S120Fire criteria · duration

120-minute fire resistance

120-minute fire resistance means that a wall, glass partition or glass keeps its integrity (E) for 120 minutes in a fire; depending on the project, the class is EI120 (insulated) or EW120 (radiation-limited). The walls of an escape stair and a fire safety lobby, the partitions of a boiler room and shaft walls in a high-rise building need at least 120 minutes; for a door in these walls the regulation specifies 90 minutes.

EI120 fire resistance Turkey – frameless glass wall and door
Frameless 120-minute glass wall
The letters in EI120
E integrity · I insulation
Stair and lobby walls
At least 120 min
The door in this wall
At least 90 min
Boiler room partition
At least 120 min
Polflam EI120 glass
35 / 40 mm

01 How many minutes?

How many minutes must your wall and door resist?

Choose the location; the ruler compares the time required for the glazed wall and the door with the limits of the FR90 door and the 120-minute glass.

1Location

120minutesminimum · glazed wall

The wall separating a stair core needs at least 120 minutes and its door at least 90; the door also does not let smoke through. A 120-minute partition is enough for the glazed wall and a 90-minute door for the door.

  • Glass wall 120 minGlass 35 / 40 mm
  • Door 90 minFR90 door
  • Smoke-tight doorRequired by the article
  • The partition's own reportFramed or frameless

Source: BYKHY 25(2), 25(3), 34(2), 38(3), 54(2), 54(5), 57(3)

060120180240minutesglazed walldoorFR90 door120 min glassMINUTE SCALE · diagram–
Glazed wallDoorFR90 door120 min glass

02 Glazed wall

What to look for in a 120-minute glazed wall

First the glazed wall of a stair core, then the fire safety lobby; tap a view and it stays where it is.

EI120 glass partition Turkey – wall separating the stair from the floor

1 / 2 · Glazed wall of a stair coreCamera on the stair landing; fire on the office floor.

Wall≥ 120 minDoor≥ 90 min

  1. WallThe glazed wall separating the stair resists fire for at least 120 minutes; in a framed partition the glass is 35 or 40 mm.
  2. DoorThe door in the wall needs at least 90 minutes and does not let smoke through.
  3. JunctionThe door and the glazed wall are on the same line; each carries its own class with its own report.

Source: BYKHY 38(3); Polflam catalogue

03 Building section

Where are the 120-minute walls in a building?

The building in the section has five storeys and a basement: the stair and the lobby on each floor, a vertical shaft, the boiler room and fuel store in the basement, and the fire wall facing the neighbouring building. Tap one of the rules; its place is drawn in orange in the section.

What does EI120 tell you?

The letter E stands for integrity and the letter I for insulation. A glazed wall in class EI120 maintains these two properties for 120 minutes in a fire. In EW120, the W that replaces I shows that heat radiation stays limited.

ExampleLobby wall on the third floor in the section: EI 120.

Source: BYKHY Annex 3/A

boilerfuelbasementneighbouring buildingstairlobbyshaftfire wallground + 4 floorsBUILDING SECTION · diagramEI 120123456
Floor and wallSelected rule

04 Four locations

Where are 120-minute glass partitions used?

Four buildings, four partitions; choose a location and the duration required there appears beside it.

05 Your project

Which walls in your project must be 120 minutes?

The answers to these four questions separate the 120-minute walls from the 90-minute doors.

  1. 01

    What does the glazed wall separate?

    Stair, lobby, boiler room or kitchen: in all four the wall needs 120 minutes.

  2. 02

    Is there a door in the wall?

    90 minutes is enough for the door of a stair, lobby or boiler room.

  3. 03

    Is it in a fire wall?

    Fixed glass and doors carry half the wall's duration: 120 in a 240-minute wall.

  4. 04

    Framed or frameless?

    Both are made for 120 minutes; in the frameless version the panes join without mullions.

Send your plan and we will mark the 120-minute walls together. A floor plan and the partition locations are enough.

Send the plan

06 Products

Which glazed systems resist fire for 120 minutes?

Aliplast FR90 profile and Polflam glass: 120 minutes in a glazed wall and fixed glass; in a door up to 90 minutes (EI90).

  1. BR + FR90

    Frameless partition

    The panes join without mullions; BR EI120 glass is 50 mm. Frameless glass partition

  2. FR90

    Fixed glass partition

    Framed partition up to 120 minutes; glass 35 or 40 mm. Fixed partition

  3. FR90

    Door with side lights

    The fixed glass beside the door goes up to 120 minutes; the door is 90 minutes in FR90 (EI90). With side lights

For a door in a 120-minute wall, the regulation specifies 90 minutes. 90-minute fire door

Abay Yapı Sistemleri

Trusted for 30 years.

