02Partition type · one of 3 types

Frameless glass partition: 30 to 120 minutes

A frameless glass partition joins fire-resistant panes at their edges, with no vertical profile between them, to form an uninterrupted glass wall. It is made with Polflam BR glass in 30, 60, 90 and 120-minute classes; the result of a two-hour test of BR EI120 combined with Aliplast FR90 has been published. Height and pane size are set by the scope of the documents for the class.

Partition ratingEI30 – EI120
0306090120 min
Frameless glass partition Turkey – butt-jointed glass along a corridor
Frameless partitionExample view
Glass
Polflam BR
Class
EI30 – EI120
Glass thickness
30–50 mm
Weight
65–90 kg/m²
Test
BR EI120 + FR90: 120 minutes

01 Difference

How does it differ from a framed partition?

Picture the same wall in two ways. Choose: should there be vertical profiles between the panes?

Framed partition. The panes are divided by vertical and horizontal aluminium profiles; the profile holds the panes side by side. Framed fixed partition

Frameless partition. The vertical edges of the panes are joined without a mullion between them; the profile stays only at the bottom and top of the partition, and the wall looks like a single glass surface.

The diagram is not to scale; the glass layout is set on the project.

02 Components

What parts make up a frameless partition?

Three views change automatically; the line on the tab shows the transition. Tap a view to stay on it; the numbers open the parts.

Frameless fire-rated glass partition Turkey – fire side and safe corridor

1 / 3 · During a fireA fully developed fire on one side, a calm corridor on the other: the fire-resistant glass makes the difference.

RatingUp to 120 minENo flame passesIProtects from heatGlassHydrogel interlayer

  1. Polflam BR fire-resistant glassFire-resistant glass with a clear hydrogel interlayer; class EI30–EI120.
  2. Glass-to-glass jointThe vertical edges of the panes are joined without a mullion between them; the joint is also part of the tested system.
  3. Bottom channelThe glass sits in a slim aluminium channel at the bottom.

03 Classes

How many minutes does a frameless partition resist fire?

Polflam BR glass is made in four classes; as the duration increases, the glass becomes thicker and heavier. The required duration depends on the wall's role; details in the duration by wall section.

  1. EI30
    Glass thickness
    30 mm
    Weight
    65 kg/m²
  2. EI60
    Glass thickness
    35 / 38 mm
    Weight
    69 / 75 kg/m²
  3. EI90
    Glass thickness
    45 mm
    Weight
    82 kg/m²
  4. EI120
    Glass thickness
    50 mm
    Weight
    90 kg/m²

120 minutes: BR EI120 and Aliplast FR90 were tested together; the result of the two-hour test has been published.

Abay Yapı Sistemleri

Trusted for 30 years.

We prepare frameless glass partitions with Polflam BR glass in our Istanbul workshop, to each project's dimensions.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Frameless glass partition project Turkey – door and glass partition in a lift lobbyFrameless glass partition project Turkey – glass partition between stair lobby and officeFrameless glass partition project Turkey – black-framed door and glass partition in a corridor
Lift lobby · Door and glass partition
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Glass partitions and doors on the same line in our reference projects.

Above, our glass partition projects; below, doors planned together with the partition. Tap a photo, use the arrows to browse.

04 BR or FR?

Which Polflam glass is used?

There are two separate product families for frameless partitions. One cannot simply be used in place of the other; whichever has the documents for the project is used.

  1. BR

    Glass-to-glass joint

    The vertical edges of the panes are joined without a mullion between them. Covers classes EI30, EI60, EI90 and EI120; thickness 30–50 mm.

  2. FR

    Directly into the wall opening

    A separate product family in which the glass is fitted directly into the wall opening. EI120 FR glass is 35 mm thick.

05 Where it is used

Where are frameless glass partitions used?

Where the Turkish Fire Regulation (BYKHY) requires a 60 or 120-minute wall and uninterrupted visibility is also needed. In the scenes the fire always stays behind the glass.

