any circumstances.

Source: BYKHY 47(2)

What is the maximum compartment area in a school?

In education facilities a fire compartment is at most 6,000 m². If suitable systems such as detection, sprinklers and smoke extraction are installed, there is no area limit.

Source: BYKHY Annex 4

Is emergency lighting mandatory in a school?

Yes. Emergency lighting is required in education buildings; it switches on automatically when normal lighting fails and lights the escape routes.

Source: BYKHY 72(1), 72(2)(a)

How many exits should a sports hall have?

Multi-purpose sports facilities are counted at 3 m² per person. A hall larger than 150 m² needs at least two exits, and one larger than 1,500 m² at least three.

Source: BYKHY Annex 5/A, 39(2)

What is required to convert a building into a nursery or school?

If an existing building is to be used as a nursery or primary school, the regulation's special provisions for existing buildings do not apply; the general provisions are the basis.

Source: BYKHY 138(1)