02Door type · one of 4 types

Double-leaf glazed fire door

A double-leaf fire door is used for wide openings where a single leaf is not enough. The regulation allows a single-leaf door an opening (clear opening width) of no more than 120 cm; where more than 500 people are on a floor, the escape route must be at least 150 cm, a width only two leaves can provide. We make the glazed version with Aliplast profiles and Polflam glass up to 3.17 × 2.87 m.

Fire resistance60 min
0306090120 min
Double-leaf glazed fire door Turkey – with side lights in a floor lobby Panic bar on each leafOpens without a handle · BYKHY 47(5) Meeting stileWhere the leaves meet DaylightFrom the stair window into the lobby
Floor lobby · Abay installation
Maximum size
3.17 m wide × 2.87 m high
Fire resistance
60 minutes (EI60 report)
Profile
Aliplast FR65 · FR90
Glass
Polflam fire-resistant glass, 20–32 mm
When it is needed
When the opening exceeds 120 cm · floors with more than 500 people

01 When double leaf

When is a double-leaf door required?

An escape door's opening is at least 80 cm, and on a single-leaf door it cannot exceed 120 cm (47(1), 47(4)). The number of people on the floor sets the opening required. Choose a row or drag the slider.

Opening required by the regulation · number of people on the floor and high-rise building

The door is part of the escape route; its width is measured the same way, with the door fully open (33(5)). The regulation does not require double leaves directly by building type or height; what decides is the number of people on the floor and the opening required.

140 cm
Plan view · leaves fully open

Double leaf

A single-leaf exit door cannot be wider than 120 cm.

BYKHY 47(4)

02 Components

What parts make up a double-leaf door?

How many minutes a door resists fire does not depend on a single part: the frame, glass, seals and hardware are tested together. Tap a number on the image.

Double-leaf glazed fire door parts Turkey – panic bar, door closer, meeting stile

  1. Frame and leafThe frame is the aluminium surround fixed to the wall; the leaf is the part that opens and closes. It is 65 mm deep in the FR65 system and 90 mm in the FR90 system.
  2. Fire-resistant glassPolflam glass: 20 mm thick for 30 minutes, 25 mm for 60 minutes, 32 mm for 90 minutes. It transmits 85–87% of light; both sides stay visible with the door closed.
  3. Meeting stile and sealWhere the two leaves meet when the door closes, and the seal between them. On escape stair and fire safety lobby doors the regulation requires that smoke does not pass through the door (smoke-tightness).BYKHY 47(3)
  4. Panic barA horizontal bar across the door; push it and the door opens without turning a lever handle. It is mandatory on doors leading out of the building and where more than 100 people are on a floor. The door cannot be kept locked.BYKHY 47(5), 47(2)
  5. Door closer on each leafThe mechanism at the top corner of the door closes it automatically when released. It is mandatory on escape stair and fire safety lobby doors. The door must open with no more than 110 N, roughly an 11 kg push.BYKHY 47(3), 47(6)

Panic bar, lock, door closer and colour are chosen from the options listed in the door's fire report.

03 Sizes

Double-leaf fire door sizes.

The drawing is to scale; the person beside it is 1.75 m tall. FR65 and FR90 are two separate profile systems; the last two tabs show the doors fire-tested.

Overall size, net opening and clear opening width differ even on the same door. The size that can be made for a project is set by the size of the door in the test. Fire door sizes

Abay Yapı Sistemleri

Trusted for 30 years.

We make double-leaf glazed fire doors with Aliplast profiles and Polflam glass in our Istanbul workshop, to each project's dimensions.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
Double-leaf glazed fire door project Turkey – double leaf with panic bars, side and top lightsDouble-leaf glazed fire door project Turkey – double leaf held open in a lift lobbyDouble-leaf glazed fire door project Turkey – stair front at a restaurant entranceDouble-leaf glazed fire door project Turkey – double leaf with side and top panelsDouble-leaf glazed fire door project Turkey – door and glass partition in a lift lobby
Lobby passage door · Double leaf · side and top lights
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Double-leaf and other installations from our reference projects.

Our double-leaf installations are in the top row, our other projects below. Tap a photo to enlarge it.

04 Fire resistance

What does “EI2 60-C0” on the document mean?

The short code written in the door's fire report. Each letter stands for a property; hover over or tap it.

-

E · Integrity
Flames and hot smoke do not pass through the door.
I · Insulation
The temperature rise on the escape-side surface of the door stays limited. The small figures 1 and 2 indicate two different heat measurement methods; both are 60 minutes in the report.
60 · Minutes
The time for which these two properties held in the test.
C · Self-closing
The door closes by itself with a door closer. The regulation requires this on escape stair and fire safety lobby doors.

Required fire resistance by location

Door locationRequired by the regulationArticle
Stair and lobby · new building, fewer than 4 storeys60 min · smoke-tight47(3)
Stair and lobby · basement or more than 4 storeys90 min · smoke-tight47(3)
Hotel corridor · smoke-stop partition60 min · smoke-tight50(6)(a)
Stair · existing building, lower than 30.50 m60 min · smoke-tight157(1)
Stair · existing building, 30.50 m and higher90 min · smoke-tight157(1)

"Lobby": the fire safety lobby in front of an escape stair. Where the regulation requires that smoke does not pass, the door's documents also carry the letter S. Source: official text of the BYKHY.

