KFire criteria · duration
Fire door resistance ratings
The number in a fire door's class is the number of minutes the door withstood fire under test conditions; the letters state the type of protection: E integrity, EW integrity and radiation limit, EI integrity and insulation. The door's location decides which rating is needed: room door, compartment, stair, lobby or shaft.
- Ratings
- 30 · 60 · 90 · 120 minutes
- Class type
- E · EW · EI
- Door
- Up to EI90
- Partition
- Up to EI120
01 Which rating where
Which fire resistance rating is required where?
Four ratings and their typical locations in the regulation; each has its own detailed page.
EI30 · 30 minutes
Hotel room door
In a hotel, a room door opening onto an internal corridor is rated for at least 30 minutes and is self-closing (50(1)(b)). EI30 page
EI60 · 60 minutes
Compartment and stair
Compartment boundary at least 60 minutes (4(1)(tt)); the door of a stair serving fewer than 4 storeys at least 60 minutes (47(3)). EI60 page
EI90 · 90 minutes
Lobby and tall stair
Fire safety lobby door at least 90 minutes (34(2)); the door of a stair serving a basement or more than 4 storeys at least 90 minutes (47(3)). EI90 page
EI120 · 120 minutes
Lobby wall and shaft
Fire safety lobby wall at least 120 minutes (34(2)); in a high-rise building, the services shaft wall at least 120 minutes (25(3)). EI120 page
02 E, EW, EI
What do the E, EW and EI classes mean?
The letter states the type of protection, the number the minutes.
| Class | What it provides | Note |
|---|---|---|
| E | Integrity: against the passage of flames and hot gases | No thermal insulation |
| EW | Integrity and limiting heat radiation: the glass does not break in a fire and no flame or smoke passes; part of the heat reaches the other side | Not a thermal insulation class · we also make EW30, EW60, EW90, EW120 |
| EI | Integrity and insulation: the glass does not break in a fire, and the temperature rise on the unexposed face is limited | EI30, EI60, EI90, EI120 |
Glass layers and classes: Fire-rated glass
03 Systems
Up to how many minutes do Abay systems resist fire?
Doors and partitions made with Aliplast profiles and Polflam glass.
| Product | Aliplast FR65 | Aliplast FR90 |
|---|---|---|
| Door | EI30, EI60 | EI30, EI60, EI90 |
| Fixed partition | EI30, EI60 | EI30, EI60, EI90, EI120 |
| Location of use | Interior | Interior and exterior |
04 FAQ
About fire resistance ratings
The rating follows from the door's location and the building. Send us the plan and the door's location; we will set the rating and its certification together.
What does EI60 mean?
EI60 is the class showing that a door or partition kept both its integrity (E) and its insulation (I) for 60 minutes under test conditions. The number states the minutes, the letters the type of protection.
How many minutes must a fire door resist fire?
The rating depends on the door's location: a hotel room door at least 30, a compartment boundary at least 60, a fire safety lobby door at least 90 minutes.
Source: BYKHY 50(1)(b), 4(1)(tt), 34(2)
Is smoke-tightness part of the fire resistance rating?
No, it is assessed separately. For stair and lobby doors the regulation requires smoke-tightness in addition to the fire resistance rating.
Source: BYKHY 47(3)
Where are 120 minutes required?
The fire safety lobby wall and, in a high-rise building, the services shaft wall are rated for at least 120 minutes. Aliplast FR90 fixed glazed partitions are made up to EI120.
Source: BYKHY 34(2), 25(3)
→ Quote
Let us set your door's rating together.
Door location, number of storeys and use: let us set the rating together.
- Phone
- +90 216 428 38 20
- abay@abayyapi.com
- Production
- Istanbul