C7Fire criteria · location
Fire wall door
A fire wall is a vertical element separating two buildings, or parts of the same building with different fire loads. A fire wall separating adjoining buildings is rated for at least 90 minutes. If a door or fixed vision panel in the wall cannot be avoided, it is rated for at least half the wall's rating; the door is self-closing and smoke-tight.
- Wall between adjoining buildings
- At least 90 minutes
- Door and fixed glazing in the wall
- At least half the wall's rating
- Door in a 90-minute wall
- At least 45 minutes
- Door closing
- Self-closing, smoke-tight
- Services penetration
- Sealed for the wall's rating
01 Door rating
How many minutes must a door in a fire wall resist fire?
The wall's rating sets the rating of the door and fixed glazing: at least half. Choose your wall's fire resistance; the ratings in the section change.
1Wall fire resistance
45minutesminimum · door and fixed glazing
In a 90-minute wall separating adjoining buildings, the door and fixed vision panel are rated for at least 45 minutes.
The door is self-closing and smoke-tight; the area around the opening is kept clear of combustible materials.
- Nearest classEI60 · Aliplast FR65 or FR90
Source: BYKHY 25(1), 25(2)
02 What the door needs
What should you check in a fire wall door?
First the door in the wall, then the fixed glazing and the services passing through the wall; tapping a tab locks the view.
1 / 2 · Door in the wallThere is a fire in the neighbouring building; the door is closed and this side is clear.
- DoorAt least half the wall's rating: 45 minutes in a 90-minute wall.
- Door closerThe door is self-closing and smoke-tight.
- SurroundingsThe area around the opening is kept clear of all combustible materials.
Source: BYKHY 25(1), 25(2)
2 / 2 · Fixed glazing and servicesThe fixed vision panel in the wall and the pipe passing through it.
- Fixed glazingThe fixed vision panel is also rated for at least half the wall's rating.
- ServicesThe gap around the pipe is sealed, with no opening left, for the wall's rating.
- WallThere are no other holes or voids in the fire wall.
Source: BYKHY 25(2)
03 Rules for the wall
How is a fire wall built in a building?
Section through two adjoining buildings: the wall between them, the floor slabs, the façade level with the lower roof, and the roofs. Choose one of the rules; its location appears in the section.
At least 90 minutes between adjoining buildings
Fire walls separating adjoining (terraced) buildings are rated for at least 90 minutes. Every wall separating semi-detached houses is a fire wall, and the houses count as separate buildings.
ExampleIn the section, the wall separating buildings A and B runs uninterrupted from the basement floor to A's roof.
Source: BYKHY 25(1), 24(3)
Door and fixed glazing at least half the wall's rating
There are no holes or voids in a fire wall. If a door or fixed vision panel cannot be avoided, it is rated for at least half the wall's rating; the door is self-closing and smoke-tight.
ExampleIn the section, the ground-floor door and the fixed glazing on the 1st floor in the 90-minute wall are rated for at least 45 minutes.
Source: BYKHY 25(2)
Services penetrations sealed for the wall's rating
If services such as water, electricity, heating or ventilation pass through the wall, the gap around them is sealed, with no opening left, for the wall's fire resistance rating. The area around doors and windows is kept clear of combustible materials.
ExampleIn the section, the pipe penetration at 2nd-floor level is sealed for 90 minutes; the area in front of the door is clear.
Source: BYKHY 25(2)
All floor slabs have the quality of a fire wall
All floor slabs in the building have the quality of a fire wall; their fire resistance ratings are given in Annex 3/B.
ExampleIn the section, the floor slabs of both buildings.
Source: BYKHY 26(1)
The façade level with the lower roof is non-combustible
In adjoining buildings of different heights, the external façade cladding of the taller building's storey level with the lower building's roof is made with non-combustible material or systems.
ExampleIn the section, the east façade of A above B's roof.
Source: BYKHY 27(2)(c)
Roof as a fire barrier in adjoining buildings
In adjoining (terraced) buildings, the slab the roof sits on acts as a horizontal fire barrier; the roof structure and covering are made of non-combustible material.
ExampleIn the section, the roof slabs of buildings A and B.
Source: BYKHY 28(3)
04 Four locations
Where is a door in a fire wall most common?
Four situations in adjoining buildings and in different parts of the same building; choose a location and the door's requirements are marked alongside.
