S90Fire criteria · duration
90-minute fire door
A 90-minute fire door keeps its integrity intact for 90 minutes in a fire; the class is chosen as EI90 or EW90, as the project requires. The door of an escape stair serving a basement or more than 4 storeys, a fire safety lobby and the exit door of a boiler room need at least 90 minutes. A door in a 180-minute fire wall is also 90 minutes.
- The letters in the class
- E integrity · I insulation · W radiation
- Stair going down to a basement
- At least 90 min
- Fire safety lobby
- At least 90 min
- Boiler room exit
- At least 90 min
- Polflam EI90 glass
- 32 mm
01 Needed?
Does your door need 90 minutes?
Choose the location; the minute scale sets the duration that location requires beside a 60, 90 and 120-minute door.
1Location
Does it go down to a basement?
2Wall rating, min
90minutesminimum · this location
The escape stair serves 6 storeys, i.e. more than 4: the door needs at least 90 minutes and 90 minutes is enough.
- 90 minutes is enoughGlass 32 mm
- Smoke-tightRequired by the article
- Self-closingWith a closer
- Report for its own typeSingle or double
Source: BYKHY 25(2), 34(2), 38(3), 47(3), 54(5), 157(1)
02 What the door needs
What to look for in a 90-minute door
First the door of a stair going down to the basement, then the boiler room exit; tap a view and it stays put.
1 / 2 · Door of a stair going down to the basementCamera on the stair's basement landing; fire in the basement corridor.
- DurationThe door of a stair going down to the basement resists fire for at least 90 minutes.
- AccessThe door is self-closing; it allows a firefighter or staff member to enter from outside when needed.
- GlassA glazed 90-minute door is fitted with 32 mm thick Polflam EI90 glass.
Source: BYKHY 47(3); Polflam catalogue
2 / 2 · Exit door of a boiler roomCamera in the basement corridor; the boiler room is on fire.
- DurationThe exit door of a boiler room resists fire for at least 90 minutes and does not let smoke through.
- CloserThe door is capable of closing by itself.
- DirectionWhere there are several exit doors, they are placed in opposite directions as far as possible.
Source: BYKHY 54(5)
03 Building section
Where are the 90-minute doors in a building?
A building with a basement, ground floor and four upper floors: escape stair, lobby and boiler room in the basement, fire wall towards the neighbouring building. Choose a rule; its place in the section appears in orange.
What do EI90 and EW90 tell you?
In the Annex 3/A table, E denotes integrity and I insulation; the number next to the letters is minutes. An EI90 door maintains these two properties for 90 minutes in a fire; an EW90 door keeps its integrity for 90 minutes and limits radiated heat.
ExampleThe class line for the second-floor stair door reads EI 90 or EW 90.
Source: BYKHY Annex 3/A
90 minutes on a stair serving a basement or more than 4 storeys
In a new building, if the escape stair serves basement floors or more than 4 storeys, its doors resist fire for at least 90 minutes. These doors do not let smoke through and are self-closing.
ExampleThe stair in the section serves the basement, the ground floor and four upper floors: all six doors are 90.
Source: BYKHY 47(3)
Stair core: wall 120, door 90 minutes
The wall of the stair core needs 120 minutes and its door 90; the door also does not let smoke through. The 60 minutes in 47(3) for a building with few storeys is assessed in the project alongside this article.
ExampleIn the section, the stair wall is 120 and the floor door 90.
Source: BYKHY 38(3), 47(3)
90-minute door in a fire safety lobby
The lobby is separated from the other parts by a wall of at least 120 minutes and a smoke-tight door of at least 90 minutes.
ExampleThe lobby in front of the stair in the basement: wall 120, door 90.
Source: BYKHY 34(2)
Boiler room exit door: 90 minutes
Every door leading out of a boiler room needs at least 90 minutes; the door does not let smoke through and is self-closing. Several doors are placed in opposite directions as far as possible.
ExampleThe door of the basement boiler room opening onto the corridor: 90.
Source: BYKHY 54(5)
Door in a 180-minute fire wall: 90 minutes
A fire wall separating adjoining buildings is designed with a fire resistance of at least 90 minutes; a door in it carries at least half the wall's duration.
ExampleGround-floor door in the 180-minute wall towards the neighbouring building: 90.
Source: BYKHY 25(1), 25(2)
04 Four locations
Where are 90-minute fire doors used?
Four buildings, four doors; choose a location and the duration required of that door appears beside it.
Fire side
Escape side
- In a multi-storey residential building The stair of a ten-storey residential building serves more than 4 storeys; every floor door resists fire for at least 90 minutes and is self-closing. BYKHY 47(3)90 Fire escape stair door page
- In a shopping centre car park The door from the basement car park into the stair lobby is the door of a stair serving the basement: at least 90 minutes and smoke-tight. BYKHY 47(3)90 Shopping centre page
- In an old office building In an existing building 30.50 m high or more, the stair door resists fire for at least 90 minutes; the door is at least 70 cm wide and 190 cm high. BYKHY 157(1)90 New and existing buildings page
- In a factory fire wall A door in a 180-minute fire wall carries half the wall's duration: at least 90 minutes, self-closing and not letting smoke through. BYKHY 25(2)90 Factory and warehouse page
05 Your project
Which doors in your project must be 90 minutes?
Your answers to four questions show the 90-minute doors.