We make 120-minute glass partitions with Aliplast FR90 profiles and Polflam glass in our Istanbul workshop, to the project's dimensions.

154
corporate references
Aliplast
authorised manufacturer and distributor in Turkey
Polflam
partner for fire-resistant glass
Istanbul
head office and production, Istanbul
EI120 glass partition project Turkey – glass partition and glazed doors in a stair hallEI120 glass partition project Turkey – glass partition between stair lobby and officeEI120 glass partition project Turkey – black-framed door and glass partition in a corridorEI120 glass partition project Turkey – glass partition and door enclosing a meeting roomEI120 glass partition project Turkey – double leaf with side and top panels
Stair hall · Glass partition
30yearsof trusted manufacturing and installation
  1. 01Project and useBuilding type, required rating, door location
  2. 02Size and openingOverall size, clear width, opening direction
  3. 03System and hardwareProfile, glass, lock, closer
  4. 04Quote and productionScope agreed, delivered with the document set

Projects

Glass partitions and fixed-glass lines from our reference projects.

Projects where we have installed glass walls and partitions; below, the doors on the same lines. Tap a photo to enlarge it and use the arrows to move on.

07 Document set

Which document states the partition's 120 minutes?

The partition's duration is in the test document for its own type; the thickness and class of the glass are in the Polflam declaration.

Four checks at handover

  1. Class. The partition's document must state at least 120 minutes, with the class required in the project (EI 120 or EW 120).
  2. Type. The document must cover the partition's own type: framed or frameless.
  3. Size. The partition to be built must not exceed the height and glass size tested in the document.
  4. Door. The 90 minutes of the door in the wall are shown in a separate document.
  • Test resultPolflam BR EI120 + Aliplast FR90Frameless partition · EI 120Document centre
  • DeclarationPolflam EI120 glass35 / 40 mmDocument centre
  • CatalogueAliplast FR90 partitionEI 30 – EI 120Document centre
  • AuthorisationAliplast manufacturing authorisationAbay Yapı's manufacturing authorisationDocument centre

Source: Aliplast and Polflam documents

Request the documents for your 120-minute partitions. The documents are compiled for the partition's type and size.

Document centre

08 FAQ

About 120-minute fire resistance

Which wall needs 120 minutes and which door 90 can be seen on the plan. Send your plan and we will sort them out together.

0216 428 38 20Send a question

What does EI120 mean?

EI120 describes a wall, partition or glass that does not lose its integrity (E) and insulation (I) for two hours in a fire; the meanings of the letters are in the regulation's Annex 3/A table.

Source: BYKHY Annex 3/A

Where is 120-minute fire resistance mandatory?

Walls separating an escape stair and a fire safety lobby, boiler room partitions, the separation between the fuel store and the boiler room, kitchen partitions and shaft walls in a high-rise building need at least 120 minutes.

Source: BYKHY 25(3), 34(2), 38(3), 54(2), 56(1), 57(3)

How many minutes should a door in a 120-minute wall resist?

For a door in the 120-minute wall of a stair, lobby or boiler room, the regulation specifies at least 90 minutes. Where the door itself needs 120 minutes is a 240-minute fire wall.

Source: BYKHY 25(2), 34(2), 38(3), 54(5)

How thick is 120-minute fire-rated glass?

In a framed partition Polflam EI120 glass is 35 or 40 mm; in a frameless partition Polflam BR EI120 glass is 50 mm. The partition's class is set by the report in which glass and profile were tested together.

Source: Polflam catalogue

Can a frameless glass partition resist fire for 120 minutes?

Yes. A partition whose panes join without mullions has been tested for 120 minutes with Polflam BR EI120 glass and an Aliplast FR90 perimeter profile.

Source: Polflam BR EI120 + Aliplast FR90 test result

How many minutes should a boiler room wall resist?

The partitions separating a boiler room from the rest of the building resist fire for at least 120 minutes; the partition between it and the fuel store is also 120 minutes. The exit doors need 90 minutes.

Source: BYKHY 54(2), 54(5), 56(1)

What does separating the basement with a 120-minute partition achieve?

In a residential building, a basement whose entrance, exit and shafts are separated from the upper floors by a 120-minute floor slab or partition is not counted in the total building height and is assessed separately for fire safety measures.

Source: BYKHY 48(7)

→ Quote

Tell us about your 120-minute partitions.

Write the partition's location, length and height: our technical team will determine whether it should be framed or frameless, the class and the document set, and get back to you.

Call · 0216 428 38 20Email

Production
Istanbul

Quote form* required field

CallRequest a quote