Fire side
Safe side
- Between two adjoining business premises The wall separating two adjoining (terraced) shops is a fire wall and is rated for at least 90 minutes. The connecting door between them is rated for at least 45 minutes. BYKHY 25(1), 25(2)45
- Between storage and production in the same building A fire wall also separates parts of the same building with different fire loads, such as a warehouse full of combustible material and a production hall. The door in the wall is rated for half the wall's rating. BYKHY 4(1)(rr), 25(2)½ Factory and warehouse page
- In the shared basement of adjoining buildings Walls shared by two or more buildings are built fire-rated and have the quality of compartment walls. The connecting door in the basement is self-closing and smoke-tight. BYKHY 24(2), 24(3), 25(2)45
- In a link passage to an adjoining building A passage connecting two buildings is closed off by a door where the fire wall is. The door is self-closing; there is no combustible material around it. BYKHY 25(2)½
05 Your project
Which door does your fire wall need?
These four answers set the door's rating and type.
- 01
Are the buildings adjoining (terraced)?
The wall separating adjoining buildings is a fire wall and is rated for at least 90 minutes.
- 02
How many minutes is the wall rated for?
The rating of the door and fixed glazing in the wall is at least half of this.
- 03
Does the wall need a door or glass?
If an opening cannot be avoided, the door is self-closing and smoke-tight.
- 04
Do services pass through the wall?
The gap around the penetration is sealed, with no opening left, for the wall's rating.
Let us specify the openings in your fire wall together. Send the section and the wall's rating; our technical team will review them.
Send the project06 Glazed door
Can a fire wall have a glazed door?
The door and fixed vision panel are made with Aliplast profiles and Polflam glass to half the wall's rating.
90 min wall
EI60 door
The nearest class meeting 45 minutes; single or double leaf. Aliplast FR65
Wide opening
With side lights
Fixed glazing beside the door; both with the same rating. With side lights
180 min wall
EI90 door
Half the wall is 90 minutes: FR90 door, up to EI120 in glazing. Aliplast FR90
Smoke-tightness of the door in a fire wall is a requirement of the article; this property is shown with certification for the door's number of leaves and size. Fire-rated glass
Abay Yapı Sistemleri
Trusted for 30 years.
We make fire wall doors and fixed glazing with Aliplast profiles and Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul




- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Single-leaf and side-light doors from our reference projects.
Top row: our single-leaf and side-light doors; bottom row: double-leaf passage doors. Tap a photo; browse with the arrows.
07 Document set
Which documents are required for a door in a fire wall?
The door and fixed glazing prove half the wall's rating, and the door also proves smoke-tightness, with certification.
Four checks at handover
- Half the rating. The minutes in the door's and fixed glazing's reports are at least half the wall's rating.
- Smoke. The door's report includes a smoke-tightness class.
- Closing. The door closer is the same as the hardware the door was tested with.
- Penetrations. The sealing of services passing through the wall meets the wall's rating.
- ClassificationDoor classification reportWith number of leaves and sizeRequest
- ClassificationFixed glazing classification reportWith glass sizeRequest
- DeclarationDeclaration of performanceCE markedRequest it
- DrawingDoor to fire wall junction detailDWGRequest
Source: Turkish Construction Products Regulation 6(1), 10(2)
Request the document set for the fire wall door. Documents are sent together with the door and glass dimensions.
Request the document set08 FAQ
About fire wall doors
The fire wall's rating and openings are set by the project architect, the fire consultant and fire brigade approval. The rules are here; let us choose the door and glass for your wall together.
What is a fire wall?
A vertical element between two buildings, or between parts of the same building with different fire loads, that stops the advance and spread of fire for a set time.
Source: BYKHY 4(1)(rr)
How many minutes must a fire wall resist fire?
Fire walls separating adjoining (terraced) buildings from each other are designed to be rated for at least 90 minutes.
Source: BYKHY 25(1)
Can a door be fitted in a fire wall?
There are no holes or voids in a fire wall. If a door or fixed vision panel cannot be avoided, it is rated for at least half the wall's rating; the door is self-closing and smoke-tight.
Source: BYKHY 25(2)
How many minutes should a door in a fire wall resist?
At least half the wall's fire resistance rating. In a 90-minute wall separating adjoining buildings the door is rated for at least 45 minutes, in a 120-minute wall at least 60 minutes.
Source: BYKHY 25(1), 25(2)
Can services pass through a fire wall?
Services such as water, electricity, heating and ventilation can pass through; the gap around them is sealed against fire and smoke, with no opening left, for at least the wall's fire resistance rating.
Source: BYKHY 25(2)
Is the wall between semi-detached houses a fire wall?
Yes. Every wall separating semi-detached houses is built as a fire wall, and the houses are treated as separate buildings. Walls shared by two or more buildings are built fire-rated.
Source: BYKHY 24(3)
What should the roof and façade be like in adjoining buildings?
In adjoining buildings the slab the roof sits on is a horizontal fire barrier; the roof structure and covering are non-combustible. In adjoining buildings of different heights, the taller building's façade level with the lower building's roof is clad with non-combustible material.
Source: BYKHY 28(3), 27(2)(c)