Frameless glass partition Turkey – fire safety lobby wall Frameless fire-rated glass partition Turkey – basement stair separation Frameless glass partition Turkey – hospital ward floor and double leaf Frameless glass partition Turkey – open-plan office compartment Fire side Safe side
EIFire-rated60–120 min depending on location · BYKHY 34(2), 48(7), 4(1)(tt)
HContinuous along the lineNo unrated openings · BYKHY 24(7)
KIts door is smoke-tightAt least 90 min · BYKHY 34(2)
Fire safety lobbyRequired here
  1. Fire safety lobby A fire safety lobby is separated from other parts of the building by a wall with at least 120 minutes' resistance and a smoke-tight door with at least 90 minutes' resistance. Frameless glass makes this wall uninterrupted and transparent; in the scene the floor is burning while the lobby is empty and clear. BYKHY 34(2)120 Fire safety lobby page
  2. Basement separation in housing In residential buildings, a basement separated from the upper floors, together with its entrance, exit and shafts, by a floor or partition with 120 minutes' resistance is not counted in the building heights in 48(5) and is assessed separately. In the scene the basement fire stays behind the glass. BYKHY 48(7)120 EI120 · 120 minutes page
  3. Hospital ward floor In-patient floors larger than 300 m² are divided into two or more compartments, each at least half the floor's size, or a protected horizontal evacuation area is provided; no unrated opening is left between compartments. BYKHY 49(1)(b), 24(7)Compartment line Hospital page
  4. Compartment on an office floor Elements separating a compartment, including ceiling and floor, resist for at least 60 minutes; no unrated opening is left between them. In the scene the fire is just starting, on the other side of the glass. BYKHY 4(1)(tt), 24(7)60 Fire compartment page

06 Document set

Which documents should you ask for with a frameless partition?

The class of a glass-to-glass joint is shown by the test of the partition that includes the joint; the glass declaration alone is not enough.

Four checks in a quote

  1. The partition's test. The class is shown by the glass-to-glass partition's own test; the glass declaration does not replace it.
  2. Pane size. The glass pane on the project must not be larger than the pane tested in the report.
  3. Same glass. The Polflam BR glass used in the test is also used on the project; its label and the etched stamp in its corner are checked.
  4. Authorisation. Ask for the manufacturing authorisation the partition manufacturer has received from the system owner.
  • Test resultBR EI120 + Aliplast FR90Frameless partition, 120 minutesRequest it
  • Glass declarationPolflam BR glassEI30–EI120 · does not replace the partition reportRequest it
  • AuthorisationAliplast manufacturing authorisationAuthorised manufacturer and distributor in TurkeyRequest it
  • DrawingFrameless partition sectionsDWGRequest it

Request the frameless partition's document set. The test result and manufacturing authorisation are shared with company and project details.

Request the document set

07 FAQ

About frameless glass partitions

If your question is not here, ask our technical team.

0216 428 38 20Send a question

How many minutes does a frameless glass partition resist fire?

30, 60, 90 or 120 minutes with Polflam BR glass. The result of a two-hour test in which BR EI120 glass and the Aliplast FR90 profile were tested together has been published. The required duration depends on the wall the partition sits in; for example, the wall of a fire safety lobby resists for at least 120 minutes.

Source: BYKHY 34(2)

How does the partition resist fire without profiles between the panes?

The vertical edges of the panes are joined with no mullion between them, and this joint is part of the system tested together with the glass. The partition's class is shown not by the glass declaration alone but by the test of the partition that includes the joint.

How tall can a frameless partition be?

Height and pane sizes are set by the scope of the documents for the chosen class. Send us the partition's size and the required duration, and we will answer according to the report's field of application.

What is the difference between BR and FR glass?

BR panes are joined at their vertical edges with no mullion between them. FR is a separate product family in which the glass is fitted directly into the wall opening; EI120 FR glass is 35 mm thick. One cannot simply be used in place of the other.

How heavy is a frameless glass partition?

The weight per square metre of BR glass rises with the class: EI30 65 kg, EI60 69 or 75 kg, EI90 82 kg, EI120 90 kg.

What determines the price of a frameless glass partition?

The partition's length and height, the required duration (the glass thickness and weight depend on it), the number of panes, whether the partition contains a door, and installation conditions. Send us the size and location of the partition, and we will prepare a quote within the scope of the report.

→ Quote

Tell us the frameless partition's size.

Our technical team will determine the glass class, pane layout and document set and get back to you. If you have a plan or elevation drawing, send it by email.

Call · 0216 428 38 20Email

Production
Istanbul

Quote form* required field

CallRequest a quote