- 01
Does the stair go down to the basement?
All floor doors of a stair going down to a basement are 90 minutes.
- 02
How many storeys does the stair serve?
If more than 4, 90 minutes; at exactly 4 storeys the duration is settled in the project.
- 03
Is there a lobby or a boiler room?
The doors of a fire safety lobby and a boiler room need 90 minutes.
- 04
Is the door in a fire wall?
The door carries half the wall's duration: 90 in a 180-minute wall.
Send your section and we will mark the 90-minute doors together. The number of storeys, the basement and the door locations are enough.
Send the section06 Products
Which glazed doors are made for 90 minutes?
Aliplast FR90 profile and 32 mm Polflam EI90 glass; in the FR90 door the duration goes up to 90 minutes (EI90).
FR90
Single leaf
Stair, lobby and boiler room doors; 30 to 90 minutes. Single leaf
FR90
Double leaf
Double-leaf door for car parks and wide openings; up to 90 minutes in the Aliplast range. Double leaf
FR90
With side lights
The door up to 90, the fixed glass beside it up to 120 minutes. With side lights
The lobby's 120-minute glazed wall carries a class separate from the door. Frameless glass partition
Abay Yapı Sistemleri
Trusted for 30 years.
We make 90-minute doors with Aliplast FR90 profiles and 32 mm Polflam glass, to each project's dimensions in our Istanbul workshop.
- 154
- corporate references
- Aliplast
- authorised manufacturer and distributor in Turkey
- Polflam
- partner for fire-resistant glass
- Istanbul
- head office and production, Istanbul



- 01Project and useBuilding type, required rating, door location
- 02Size and openingOverall size, clear width, opening direction
- 03System and hardwareProfile, glass, lock, closer
- 04Quote and productionScope agreed, delivered with the document set
Projects
Stair, lobby and plant room doors from our reference projects.
Doors we have installed in stair cores, lobbies and plant rooms. Tap a photo to enlarge it and use the arrows to move on.
07 Document set
Which document states the 90 minutes of the door?
The door's duration is in the classification report for its own type; the glass's 32 mm and its class are in the Polflam declaration.
Four checks at handover
- Class. The report's class line must read the class the project requires, at least EI 90 or EW 90.
- Type. The report must cover the door's own type: single leaf, double leaf or with side lights.
- Smoke. At stair, lobby and boiler room doors the article also requires smoke-tightness.
- Glass. The door uses the 32 mm EI90 glass tested in the report.
- CatalogueAliplast FR90 door systemEI 30 · EI 60 · EI 90Document centre
- Test reportFR90 double-leaf glazed doorITB 2020 · no flame through for 98 minutes, insulation 97 minutesDocument centre
- DeclarationPolflam EI90 glass32 mmDocument centre
- AuthorisationAliplast manufacturing authorisationAbay Yapı's manufacturing authorisationDocument centre
Source: Aliplast and Polflam documents
Request the document set for your 90-minute doors. The contents of the set depend on the door's type and size.
Document centre08 FAQ
About 90-minute fire doors
The duration of basement, lobby and boiler room doors can be read from the section. Send your section and we will mark together which door needs 90 minutes.
What do EI90 and EW90 mean?
In EI90, E stands for integrity and I for insulation; 90 is the number of minutes the door maintains these two properties in a fire. In EW90, W takes the place of I: the door keeps its integrity for 90 minutes and limits radiated heat. The meanings of the letters are given in the regulation's Annex 3/A table.
Source: BYKHY Annex 3/A
Where are 90-minute fire doors mandatory?
At least 90 minutes is required at the door of an escape stair serving a basement or more than 4 storeys, at the door of a fire safety lobby and at the exit doors of a boiler room. A door in a 180-minute fire wall and the stair door of an existing building 30.50 m or higher are also 90 minutes.
Source: BYKHY 25(2), 34(2), 47(3), 54(5), 157(1)
How thick is EI90 fire glass?
Polflam EI90 glass is 32 mm, 7 mm thicker than EI60 glass. The door's class is set not by the glass thickness alone but by the report in which the glass was tested together with the profile.
Source: Polflam catalogue
How many minutes should a basement fire door resist?
If the escape stair serves basement floors, its doors resist fire for at least 90 minutes, do not let smoke through and are self-closing. The exit doors of a boiler room in the basement also need 90 minutes.
Source: BYKHY 47(3), 54(5)
Is an escape stair door 60 or 90 minutes?
In a new building, 47(3) specifies 60 minutes on a stair serving fewer than 4 storeys and 90 minutes on one serving a basement or more than 4 storeys. 38(3), however, gives 90 minutes to the door separating the stair from the other parts; the duration is settled in the project by reading the two articles together.
Source: BYKHY 38(3), 47(3)
How many minutes should a fire safety lobby door resist?
The lobby door resists fire for at least 90 minutes and its wall for at least 120; the door does not let smoke through and is self-closing. The lobby's glazed wall also carries the 120-minute class.
Source: BYKHY 34(2), 47(3)
What is the difference between 90 and 120 minutes?
The difference is 30 minutes. A door in a 240-minute fire wall needs 120 minutes, half the wall's duration, and 90 minutes is not enough. In a high-rise building the shaft wall is 120 and the shaft hatch 90 minutes; walls where 120 minutes is required are on the 120-minute fire resistance page.
Source: BYKHY 25(2), 25(3)