05 Where it is used

Where are double-leaf glazed fire doors used?

Double leaves in four locations: in each scene, see which side of the glass the fire stays on and what the regulation requires of the door there.

Double-leaf fire door Turkey – stair entrance Double-leaf fire door Turkey – exit from a busy office floor Double-leaf glazed fire door Turkey – hospital corridor Glazed double-leaf fire door Turkey – hotel smoke stop Fire side Escape side
EIFire-rated60–90 min depending on location · BYKHY 47(3)
SSmoke-tightBYKHY 47(3), 50(6)(a)
CSelf-closingBYKHY 47(3)
POpens without a handleOpens in the escape direction · BYKHY 47(5)
Fire escape stair entranceRequired at this location
  1. Fire escape stair entrance The floor's occupants pass into the stair through this door. The door is smoke-tight and self-closing; it is rated for at least 60 minutes if the stair serves fewer than 4 storeys, and at least 90 minutes if it serves a basement or more than 4 storeys. BYKHY 47(3)6090 Fire escape stair door page
  2. Busy floor exit Where more than 100 people are on a floor, escape stair, corridor and lobby doors open in the escape direction without a lever handle. In spaces for more than 50 people, the exit door opens in the direction of escape and is never kept locked. BYKHY 47(2), 47(5)Panic bar Emergency exit door page
  3. Hospital corridor Hospital corridors are at least 2 m wide, and ward floors larger than 300 m² are divided into fire compartments. A double-leaf glazed door between compartments provides fire separation while keeping both sides of the corridor visible. BYKHY 49(1)(b), 49(2)Compartment line Hospital page
  4. Hotel corridor smoke stop Unventilated internal hotel corridors are divided at intervals by smoke-stop doors. Escape doors in these partitions are rated for at least 60 minutes and smoke-tight; they may be single- or double-leaf, with a gap of no more than 4 mm between leaf and floor. A vision panel is required on a door that is not glazed. BYKHY 50(6)(a), (ç)60 Hotel page

06 Document set

Which documents should you ask for with a double-leaf door?

Each door type has its own fire report: a single leaf's report does not cover a double-leaf door. The door is delivered with a metal identification plate on its frame and the document set.

Double-leaf fire door label Turkey – metal plate on the frame Metal plateClass · system · serial no · glass
  • Fire reportFR90 double leaf · 60 minutesClassification report FIRES-CR-178-17-AUPERequest
  • Test reportFR90 double-leaf glazed doorITB 2020 · no flame through for 98 minutes, insulation 97 minutesRequest
  • AuthorisationAliplast manufacturing authorisationAbay's authorisation to manufacture this systemRequest
  • Glass documentPolflam 60-minute glass, 25 mmDeclaration of performance (DoP) · covers the glass only, not a substitute for the door's reportRequest
  • DrawingFR65 / FR90 double-leaf sectionsArchitectural drawing file (DWG)Request

Request the document set for your project. Documents are shared together with company and project details.

Request the document set

07 FAQ

About double-leaf fire doors

If your question is not here, ask our technical team.

0216 428 38 20Send a question

When is a double-leaf fire door required?

When the required opening exceeds 120 cm. The regulation keeps the clear opening width of a single-leaf exit door between 80 and 120 cm. The number of people on the floor sets the opening required: on a floor of 501–2000 people an escape route is at least 150 cm, and at 2001 and over at least 200 cm; these widths can only be achieved with two leaves.

Source: BYKHY 47(4), 33(1)

How is clear opening width measured on a double-leaf door?

The clear opening width is the distance between the leaf faces with both leaves open at 90 degrees. The door's overall size, glass size and clear opening are all different; the quote lists each of the three separately.

Source: BYKHY 47(4)

How long does a double-leaf glazed fire door resist fire?

There is a 60-minute fire report (EI60) for the Aliplast FR90 double-leaf door. In a 2020 test at ITB laboratory in Poland, the same system let no flame through for 98 minutes. The door's location decides how many minutes it must resist fire: in a new building, at least 60 for an escape stair serving fewer than 4 storeys, and at least 90 for one serving a basement or more than 4 storeys.

Source: BYKHY 47(3)

Is a panic bar mandatory on a double-leaf fire door?

It is mandatory on escape doors opening to a safe area at ground level and, where more than 100 people are on a floor, on the escape stair, corridor and lobby doors on that floor: the door opens in the escape direction without using a lever handle.

Source: BYKHY 47(5)

What is the maximum size of a double-leaf fire door?

The largest overall size is 3,170 × 2,870 mm for FR90 and 2,690 × 2,500 mm for FR65 (width × height). The size that can be used on a project is set by the field of application of the classification report.

What determines the price of a double-leaf fire door?

Size, the required duration (which sets the glass thickness), the system (FR65 or FR90), hardware (panic bars and door closers on both leaves), quantity and installation conditions. Share the size and the door's location and we will prepare a quote within the scope of the documents.

What determines the price

→ Quote

Share the size of your double-leaf door.

Our technical team will identify the system, class and document set and get back to you. If you have a project file, you can also send it by email.

Call · 0216 428 38 20Email

Production
Istanbul

Quote form* required field

CallRequest a quote